Digital output – “ Sensor individual” e.g. Fan – output ..........58 Control: Heating-PI on AO2.................59 Learning-In of Sensors ..................60 Controller Adjustment ..................61 Xp Proportional Range ..................61 Tn Integral Time ....................61 Typical Controller Settings...................61 Version Change....................62 Thermokon Sensortechnik GmbH Page 3...
1 Introduction 1.1 Product Overview The SRC-ADO-BCS is designed for receiving und processing telegrams of Thermokon wireless sensors of the EasySens product line and other brand devices transmitting measuring values according to the EnOcean standard. The measuring values of the sensors can be assigned to analogue (0-10V) and/or digital outputs.
Interpretation of measuring range Selection of EnOcean data byte o Pilot Contact Window contact SecuSignal Wireless chair Motion sensor Digital contact Presence button Switching o 1 button – operation (toggle) o 2 button – operation Blind Shutter Thermokon Sensortechnik GmbH Page 7...
Page 9
Pilot Contact Window contact SecuSignal Wireless chair Motion sensor Digital contact Presence button Dimming o 1 button – operation o 2 button – operation Switching o 1 button – operation (toggle) o 2 button – operation Thermokon Sensortechnik GmbH Page 8...
Connect the SRC-ADO to the PC by an USB cable. In the window “ Assistant for searching of new hardware“ select “ Install software from a list or a certain source“ . 2.2.3 Logo-Test Continue the Window-Logo test. Picture 2: Windows-Logo Test Thermokon Sensortechnik GmbH Page 9...
Picture 3-1 shows the start window which is displayed after the programme start. Menu Select function Configure output konfigurieren Output value Ausgabewert Monitor Picture 3-1: Start Window Thermokon Sensortechnik GmbH Page 10...
Interpretation of measuring range Selection of EnOcean data byte o Pilot Contact Window contact SecuSignal Wireless chair Motion sensor Digital contact Presence button Switching o 1 button – operation (toggle) o 2 button – operation Blind Shutter Thermokon Sensortechnik GmbH Page 12...
Page 14
Pilot Contact Window contact SecuSignal Wireless chair Motion sensor Digital contact Presence button Dimming o 1 button – operation o 2 button – operation Switching o 1 button – operation (toggle) o 2 button – operation Thermokon Sensortechnik GmbH Page 13...
Picture 3-1: Test Window 3.5.3 Help In the menu “ Via“ there are information about the manufacturer and the product. A help for the programme can be polled via the menu “ Help” . Thermokon Sensortechnik GmbH Page 14...
If a hook mark is set with “ Read out of Sensors“ , all sensors are read out and the data are shown in the configuration software. If a scaling is put in, the data bytes are scaled. Thermokon Sensortechnik GmbH Page 15...
In the field “ Reading“ the current status of the output can be displayed by activating the hook mark. 4.1.3 Scaling of Output Quantity The analogue output can be adjusted in the field “ lower and upper output voltage“ of 0- 10 V. Thermokon Sensortechnik GmbH Page 17...
Picture 4-2: Sensors 4.2.2 Learning-In For learning-in a sensor, the „ SensorID learn-in“ – button must be actuated. The learning-in window is displayed when a device type was selected. Picture 4-3: Learning-In Window Thermokon Sensortechnik GmbH Page 18...
By means of the info button the data bytes of the sensor are displayed. Picture 4-5: Monitor For the precise meaning of the individual data bytes, please see the product data sheet of the sensor manufacturer. Thermokon Sensortechnik GmbH Page 19...
Fields “ lower-“ and “ upper scaling“ : The input values must be within the measuring range of the sensor. o Fields “ lower-“ and “ upper output voltage“ The input values must be within the 0-10V output range. Thermokon Sensortechnik GmbH Page 20...
Page 22
In the field “ Output“ the current status of the output can be displayed by activating the hook mark. o Lower output voltage and output voltage Scaling of output voltage in the range 0-10V Thermokon Sensortechnik GmbH Page 21...
“ Sensors“ o Attention: For an averaging all sensors must have the same measuring range Number of sensors o Up to 15 sensors can be selected for an averaging and can be assigned to the output. Thermokon Sensortechnik GmbH Page 22...
Averaging is made via all sensors which are marked by a hook on the register card “ Sensors“ . Number of Sensors o Up to 15 sensors can be selected for an averaging and can be assigned to the output. Thermokon Sensortechnik GmbH Page 23...
The averaging is made via all sensors which are marked by a hook on the register card “ Sensors“ Number of sensors o Up to 15 sensors can be selected for an averaging and assigned to the output. Thermokon Sensortechnik GmbH Page 24...
Fields “ lower-“ and “ upper scaling“ : The input values must be within the measuring range of the sensor. o Fields “ lower-“ and “ upper output voltage“ The input values must be within the 0-10V output range. Thermokon Sensortechnik GmbH Page 25...
“ Sensors“ o Attention: For an averaging all sensors must have the same measuring range Number of sensors o Up to 15 sensors can be selected for an averaging and can be assigned to the output. Thermokon Sensortechnik GmbH Page 26...
Function of data bytes can be found in the product data sheet of the manufacturer Sensor Evaluation Linear: o Lower scaling and upper scaling Sensor can be scaled between 0-255 bit and is output to the output linear Thermokon Sensortechnik GmbH Page 27...
Picture 4-11: Sensor Evaluation Range 4.3.5.2 Register Card Sensors Number of Sensors o Up to 15 sensors can be selected and assigned to the output. Thermokon Sensortechnik GmbH Page 28...
Lower output voltage and output voltage Scaling of output voltage in the range 0-10V 4.3.6.1 Register Card Sensors Number of Sensors o Up to 15 sensors can be selected and assigned to the output Thermokon Sensortechnik GmbH Page 29...
By actuating the upper button, the output is dimmed brighter (e.g. the output is changed by e.g. 5% all 0,3s). By a short button actuation e.g. < 2s the lighting can be switched-on or off. Picture 4-13: Dimming - 2 – button operation Thermokon Sensortechnik GmbH Page 30...
Page 32
Lower output voltage and output voltage Scaling of output voltage in the range 0-10V 4.3.7.1 Register Card Sensors Number of Sensors o Up to 15 sensors can be selected and assigned to the output Thermokon Sensortechnik GmbH Page 31...
SR65 DI, a slide switch respectively by a motion sensor. The devices for night lowering are “ OR” operating -> if one device is in night lowering when the controller is in night lowering. Picture 4-14: Property Continuous Control Thermokon Sensortechnik GmbH Page 32...
Control deviation > 0 Lower control variable limit is only effective if a control deviation is existing o Control deviation = 0 Lower control variable is always effective even if no control deviation is existing Comfort extension Thermokon Sensortechnik GmbH Page 33...
Changeover function is only on SRC-ADO-Type2 available. Changeover function is used by 2-pipe Systems. Changeover between heating and cooling could be realized by useing micro switch (SR04/SR07 MS) or an extra digital input module (SR65-DI). Thermokon Sensortechnik GmbH Page 34...
To control the fan speed with a continuous controller the same channel of the sensor as is used by the continuous controller has to be selected. Abbildung 4-15: Parameter Constant FanCoil Thermokon Sensortechnik GmbH Page 35...
1 temperature sensor can be learned-in If the FanCoil should be connected to a controller, the same channel of the sensor have to be chosen as it is used by the controller Picture 4-16: Continuous FanCoil / PI Controller Thermokon Sensortechnik GmbH Page 36...
SR65DI, a slide switch respectively by a motion sensor. For the night lowering, the devices are “ Or” operated -> if one device is in night lowering when the controller is in night lowering. Picture 4-17: Property Continuous Control Thermokon Sensortechnik GmbH Page 37...
Lower control variable limit is always effective, even if no offset is existing. Comfort Extension o The toggle between comfort operation into night lowering is made delayed by the adjusted time (s). For example with the use of a wireless chair or a motion sensor. Thermokon Sensortechnik GmbH Page 38...
Changeover function is only on SRC-ADO-Type2 available. Changeover function is used by 2-pipe Systems. Changeover between heating and cooling could be realized by using micro switch (SR04/SR07 MS) or an extra digital input module (SR65-DI). Thermokon Sensortechnik GmbH Page 39...
SR65 DI, a slide switch respectively by a motion sensor. The devices for night lowering are “ OR-operated -> if one device is in night lowering when the controller is in night lowering. Picture 4-18: Property Continuous Control Thermokon Sensortechnik GmbH Page 40...
(s). For example with the use of a wireless chair or a motion sensor. Control Property Basic-Set Point o Basic set point for control Output In the field “ Output“ the current status of the output can be displayed by activating the hook mark. Thermokon Sensortechnik GmbH Page 41...
Window contacts are “ OR“ -operated, i.e. all window contacts must be closed If the window is opened, the controller switches to 100% if the antifreeze temperature was fallen below Devices for night lowering are “ OR“ -operated. Thermokon Sensortechnik GmbH Page 42...
To control the fan speed with a continuous controller the same channel of the sensor as is used by the continuous controller has to be selected. Abbildung 4-19: Parameter FanCoil Thermokon Sensortechnik GmbH Page 43...
1 temperature sensor can be learned-in If the FanCoil should be connected to a controller, the same channel of the sensor have to be chosen as it is used by the controller Picture 4-20: Continuous FanCoil / PI Controller Thermokon Sensortechnik GmbH Page 44...
(Thus, also see SecuSignal® data sheet ) The relay is switched-on if: the windows are opened motion was detected the digital contacts are closed the wireless chair is occupied the presence button is pressed slide switch is switched Thermokon Sensortechnik GmbH Page 45...
In the field “ Output“ the current status of the output can be displayed by activating the hook mark 4.4.4.2 Register Card Sensors Number of Sensors o Up to 15 sensors can be selected and assigned to an output Picture 4-21: Pilot Relay Thermokon Sensortechnik GmbH Page 46...
Temperature of SR04 is inverted -> 0 °C = 255 bit and 40 °C = 0 bit Selection data byte: data byte 1 Lower switch value: 0 bit Upper switch value: 255 bit – (30 °C / 40 °C * 255 bit) = 64 bit Thermokon Sensortechnik GmbH Page 47...
In the field “ Output“ the current status of the output can be displayed by activating the hook mark. 4.4.5.2 Register Card Sensors Number of sensors o Up to 15 sensors can be selected and assigned to the output Thermokon Sensortechnik GmbH Page 48...
In the field “ Output“ the current status of the output can be displayed by activating the hook mark. 4.4.6.2 Register Card Sensors Number of sensors o Up to 15 buttons can be selected and assigned to the output. Thermokon Sensortechnik GmbH Page 49...
In the field “ Output“ the current status of the output is displayed by activating the hook mark. 4.4.7.2 Register Card Sensors Number of sensors o Up to 15 buttons can be selected and assigned to the output Thermokon Sensortechnik GmbH Page 50...
In the field “ Output“ the current status of the output is displayed by activating the hook mark. 4.4.8.2 Register Card Sensors Number of sensors o Up to 15 buttons can be selected and assigned to the output. Thermokon Sensortechnik GmbH Page 51...
In the field “ Output“ the current status of the output can be displayed by activating the hook mark. 4.4.9.2 Register Card Sensors Number of sensors o Up to 15 buttons can be selected and assigned to the output Thermokon Sensortechnik GmbH Page 52...
In the field “ Output“ the current status of the output can be displayed by activating the hook mark. 4.4.10.2 Register Card Sensors Number of sensors o Up to 15 buttons can be selected and assigned to the output Picture 4-27: Blind Thermokon Sensortechnik GmbH Page 53...
In the field “ Output“ the current status of the output is displayed by activating the hook mark. 4.4.11.2 Register Card Sensors Number of sensors o Up to 15 buttons can be selected and assigned to the output Picture 4-28: Shutter Thermokon Sensortechnik GmbH Page 54...
For clearing an output no sensor should be assigned to the output. In the register card sensors there should be no hook mark. For clearing an output, select “ Not used” (1) in the main menu. Then use button “ sensor configuration” (2). Picture 4-29: Deleting Output Thermokon Sensortechnik GmbH Page 55...
Select the requested function, here „ Sensor Temperature AO1“ , in the output function list(1). Picture 5-1: Selection Sensor Temperature AO1 The output must be configured and a sensor must be assigned to the output. Therefore, actuate the button “ configure output” (2). Thermokon Sensortechnik GmbH Page 56...
Page 58
Software description SRC-ADO Picture 5-2: Property In the property “ rider“ a scaling of the sensor is possible. If no parameters should be amended, it can be changed in the rider “ sensors” . Thermokon Sensortechnik GmbH Page 57...
If a window is opened, the control variable amounts to 0% as long as the anti-freeze limit is achieved. If the anti-freeze is under-run, the control variable is 100%. Moreover a lowering for night operation of 4K was selected. Thermokon Sensortechnik GmbH Page 59...
Picture 5-5: Learning-in of Sensors Select the device type (2) and actuate the button „ learning-in of sensors“ (3). Now the window “ learning-in of sensors” appears and a sensor can be learned-in, accordingly (4). Thermokon Sensortechnik GmbH Page 60...
PI-controller due to its P-part. 6.3 Typical Controller Settings Hot water heating: Xp=5K / Tn=150min Under floor heating: Xp=5K / Tn=240min Electric heating: Xp=4K / Tn=90min Fan heating: Xp=4K / Tn=90min Thermokon Sensortechnik GmbH Page 61...
7 Version Change Version 3.0 Devices including hardware version 1 and 2 cannot be configured by the software version 3.0. Please use software version 2. Version 3.1 Checking firmware of SRC-ADO type 1 and type 2 Thermokon Sensortechnik GmbH Page 62...