Jumper Settings - Ferro Q Installation And Operation Manual

High frequency battery charger
Table of Contents

Advertisement

Jumper Settings

CAUTION: Remove AC and DC power from the charger before changing any jumper settings.
Refer to figure 1 for location of jumpers.
- Jumper J5 should be set to match the battery voltage.
Volts
80V
72V
64V
48V
36V
24V
1
12V
2
SP
1
For non-standard battery voltages above 80V, the jumper is set on 12 and a resistor is installed in the
charger wire harness based on the following calculation: R = 1250 x (Nominal Battery Voltage) – 15000.
2
For non-standard battery voltages between 12V and 80V, the jumper is set on SP and resistor R9 is
installed on the control based on the following calculation: R9 = 1250 x (Nominal Battery Voltage) –
15000.
- Jumper J4 is used to lock out several parameters in the programming mode.
Caution: Placing jumpers on any other position on J4 may damage the control and voids the warranty.
PARAMETER LOCKOUT
LOCKED
UNLOCKED
J4
J4
J4
J6
Figure 1. 46-271D Layout
J9
J5
J2
Page 12 of 18