PLEASE NOTE This user’s manual includes the latest information at the time of printing. ClipperCreek, Inc. reserves the right to make changes to this product without further notice. Changes or modifications to this product by other than an authorized service facility may void the product warranty.
électriques et les pratiques courantes de prévention des accidents. Instructions Pertaining to a Risk of Fire or Electric Shock When using the the LCS, basic electrical safety precautions should be followed: • Use this charge station to charge electric vehicles equipped with an charge port only.
Page 6
Instructions se Rapportant à un Risque d’Incendie ou de Choc Électrique Lorsque l’utilisation de la LCS, précautions fondamentale de sécurité électrique doivent être suivies: • Utilisez cette station de recharge pour charger les véhicules électriques équipés d’un SAE-J1772...
Le LCS n’est pas équipé pour contrôler les ventilateurs. Ne chargez pas le véhicule avec les LCS si la ventilation est nécessaire. CAUTION: DO NOT CHARGE a vehicle indoors if it requires ventilation.
Within a few seconds the green “Charging” light on the face of the LCS will turn on and the charging cycle will begin. After an av- erage driving day the vehicle battery pack will require several hours to recharge completely.
LCS User’s Manual THE LCS FRONT PANEL The front panel on the LCS has four indicator lights: POWER (yellow), indicates that power is available to the LCS. CHARGING (green), indicates that the vehicle is requesting a charge and AC power is currently applied to the vehicle.
(généralement utilisé comme Neutre) doit être mis à la terre quelque part dans le système. Une connexion Neutre n’est pas exigée par la LCS. Seulement ligne 1, ligne 2, et Mise à la Terre sont nécessaires, comme le montre la Figure 3.
Page 11
Notice that L1, L2, & Ground are labeled on each diagram. Those transformer outputs correspond to the same inputs on the LCS. Also, each of the two 3-phase diagrams shows an L3 output, which is not used. Do not connect all three phases of a 3-phase secondary to the LCS.
Page 12
With a wye-connected secondary, any two of the legs can be used to provide 208V to the LCS. For example, L1 & L2, or L1 & L3, or L2 & L3. Leave the unused leg open. Do not connect it to a Neutral bar, or to Ground.
Page 13
LCS User’s Manual L3 (DO NOT USE!) 240V 120V NEUTRAL (NOT USED) 120V GROUND Figure 4 - 240V 3-Phase, Delta-Connected, with center-tap on one leg CAUTION: With the delta connection, one leg must be center-tapped. Only the two phases on either side of the center tap can be used. The two phases must both measure 120V to Neutral.
LCS. No “Neutral” point is available to be connected to ground for ground-fault protection. The LCS will not allow the contactor to close if it does not sense the presence of a Ground wire connected to a “Neutral” point on the transformer secondary.
Page 15
Machine screw size #10 hardware is recommended for mounting the LCS. Screw shafts of at least 2” are recommended. The LCS mounting holes are 3/16” in diameter, so ensure that the screw heads do not exceed this size. Place appropriately sized washers between the screw heads and the LCS enclosure mounting flanges.
• The vertical alignment of the LCS and SAE-J1772™ connector holster mounting holes allows for the convenient mounting of both components onto the same post or wall structure. For example, the holster may be mounted directly above the LCS.
WIRING INSTRUCTIONS (Hardwired LCS) Route the LCS conduit to a nearby service panel or junction box. Use the included ¼” trade size watertight fitting to provide a moisture-resistant seal with the service panel or junction box. If necessary, drill a 1/2” diameter hole to accommodate the liquid-tight fitting or use the included 1/4”...
The plug extends from the top of the LCS enclosure. Regulations limit this plug to a maximum of 12 inches in length. For this reason, the LCS-P must be mounted below the NEMA receptacle and must also be located within 12 inches of it.
électricien qualifié. MOVING & STORAGE INSTRUCTIONS Note that both the hardwired LCS and the plug-in LCS-P are intended for fixed installations. For mounting requirements, consult the Mounting Procedures section of the Installation Instructions in this manual.
PLEASE HAVE THE MODEL NUMBER AND SERIAL NUMBER AVAILABLE WHEN YOU CALL. This information is printed on the label on the side of the LCS enclosure. If your call is made after business hours or on weekends, please leave your name, telephone number, the unit serial number, and a brief description of the problem.
25 ft (7.6M) Note that the maximum current for the vehicle is set by the duty cycle of the Pilot waveform. Output power is variable depending upon the LCS model and vehicle demand. Plugs: Attached NEMA L6-30P, NEMA 14-30P, NEMA 6-50P and NEMA 14-50P plugs are available for the LCS-20P, LCS-25P and LCS-30P.
(first use). The product installation date must be evidenced and communicated to ClipperCreek by way of the warranty registration card (or its equivalent). The warranty registration card must be filled out completely and accurately, and returned to ClipperCreek within 30 days after installation, and the product installation date shall be within 6 months after the purchase date.