Berkeley BPC Series Quick Start Manual

Pump controller

Advertisement

Quick Links

293 Wright Street • Delavan, WI 53115
BERKELEY Pump Controller
ABOUT
The BERKELEY Pump Controller (BPC) is pre-jumpered
and programmed with the BERKELEY Assistant , provid-
ing ease of setup for constant pressure applications. The
BERKELEY Assistant defaults to pre-defined parameters
as described in this guide, and also prompts the user for
application-specific information.
This guide covers the startup of the BERKELEY
Assistant for constant pressure applications. For other
programs, refer to the ABB manual provided.
SAFETY
Hazardous voltage. Can shock, burn, or
cause death. Ground pump before connecting to power
supply. Disconnect power before working on system
components.
Wire pump motor for correct voltage. See motor
nameplate.
Ground motor to drive before connecting to
power supply.
Meet National Electrical Code, Canadian Electrical
Code, and local codes for all wiring.
Local / Remote
Motor Rotation
Indicator
Indicator
PAR EDIT
PAR EDIT
REM
REM
Left Button
9909 MOTOR NOM POWER
9909 MOTOR NOM POWER
Function
3.0 hp
3.0 hp
EXIT
EXIT
Left Button
Scroll
Buttons
Local /
Remote
Stop
FIGURE 1: Control Panel Button Location
Controller Mode
PID Address
andFunction
Description
00:00
00:00
SAVE
SAVE
Value
Right Button
Function
Right Button
Help
Start
QUICK START GUIDE
INSTALLATION
Connect Transducer
Install the transducer where pressure is to be maintained.
The BERKELEY Assistant requires a 4 - 20 ma transduc-
er (Figure 2). The transducer's power lead should be
attached to terminal 10 or the terminals as shown below
and the 4 - 20 ma output lead should be attached to ter-
minal 5 (Figure 3). The transducer has a brown power
lead and a blue 4 - 20 ma output lead.
(All jumper terminals may need to be loosened to attach
leads above the jumper board).
The jumper board eliminates the need to hand wire termi-
nals 9 to 11, 10 to 19, 11 to 12 and 18 to 21.
Before applying power, make sure the front cover is on
and the control module is in place.
Startup the BERKELEY Assistant
Apply power to the unit, and follow
the steps on Pages 2 and 3 after
the controller's screen is lit.
FIGURE 2: Transducer and Cable
Jumper Board
4 - 20 ma Output
FIGURE 3: Transducer connection to Terminal strip
BPC Series
Transducer cable
Transducer
DIP Switches
+24 volt
Power
Connection
Power Lead
BE770 (Rev. 7/13/05)

Advertisement

loading
Need help?

Need help?

Do you have a question about the BPC Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Berkeley BPC Series

  • Page 1 Install the transducer where pressure is to be maintained. ing ease of setup for constant pressure applications. The The BERKELEY Assistant requires a 4 - 20 ma transduc- BERKELEY Assistant defaults to pre-defined parameters er (Figure 2). The transducer’s power lead should be...
  • Page 2 00:00 00:00 EXIT EXIT the user will be prompted installation and then press to run the BERKELEY ASSISTANT . Scroll to YES and then select OK. Wait while the assistant loads. On subsequent startups, the BERKELEY ASSIS- TANT can be found in the ASSISTANTS menu.
  • Page 3 PAR EDIT PAR EDIT EDIT EDIT 9906 MOTOR NOM CURR 9906 MOTOR NOM CURR 9905 MOTOR NOM VOLT 9905 MOTOR NOM VOLT 3.8 A 3.8 A 460 V 460 V MOTOR MOTOR VOLTAGE CURRENT SCREEN SCREEN 00:00 00:00 EXIT EXIT 00:00 00:00 SAVE...
  • Page 4 9907 4125 WAKE-UP DEV per 4025 Upon initial startup, the BERKELEY ASSISTANT runs mode the drive holds a constant speed which can be automatically. On subsequent runs, use the steps below adjusted using the up/down buttons. The speed which will to run the BERKELEY ASSISTANT .
  • Page 5: Tank Sizing

    If the motor is rated for Timer Function: operation at multiple voltages, select the voltage nearest The BERKELEY VFD includes four timer functions. Each the utility voltage. Ensure the motor connections corre- timer function can include up to four daily / weekly start spond to the voltage selected.
  • Page 6: Helpful Hints

    Saving and Recalling Settings will allow the pump to run with zero flow (dead head). The water in the pump can overheat. The BERKELEY VFD can save and recall (2) sets of user parameters (use parameter 9902). After running the Sleep Options...
  • Page 7: Installation Record

    HELPFUL HINTS (Continued) Automatic Restarts After Power Failure Dip Switch in ON The BERKELEY VFD can be configured to automatically Position restart after power loss. This will energize the motor whenever power is present. To enable this mode, set parameter 1002 to DI1, and set the Dip Switch on the jumper board to ON.
  • Page 8 86° F with proper flow conditions cooling the firmware version of the drive and keypad. motor, parameter 3007 can be set to 112%. BERKELEY technical support number is Submersible motors should always operate within its service factor limit.