Dimensions EDUS041111_a 4. Dimensions Indoor Unit FTXN09/12KEVJU AIR FLOW (INDOOR) THE MARK (®) SHOWS PIPING DIRECTION REAR 30-5/16(770mm) RIGHT LEFT INCLUDING MOUNTING PLATE 7-7/8(200mm) 1-15/16(50mm)MIN. 1-15/16(50mm)MIN. 7-51/64(198mm) (SPACE FOR (SPACE FOR REQUIRED SPACE FRONT PANEL FIXING SCREWS MAINTENANCE) MAINTENANCE) (INSIDE) GENERAL RATING NAME PLATE SIGNAL RECEIVER...
Wiring Diagrams EDUS041111_a 5. Wiring Diagrams Indoor Unit FTXN09/12KEVJU PCB 1 PCB 2 FIELD WIRING. TRANSMISSION GRN/YLW LED1 CIRCUIT LED2 RECTIFIER OUTDOOR – MR10 CAUTION NOTE THAT OPERATION WILL 3.15A t° RESTART AUTOMATICALLY IF – THE MAIN POWER SUPPLY IS IPM200 TURNED OFF AND THEN BACK SIGNAL...
Page 16
EDUS041111_a Wiring Diagrams Outdoor Unit RKN09/12KEVJU, RXN09/12KEVJU FIELD WIRING indoor outdoor IN CASE OF NOTE IN CASE OF HEAT PUMP 1.REFER TO THE NAMEPLATE FOR THE POWER REQUIREMENTS. COOLING ONLY TYPE TYPE C5 , C6, C119 : CAPACITOR DB1 , DB2 , DB3 : DIODE BRIDGE (OUTDOOR) (DISCHARGE)
EDUS041111_a Piping Diagrams Outdoor Unit RKN09/12KEVJU OUTDOOR UNIT HEAT EXCHANGER 9/32CuT 9/32CuT MOTOR OPERATED VALVE 3/16CuT 1/4CuT 1/4CuT 3/16CuT MUFFLER WITH MOTOR FILTER PROPELLER FAN FIELD PIPING (1/4CuT) LIQUID STOP VALVE REFRIGERANT FLOW MUFFLER MUFFLER 3/8CuT FIELD PIPING DISCHARGE PIPE COOLING COMPRESSOR (3/8CuT)
Page 19
Piping Diagrams EDUS041111_a RXN09/12KEVJU OUTDOOR UNIT OUTDOOR TEMPERATURE HEAT EXCHANGER 9/32CuT THERMISTOR 9/32CuT MOTOR OPERATED VALVE 3/16CuT 1/4CuT 1/4CuT 3/16CuT MUFFLER WITH MOTOR FILTER PROPELLER FAN 3/8CuT FOUR WAY VALVE ON : HEATING FIELD PIPING (1/4CuT) LIQUID STOP VALVE REFRIGERANT FLOW MUFFLER MUFFLER FIELD PIPING 3/8CuT...
Page 26
EDUS041111_a Capacity Tables Symbols: Note: : Airflow rate /min.) 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat. : Bypass factor shows nominal (rated) capacities and power input. 3. TC, PI and SHC must be calculated by interpolation using the figures in the : Entering wet bulb temp.
Page 28
EDUS041111_a Capacity Tables Symbols: Note: : Airflow rate /min.) 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat. : Bypass factor shows nominal (rated) capacities and power input. 3. TC, PI and SHC must be calculated by interpolation using the figures in the : Entering wet bulb temp.
Page 30
EDUS041111_a Capacity Tables Symbols: Note: : Airflow rate /min.) 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat. : Bypass factor shows nominal (rated) capacities and power input. 3. TC, PI and SHC must be calculated by interpolation using the figures in the : Entering wet bulb temp.
Page 32
EDUS041111_a Capacity Tables Symbols: Note: : Airflow rate /min.) 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat. : Bypass factor shows nominal (rated) capacities and power input. 3. TC, PI and SHC must be calculated by interpolation using the figures in the : Entering wet bulb temp.
Page 34
EDUS041111_a Capacity Tables Symbols: Note: : Airflow rate /min.) 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat. : Bypass factor shows nominal (rated) capacities and power input. 3. TC, PI and SHC must be calculated by interpolation using the figures in : Entering wet bulb temp.
Capacity Tables EDUS041111_a Capacity Correction Factor by the Length of Refrigerant Piping (Reference) The cooling capacity and the heating capacity of the unit have to <— line : cooling capacity> be corrected in accordance with the length of refrigerant piping — <--- line : heating capacity>...
Page 36
EDUS041111_a Capacity Tables 7.3.3 24 Class R-410A (24 class) Range of the Refrigerant Additional Charge 16.4 32.8 49.2 65.6 82.0 Piping length (ft) Note: The graphs show the factor when additional refrigerant of the proper quantity is charged. Room Air Conditioners K-Series...
Operation Limit EDUS041111_a 8. Operation Limit RKN09/12KEVJU Cooling 114.8 57.2 73.4 82.4 Indoor temp.(°FWB) The graphs are based Note: Operation can be extended to 0ºF in cooling on the following conditions. with use of the optional wind baffle. · Equivalent piping length 25ft ·...
Page 38
EDUS041111_a Operation Limit RXN09/12KEVJU Heating Cooling 64.4 114.8 (5 °FDB) 57.2 73.4 82.4 Indoor temp.(°FWB) The graphs are based Note: Operation can be extended to 0ºF in cooling Indoor temp.(°FDB) on the following conditions. with use of the optional wind baffle. ·...
Sound Level EDUS041111_a 9. Sound Level Measuring Location Note: Indoor Unit 1. Operation sound is measured in an anechoic chamber. Single Split Duct-Free System 2. The data are based on the conditions shown in the table 3.3 ft below. (R5162) Outdoor Unit 3.3 ft (R4796)
Electric Characteristics EDUS041111_a 10. Electric Characteristics Power Supply COMP Indoor Unit Outdoor Unit Hz - Volts Voltage Range 60 - 208 0.19 0.20 MAX. 60 Hz 253 V FTXN09KEVJU RKN09KEVJU — MIN. 60 Hz 187 V 60 - 230 0.17 0.18 60 - 208 0.19...
EDUS041111_a Installation Manual 11. Installation Manual 11.1 Indoor Unit - 09/12 Class Read these SAFETY CONSIDERATIONS for Installation carefully installation manual. Improper installation may result in water leakage, electric shock, or fire. before installing an air conditioner or heat pump. After completing •...
Page 45
Installation Manual EDUS041111_a parts other than those specified by Daikin are used, operation is not possible when connected to other fire or explosion may occur. units. • Do not touch the switch with wet fingers. Touching a • Remote controller (wireless kit) transmitting distance switch with wet fingers can cause electric shock.
Page 47
Installation Manual EDUS041111_a Preparation before Installation Removing and installing front panel • Removal method Hook fingers on the tabs on the left and right of the main body, and open until the panel stops. Slide the front panel sideways to disengage the rotating shaft.
Page 48
EDUS041111_a Installation Manual Indoor Unit Installation Drawings How to attach the indoor unit Mounting Hook the claws of the bottom frame plate to the mounting plate. If the claws are difficult to hook, remove the front grille. Clip Mounting plate How to remove the indoor unit Push up the marked area (at the lower part of the front grille) to...
Page 49
Installation Manual EDUS041111_a Indoor Unit Installation Installing the mounting plate • The mounting plate should be installed on a wall which can support the weight of the indoor unit. 1) Temporarily secure the mounting plate to the wall, make sure that the plate is completely level, and mark the boring points on the wall.
Page 50
EDUS041111_a Installation Manual Boring a wall hole and installing wall embedded pipe • For walls containing metal frame or metal board, be sure to use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire. Inside Outside •...
Page 51
Installation Manual EDUS041111_a Indoor Unit Installation 3-2. Left-side, left-back, or left-bottom piping How to replace the drain plug and drain hose Drain hose attachment position • Replacing onto the left side * The drain hose is on the back of the unit. 1) Remove the insulation fixing screws on the right and remove the drain hose.
Page 52
EDUS041111_a Installation Manual Wiring 1) As shown in the illustration, insert the wires including the ground wire into the conduit and secure them with lock nut onto the conduit mounting plate. 2) Strip wire ends (9/16 inch (15mm)). 3) Match wire colors with terminal numbers on indoor and outdoor unit’s terminal blocks and firmly screw wires to the corresponding terminals.
Page 53
Installation Manual EDUS041111_a Indoor Unit Installation 5-5. Prepare the accessory (separate product) [Figure 2]. 1) Remove the cover from the accessory (separate product). 2) Insert the connection cord into connector “S21” (white) in the accessory (separate product). 3) Route each of the connection cords through the cut-outs in the accessory, then reinstall the accessory cover in its original position.
Page 54
EDUS041111_a Installation Manual Drain piping The drain hose should be inclined downward. 1) Connect the drain hose, as described right. No trap is permitted. Do not put the end of the hose in water. 2) Remove the air filters and pour some water into the drain pan to check the water flows smoothly.
Page 55
Installation Manual EDUS041111_a Refrigerant Piping Work Refrigerant piping CAUTION • Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.) • To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.) •...
Page 56
EDUS041111_a Installation Manual Trial Operation and Testing Trial operation and testing 1-1 Measure the supply voltage and make sure that it falls in the specified range. 1-2 Trial operation should be carried out in either cooling or heating mode. For Heat pump •...
Daikin are used, • Only qualified personnel must carry out the installation fire or explosion may occur.
Page 58
EDUS041111_a Installation Manual • Do not allow children to play on or around the unit to Install the indoor unit far away from fluorescent lamps prevent injury. as much as possible. • Indoor units are for indoor installation only. Outdoor •...
Page 59
Installation Manual EDUS041111_a Accessories Room Air Conditioners K-Series...
Page 60
EDUS041111_a Installation Manual Room Air Conditioners K-Series...
Page 61
Installation Manual EDUS041111_a Room Air Conditioners K-Series...
Page 62
EDUS041111_a Installation Manual Room Air Conditioners K-Series...
Page 63
Installation Manual EDUS041111_a Room Air Conditioners K-Series...
Page 64
EDUS041111_a Installation Manual Room Air Conditioners K-Series...
Page 65
Installation Manual EDUS041111_a Room Air Conditioners K-Series...
Page 66
EDUS041111_a Installation Manual Room Air Conditioners K-Series...
Page 67
Installation Manual EDUS041111_a Room Air Conditioners K-Series...
Page 68
EDUS041111_a Installation Manual 3P276866-2 Room Air Conditioners K-Series...
Daikin are used, • Only qualified personnel must carry out the installation fire or explosion may occur.
Page 70
EDUS041111_a Installation Manual • Do not allow children to play on or around the unit to • Remote controller (wireless kit) transmitting distance prevent injury. can be shorter than expected in rooms with electronic fluorescent lamps (inverter or rapid start types). •...
Page 71
Installation Manual EDUS041111_a Accessories Accessories Accessories supplied with the outdoor unit: (B) Drain plug (Heat pump models) (A) Installation manual There is on the bottom packing case. Room Air Conditioners K-Series...
Page 72
EDUS041111_a Installation Manual Precautions for Selecting the Location 1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified. 2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a nuisance to the neighbors of the user.
Page 73
Installation Manual EDUS041111_a Installation Guidelines • Where a wall or other obstacle is in the path of outdoor unit’s inlet or outlet airflow, follow the installation guidelines below. • For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less. Wall facing one side Walls facing two sides More than 1-15/16 (50)
Page 74
EDUS041111_a Installation Manual Flaring the pipe end (Cut exactly at 1) Cut the pipe end with a pipe cutter. right angles.) Remove burrs. 2) Remove burrs with the cut surface facing Flaring downward so that the chips do not enter the pipe. Set exactly at the position shown below.
Page 75
Installation Manual EDUS041111_a Outdoor Unit Installation Purging air and checking gas leakage • When piping work is completed, it is necessary to purge the air and check for gas leakage. WARNING • Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle. •...
Page 76
EDUS041111_a Installation Manual Refilling the refrigerant Check the type of refrigerant to be used on the machine nameplate. Precautions when adding R410A Fill from the liquid pipe in liquid form. It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation. 1) Before filling, check whether the cylinder has a siphon attached or not.
Page 77
Installation Manual EDUS041111_a Pump Down Operation In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 1) Remove the valve cap from liquid stop valve and gas stop valve. Hexagonal 2) Carry out forced cooling operation. wrench Liquid 3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
Page 78
EDUS041111_a Installation Manual Wiring WARNING • Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire. • Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fire.
Page 79
Installation Manual EDUS041111_a Wiring CAUTION • When connecting the connection wires to the terminal board using a single core wire, be sure to perform curling. Problems with the work may cause heat and fires. Excessive strip length Strip wire end may cause electrical to this point.
Daikin are used, • Only qualified personnel must carry out the installation fire or explosion may occur.
Page 81
Installation Manual EDUS041111_a • Do not allow children to play on or around the unit to Install the indoor unit far away from fluorescent lamps prevent injury. as much as possible. • Indoor units are for indoor installation only. Outdoor •...
Page 82
EDUS041111_a Installation Manual Accessories Accessories supplied with the outdoor unit: (B) Drain plug (Heat pump models) There is on the bottom packing case. Precautions for Selecting the Location Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplifi ed. Choose a location where the hot air discharged from the unit or the operation noise will not cause a nuisance to the neighbors of the user.
Page 83
Installation Manual EDUS041111_a Room Air Conditioners K-Series...
Page 84
EDUS041111_a Installation Manual Installation Guidelines • Where a wall or other obstacle is in the path of outdoor unit’s inlet or outlet airfl ow, follow the installation guidelines below. • For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less. Wall facing one side Walls facing two sides More than...
Page 85
Installation Manual EDUS041111_a Outdoor Unit Installation Flaring the pipe end (Cut exactly at Cut the pipe end with a pipe cutter. right angles.) Remove burrs. Remove burrs with the cut surface facing Flaring downward so that the chips do not enter the pipe. Set exactly at the position shown below.
Page 86
EDUS041111_a Installation Manual Purging air and checking gas leakage • When piping work is completed, it is necessary to purge the air and check for gas leakage. WARNING • Do not mix any substance other than the specifi ed refrigerant (R410A) into the refrigeration cycle. •...
Page 87
Installation Manual EDUS041111_a Outdoor Unit Installation Refi lling the refrigerant Check the type of refrigerant to be used on the machine nameplate. Precautions when adding R410A Fill from the liquid pipe in liquid form. It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operatio n. Before fi lling, check whether the cylinder has a siphon attached or not.
Page 88
EDUS041111_a Installation Manual Room Air Conditioners K-Series...
Page 89
Installation Manual EDUS041111_a Wiring WARNING • Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fi • Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fi •...
Page 90
EDUS041111_a Installation Manual CAUTION • When connecting the connection wires to the terminal board using a single core wire, be sure to perform curling. Problems with the work may cause heat and fi res. Excessive strip length Strip wire end may cause electrical to this point.
Page 91
Installation Manual EDUS041111_a Trial Operation and Testing Trial operation and testing Measure the supply voltage and make sure that it falls in the specifi ed range. Trial operation should be carried out in either cooling or heating mode. For heat pump •...
Only use Meanings of DANGER, WARNING, CAUTION, and NOTE Symbols: accessories made by Daikin that are specifically designed for use with the equipment and have them installed by a professional. DANGER ....Indicates an imminently hazardous situation which, if not avoided, will •...
Page 93
Operation Manual EDUS041111_a • Placing a flower vase or other containers with water or • Do not place objects in direct proximity of the outside other liquids on the unit could cause a shock or fire if unit. Do not let leaves and other debris accumulate a spill occurs.
Page 94
EDUS041111_a Operation Manual • Pay Attention to Operating Sound. Be sure to use the following places: a. Places that can sufficiently withstand the weight of the air conditioner or heat pump yet can suppress the operating sound and vibration. b. Places where warm air from the air outlet of the outside unit or the operating sound of the outside unit does not annoy neighbors.
Page 95
Operation Manual EDUS041111_a Room Air Conditioners K-Series...
Page 96
EDUS041111_a Operation Manual Room Air Conditioners K-Series...
Page 97
Operation Manual EDUS041111_a Room Air Conditioners K-Series...
Page 98
EDUS041111_a Operation Manual Room Air Conditioners K-Series...
Page 99
Operation Manual EDUS041111_a Room Air Conditioners K-Series...
Page 100
EDUS041111_a Operation Manual Room Air Conditioners K-Series...
Page 101
Operation Manual EDUS041111_a Room Air Conditioners K-Series...
Inform customers that they should store this Operation leakage, electric shock, and fire. Only use Manual with the Installation Manual for future reference. accessories made by Daikin that are specifically designed for use with the equipment and have them Meanings of DANGER, WARNING, CAUTION, and NOTE Symbols: installed by a professional.
Page 122
EDUS041111_a Operation Manual • Do not touch the air outlet or horizontal blades while can cause the unit to malfunction, and cause smoke the swing flap is in operation because fingers could or fire when they make contact with electrical parts. get caught and injured.
Page 123
Operation Manual EDUS041111_a a. Places that can sufficiently withstand the weight of the air conditioner or heat pump yet can suppress the operating sound and vibration. b. Places where warm air from the air outlet of the outside unit or the operating sound of the outside unit does not annoy neighbors.
Page 124
EDUS041111_a Operation Manual Room Air Conditioners K-Series...
Page 125
Operation Manual EDUS041111_a Room Air Conditioners K-Series...
Page 126
EDUS041111_a Operation Manual Room Air Conditioners K-Series...
Page 127
Operation Manual EDUS041111_a Room Air Conditioners K-Series...
Page 128
EDUS041111_a Operation Manual Room Air Conditioners K-Series...
Page 129
Operation Manual EDUS041111_a Room Air Conditioners K-Series...
Page 130
EDUS041111_a Operation Manual Room Air Conditioners K-Series...
Optional Accessories EDUS041111_a 13.2 <BRC944B2> Wired Remote Controller 13.2.1 Installation Manual CAUTION 1. No switch box or staple is supplied. Prepare them locally. 2. No remote controller cord is supplied. Prepare the optional remote controller cord 4 wire. 3. Be sure to turn off the power to any apparatus connected prior to mounting. 4.
Page 150
EDUS041111_a Optional Accessories 2. Securing the remote control adapter Double-face adhesive tape Remove the upper case of the remote control adapter and secure the lower case assembly. Wood screws (φ3.5mm x 16mm) (Mounting with supplied wood screws) (Mounting with supplied double-face adhesive tape) 3.
Page 151
Optional Accessories EDUS041111_a 13.2.2 Operation Manual Controller Commands and their Corresponding Functions Run indicator lamp (green) ON/OFF button Display Press to start the system. Displays the operating Displays the operating Press again to stop the system. conditions. conditions. Timer select button Mode select button Selects one of the following: ONE TIME timer ON...
Page 152
EDUS041111_a Optional Accessories Preparation before Operation Checking the power If nothing appears on the remote controller's display, turn on the circuit breaker. Setting the current time Press The current time starts blinking. lights up. 1 · 3 Press and set the current time.
Page 153
Optional Accessories EDUS041111_a Preparation before Operation Setting Temperature Indication change Temperature indication can be changed between Celsius and Fahrenheit before use. To change from Celsius temperature indication to Fahrenheit one Press and hold down at the same time for 5 seconds while the Celsius temperature is indicated.
Page 154
EDUS041111_a Optional Accessories Automatic · DRY · Cooling · Heating Operation Select your desired operation mode. Once preset, the system can get restarted in the same operation mode. Run indicator lamp (green) Press to select your desired operation mode. Each time the button is pressed, the mode changes as follows.
Page 155
Optional Accessories EDUS041111_a To adjust the temperature and airflow rate: Operation Automatic Cooling Heating mode Setting to be adjusted Temperature is adjustable. Temperature Recommended temperature cannot be Cooling : 26˚C-28˚C (79˚F~82˚F) adjusted. Heating : 20˚C-22˚C (68˚F~72˚F) (Temperature) Five levels of airflow rate setting from "...
Page 156
EDUS041111_a Optional Accessories Adjusting Airflow Direction Adjust the airflow direction for maximum comfort. To adjust the Airflow Direction Press during operation . Each time the button is pressed, the airflow direction louvers change their movement. Wall Mounted Types (without horizontal swing function) The horizontal airflow direction louvers Swing move up and down.
Page 157
Optional Accessories EDUS041111_a Wall Mounted Type (with horizontal swing function) The horizontal airflow direction louvers Swing horizontally move up and down. The horizontal airflow direction louvers Swing vertically stop just when the button is pressed. Then the vertical ones start moving right and left.
Page 158
EDUS041111_a Optional Accessories Timer Operation The Timer Operation feature automatically turns off operation when you go to sleep and turns it back on when you wake up. Use the DAILY Timer mode on weekdays, and the ONE TIME timer mode on weekends. ...
Page 159
Optional Accessories EDUS041111_a ONE TIME timer Once the timer has been activated and then deactivated, it is in the OFF mode. The ON or OFF timers can be programmed. Press to select the ONE TIME timer. Press blinks. ONE TIME light up.
Page 160
EDUS041111_a Optional Accessories Timer Operation To select the DAILY timer mode: Timers Two pairs of ON and OFF time Press to select the DAILY timer mode. settings can be programmed. Each time the button is pressed, the modes change as follows.
Page 161
Optional Accessories EDUS041111_a DAILY timer After programming, the system starts and stops each day at the preset times. Two pairs of time settings can be programmed. (Example: 8:00 10:00, and 18:00 23:00) DAILY timer indication appears. lights up. Press to select the DAILY timer.
Page 162
EDUS041111_a Optional Accessories Cleaning Cleaning the remote controller Wipe it clean with soft, dry cloth. Do not use any water hotter than 40˚C (104˚F), or v olatile liquids such as benzine, gasoline and thinner, polishing powder, or anything hard such as a scrub brush. When the unit is not used for a long time On a sunny day, keep the system running for half a day in the FAN mode to dry it up inside.
Optional Accessories EDUS041111_a 13.3 <KRP980B1> Interface Adaptor for Wired Remote Controller Safety Precautions Outline/Features • Read these Safety Precautions carefully to ensure correct installation. This set is an interface that connects a wired remote controller to a room air conditioner. This manual classifies precautions into WARNING and CAUTION.
Page 164
EDUS041111_a Optional Accessories Removing and installing front panel Opening service lid of indoor unit • Removal method The service lid is of removable type. 1)Place your fingers in the indentations on the main unit • Opening method (one each on the left and right sides), and open the panel until it stops.
Page 165
Optional Accessories EDUS041111_a Removing electrical component cover * Refer to the surface page for the removal of each part in detail. *1 Remove the front panel. WARNING *2 Remove the front grille. • Be sure to turn OFF the power at the time of installation work.
Page 166
EDUS041111_a Optional Accessories Connecting electrical component (this set) 1. Prepare the electrical component (this set). Preparing the electrical component (this set). Fig. 1 (See Fig. 1) Electrical component Remove the electrical 1) Remove the electrical component cover Insert the cord component cover.
EDUS041111_a Optional Accessories 13.6 <KPW937B4> Air Direction Adjustment Grille Before Installation Checking the parts Check the following parts Name Louver Screws M4×30L Installation manual Shape Quantity 1piece 4pieces 1piece Installation Procedure Selection of Installation Location Use when installing in a location that meets the following conditions. When installing near the border to a neighbor’s house If exhaust blows directly on passers-by because outdoor unit is installed facing a road.
Optional Accessories EDUS041111_a 13.7 <KPW937C4> Air Direction Adjustment Grille Component parts Be sure to check that the following parts are included before installation. Air direction Installation M4 x 30 Screw Name Seal Spacer adjustment grille manual Shape Qty. 1 pc . 4 pcs.
Page 176
EDUS041111_a Optional Accessories Square outlet grille whose thickness is 3/4” (20mm) Remove the outlet grille. Attach the seal ( ) to the front panel 1.Remove the 4 outlet grille fixing screws. 2.After lifting the outlet grille, move it forward to remove it from the front panel.
Page 177
Optional Accessories EDUS041111_a Room Air Conditioners K-Series...
Page 178
Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms tot he applicable standards, and is suitable for use, in the region where the product will be used.