Safety, Installation, and Operation Manual
READ COMPLETE INSTALLATION INSTRUCTIONS BEFORE STARTING.
WARNING
This product must be installed by a qualified heating and air conditioning contractor. Failure to do so
could result in serious injury from electrical shock or damage to product and voids product warranty due
to possible product misapplication.
THESE INSTALLATION INSTRUCTIONS ARE FOR THE HUMIDISTAT ONLY!
For DRISTEEM
®
Humidifier installation, follow DRISTEEM Humidifier Installation Instructions.
WARNING
1. Contact with energized electrical circuits may cause serious injury
from electrical shock. Disconnect electrical power to the Humidifier
before starting installation.
2. Sharp edges may cause serious injury from cuts. Use care when
cutting plenum openings and handling ductwork.
CAUTION
1. Do not set humidity higher than recommended or moisture can
accumulate, which may cause bacteria and mold growth or dripping
water into building spaces. Dripping water may cause property
damage; bacteria and mold growth may cause illness.
2. Do not set humidity up to recommended levels if there is
condensation on the inside of windows. Condensation damage
may result.
3. Do not mount Humidistat on supply plenum or duct. High supply
temperatures will cause the control to malfunction.
4. When installing Humidistat on downflow furnaces, ensure that
blower continues to run as programmed after a heat call is satisfied
to eliminate high temperatures from damaging the Humidistat.
DRISTEEM Duct Mounted On-Off Humidistat (DS 301)
and Duct Mounted Modulating Humidistat (DS 401)
PRINCIPLES OF OPERATION
The DRISTEEM Duct Mounted On-Off Humidistat (DS 301) and Duct
Mounted Modulating Humidistat (DS 401) are designed to be installed in
the return duct or return plenum only of the HVAC system. The Control
supplies a modulating signal to the humidifier. In terms of outdoor
temperature compensation, the Control can be set up in automatic or
manual mode, regardless of the humidifier model being controlled. The
automatic mode incorporates the supplied Outdoor Temperature Sensor to
automatically adjust the control set-point based on the outdoor
temperature. The manual mode does not require an outdoor temperature
measurement and is used for specific set-point control with the control set-
point manually adjusted by the user. The DRISTEEM Duct Mounted On-Off
Humidistat (DS 301) and Duct Mounted Modulating Humidistat (DS 401) will
accurately control the humidity in the conditioned space within the range of
15% – 55% RH.
CONTROL TYPE
ON-OFF CONTROL
The DRISTEEM Duct Mounted On-Off Humidistat (DS 301) sends a 10 VDC
signal to the humidifier when the measured return air relative humidity is
3% or more below the set-point. This energizes the humidifier at 100%
output. The Humidifier is either on at 100% capacity or it is off.
MODULATING CONTROL
The DRISTEEM Duct Mounted Modulating Humidistat (DS 401) sends a
signal to the humidifier between 0 and 10 VDC based on: a) the difference
between measured relative humidity and set-point relative humidity, and b)
where this difference or 'error' falls within an adjustable proportional
control band. The output of the Control, and therefore the Humidifier, is a
'proportion' of maximum output based on 'a' and 'b' above. See Figure 1
for graphical representation of the output.
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DS 301 and is the answer not in the manual?

Questions and answers

Summary of Contents for DriSteem DS 301

  • Page 1 ON-OFF CONTROL 4. When installing Humidistat on downflow furnaces, ensure that The DRISTEEM Duct Mounted On-Off Humidistat (DS 301) sends a 10 VDC blower continues to run as programmed after a heat call is satisfied signal to the humidifier when the measured return air relative humidity is to eliminate high temperatures from damaging the Humidistat.
  • Page 2: Installation

    INSTALLATION FIGURE 1 – Modulating Control Output STEP 1: DETERMINE LOCATION FOR CONTROL PROPORTIONAL AND MOUNT ON DUCT CONTROL BAND Note: 10 VDC The Proportional The Control must be mounted in the return duct of the HVAC system. Control Band See Figure 2 for a rooftop unit installation and Figure 3 for a split-system can be adjusted to 6%, 9%, 12%,...
  • Page 3 STEP 2: DETERMINE LOCATION FOR OUTDOOR FIGURE 5 – Alternate Location for Outdoor TEMPERATURE SENSOR Temperature Sensor The location of the Outdoor Temperature Sensor must meet these three requirements: 1. Must be mounted on North, East or West side of building out of direct sunlight FRESH AIR INTAKE 2.
  • Page 4: Operation

    STEP 7: WIRE THE CONTROL TO THE HUMIDIFIER OPERATION Wire the Control to the field wiring terminal block of the Humidifier SYSTEM CHECKOUT according to Figure 9. Use 3-wire shielded cable with ground for the wiring from the Control to the Humidifier. Note the terminal designations below. 1.
  • Page 5 TABLE 2: Relative Humidity Guide OPERATION NOTES FOR MODULATING CONTROL Outdoor Temperature (°F) As explained in the ‘Principles of Operation’ section of this manual, when configured for modulating control, the Humidistat sends a 0-10V signal to – – – the humidifier to vary the capacity of the Humidifier depending on where –...
  • Page 6: Troubleshooting Guide

    TROUBLESHOOTING GUIDE Applies to both Automatic and Manual Operation unless indicated otherwise. SYMPTOM TROUBLESHOOTING PROCEDURE Humidifier does not • Make sure equipment blower is operating and thermostat is calling for heat. operate in “Test” mode • Make sure the Outdoor Temperature Sensor is connected to the “ODT” terminals of the control. (For Manual Operation, make sure Manual Mode Resistor Case is in place of the Sensor).
  • Page 7 CUT ALONG DASHED LINE WARNING Sharp edges on the opening may cause cuts. Use care when cutting the plenum opening and installing the Humidistat. CAUTION • Do not mount Humidistat on supply plenum or duct. The unit will not withstand supply temperatures and will malfunction! •...
  • Page 8 Continuous product improvement is a policy of DRISTEEM Corporation; therefore, product features and specifications are subject to change without notice. DRISTEEM is a registered trademark of DRISTEEM Corporation and is filed for trademark registration in Canada and the European community. CUT ALONG DASHED LINE Form No.