Greystone DSD120 Installation And Maintenance Instructions Manual

Duct smoke detector

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
DSD120 Duct Smoke Detector
SPECIFICATIONS
Operating Temperature:
Storage Temperature:
Humidity:
Air Velocity:
DSD120 Footprint Dimensions:
DSD120 Weight:
Electrical
Power supply voltage:
Input capacitance:
Reset Voltage:
Reset Time (with RTS151):
Reset Time (by power down):
Power Up Time:
Alarm response time:
Sensitivity Test:
Current Requirements (Using No Accessories)
Max. standby current
Max. alarm current
CONTACT RATINGS
Alarm initiation contacts (SPST)
Alarm auxiliary contacts (DPDT)
NOTE: Alarm auxiliary contacts shall not be connected to initiating circuits of
control panels. Use the alarm initiation contact for this purpose.
Supervisory Contacts (SPDT)

TABLE OF CONTENTS

[1] Limitations of Duct Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . 1
[3] General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[4] Contents of Duct Smoke Detector Kit. . . . . . . . . . . . . . . . . . . . . . . . . . 2
[5] Detector Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[6] Sampling Tube Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[7] Measurement Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[8] Field Wiring Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
[9] Detector Status Indication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
[10] Interconnection (Multiple Fan Shut Down). . . . . . . . . . . . . . . . . . . . . 5
[11] Verification of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
[12] Detector Cleaning Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[13] Sensor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[14] Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring Diagrams.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4- 6
Detector Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
BEFORE INSTALLING
Read the Applications Guide for Duct Smoke Detectors, which provides informa-
tion on detector spacing, placement, zoning, wiring, and special applications.
This manual is available online at www.greystoneenergy.com. NFPA Standards
72, 90A, and CAN/ULC S524 should also be referenced for detailed information
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following
NFPA 72 or CAN/ULC S536 requirements. The detector should be cleaned at
least once a year.
IN-GE-DSD120-01-01
-4° to 158° F (-20° to 70° C)
-22° to 158° F (-30° to 70° C)
0% to 95% Relative Humidity Non-condensing
100 to 4000 ft./min. (0.5 to 20.3 m/sec.)
Rectangular - 14.38 in L x 4.57 in W x 2.67 in D (37cm L x 11.6cm W x 6.8cm D)
Square - 7.75 in L x 9 in W x 2.67 in D (19.7cm L x 22.9cm W x 6.8cm D)
2.5 pounds; 1.14 kg
20-29 VDC
270 µF max.
3.0 VDC min.
.03 to 0.3 sec.
0.6 sec. max.
35 sec. max.
15 sec.
See detector label
21 mA @ 24 VDC
65 mA @ 24 VDC
2.0A @ 30 VDC (resistive)
10A @30 VDC (resistive)
10A @250 VAC (resistive)
1
/
HP @240 VAC
2
1
/
HP @120 VAC
4
2.0A @ 30 VDC (resistive)
2.0A @ 125 VAC (resistive)
24 VAC 50-60-Hz
270 µF max.
2.0 VAC min.
.03 to 0.3 sec.
0.6 sec. max.
35 sec. max.
15 sec.
See detector label
65 mA RMS @ 24VAC 60Hz
135 mA RMS @ 24 VAC 60 Hz
ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE
APA151
MHR(A)/MHW(A)
RA100Z(A)
RTS151
RTS151KEY(A)
Only (A) models are ULC listed .
NOTE: Any combination of accessories may be used such that the given
PAGE
accessory loads are: 110mA or less at the Aux output, and 50mA or less at the
Alarm output.

[1] LIMITATIONS OF DUCT SMOKE DETECTORS

The National Fire Protection Association has established that DUCT DETEC-
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR
PROTECTION as a means of providing life safety. Nor are they a substitute for
early warning in a building's regular fire detection system.
Greystone Energy supports this position and strongly recommends that the user
read NFPA Standards 90A, 72, 101, and CAN/ULC S524. The DSD120 Air Duct
Smoke Detectors are listed per CAN/ULC S529 and UL 268A.
This device will not operate without electrical power. Fire situations may cause
an interruption of power. The system safeguards should be discussed with your
local fire protection specialist.
This device will not sense smoke unless the ventilation system is operating and
the cover is installed.
For this detector to function properly, it MUST be installed according to the
instructions in this manual. Furthermore, the detector MUST be operated within
ALL electrical and environmental specifications listed in this manual. Failure to
comply with these requirements may prevent the detector from activating when
smoke is present in the air duct.
1
150 English Drive, Moncton, NB E1E 4G7 Canada
Tel: +1-506-853-3057 Fax: +1-506-853-6014
www.greystoneenergy.com
120 VAC 50-60 Hz
N/A
10 VAC min.
.03 to 0.3 sec.
0.6 sec. max.
35 sec. max.
15 sec.
See detector label
20 mA RMS @ 120 VAC 60 Hz
35 mA RMS @ 120 VAC 60 Hz
STANDBY
TROUBLE
12.5mA
n/a
0mA
n/a
0mA
n/a
0mA
n/a
12mA
n/a
WARNING
ALARM
30mA Max.
29mA Max.
12mA Max.
12mA Max.
12mA Max.
I56-9201-000
5/6/2019

Advertisement

Table of Contents
loading

Summary of Contents for Greystone DSD120

  • Page 1: Table Of Contents

    [10] Interconnection (Multiple Fan Shut Down)..... 5 read NFPA Standards 90A, 72, 101, and CAN/ULC S524. The DSD120 Air Duct [11] Verification of Operation .
  • Page 2: Exploded View Of Duct Smoke Detector Components

    SECURE DETECTOR system. IN PLACE. The DSD120 detector is designed to operate on 24 VDC/VAC or 120 VAC. Alarm and supervisory relay contacts are available for control panel interface (alarm initiation), HVAC control, and other auxiliary functions. The fire alarm control panel is NOT notified when sensor maintenance its required.
  • Page 3: Sampling Tube Installation

    [7.1] AIR FLOW provided end cap. The DSD120 is designed to operate over an extended air speed range of 100 A plastic exhaust tube is included with the unit to be installed if needed. Install to 4000 FPM. To verify sufficient sampling of ducted air, turn the air handler...
  • Page 4: Field Wiring Installation Guidelines

    9 VOLT 1000 OHM 5% BATTERY 1 WATT RESISTOR The DSD120 detector is designed for easy wiring. The housing provides a termi- 9 VOLT BATTERY nal strip with clamping plates. See Figure 6 on page 4 for system wiring. *Trouble is indicated when the Supervisory Relay, switches state-Terminals...
  • Page 5: Detector Status Indication

    2 and so on. greater than 500 FPM, use a conventional manometer to measure differential • Up to 30 DSD120 units may be interconnected. pressure between the sampling tubes, as described in Section 7.1. NOTE: Alarm can be reset only at the initiating device and not at the devices Drill a inch hole 3 feet upstream from the duct smoke detector.
  • Page 6: Detector Cleaning Procedures

    The RTS151/RTS151KEY Remote Test Station facilitates test of the alarm capabil- ity of the duct smoke detector as indicated in the RTS151/RTS151KEY manual. The DSD120 duct smoke detector can be reset by the RTS151/RTS151KEY. To install the RTS151/RTS151KEY, connect the device as shown in Figure 12; wire runs must be limited to 25 ohms or less per interconnecting wire.
  • Page 7: Detector Status

    Alarm Relay: Terminals 4 and 5 are open Aux Relay does not switch states NOTE: Power Board LED is not visible unless the power board cover is removed. If any other visual indication is noted contact technical support at 1-506-853-3057. IN-GE-DSD120-01-01 I56-9201-000 5/6/2019...
  • Page 8: Warranty

    Please refer to insert for the Limitations of Fire Alarm Systems THREE-YEAR LIMITED WARRANTY Greystone Energy warrants its enclosed product to be free from defects in materials and describing the malfunction and suspected cause of failure. The Company shall not be...

Table of Contents