Abnormal point and detection method
Check code
Abnormal refrigerant circuit
During Cooling, Dry, or Auto Cooling
operation, the following conditions are
regarded as failures when detected for 1
second.
a) The compressor continues to run for 30
PL
or more seconds.
b) The liquid pipe temperature or the
condense/evaporator temperature is
75°C or more.
These detected errors will not be
cancelled until the power source is
reset.
OCH529A
Cause
1 Abnormal operation of 4-way
valve
2 Disconnection of or leakage in
refrigerant pipes
3 Air into refrigerant piping
4 Abnormal operation (no rotation)
of indoor fan
· Defective fan motor.
· Defective indoor control board.
5 Defective refrigerant circuit
(clogging)
24
Countermeasure
1 When this error occurs, be sure to replace
the 4-way valve.
2 Check refrigerant pipes for disconnection or
leakage.
3 After the recovery of refrigerant, vacuum dry
the whole refrigerant circuit.
4 Refer to "9-6-2. DC Fan motor (Fan motor/
Indoor controller board)".
5 Check refrigerant circuit for operation.
Purge air in refrigerant circuit to avoid
entry of moisture or air into refrigerant
circuit which could cause abnormal high
pressure, or replace refrigerant.