Cased Coil Placement ......................... 7 Refrigeration ..........................9 Line Set ..........................9 TXV Kit..........................11 Airflow ............................20 Appendix A – CCA Series (CE) Supplemental Installation Instructions ........... 21 Appendix B – CCA Series (CE) Parts List ..................24 CCA-410-IM (03/15) Page 2...
Page 3
List of Figures Figure 1. Heat/Cool and Cool Only Component Matchup ................. 6 Figure 2. Heat Only Component Matchup ....................6 Figure 3. General Layout of System Components ................... 7 Figure 4. General Air Handler Physical Dimensions ................8 Figure 5. Line Set Sizes .......................... 9 Figure 6.
Earthlinked Technologies shall not be liable for any defect, unsatisfactory performance, damage or loss, whether direct or consequential, relative to the design, manufacture, construction, application or installation of the field specified components.
Equipment Manuals The following is a listing of the equipment installation manuals that are provided with each component ® specified for this EarthLinked system. IMPORTANT! Read and follow all installation instructions in these manuals, ®...
Installation Component Matching CCA Series Cased Coils are ready for vertical installation as shipped. Field conversion to horizontal requires no additional components. The CCA Series Cased Coils are manufactured for vertical and horizontal applications. Heat/Cool and Cool Only (Model CCA-00XX): These cased coils are equipped with a distributor designed for providing optimum performance in the cooling mode and the heating mode.
AND/OR PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Guidelines for the cased coil (or air handler) placement relative to the compressor unit and other ® EarthLinked system components are shown in Figure 3. Figure 3. General Layout of System Components CCA-410-IM (03/15)
Dimensions for the cased coils are illustrated and listed in Figure 4. Cainet LIQ/VAP OUTLET NLET Heat/Cool, Compressor Heat Only Cool Only H x W x D W1 x D1 W2 x D2 Unit Model Model Model Inches Inches Inches Inches -018 CCA –...
Refrigeration Line Set Line set sizes for CCA Series Cased Coils connecting to the matching compressor units are listed in ® ® Figure 5. Line set liquid and vapor lines are to be insulated with Armaflex , Insul-Lock or equivalent tubing insulation at least ½”...
TXV Kit Introduction CCA Series cased coils that are intended for HEAT ONLY application are ready to install and make the refrigeration line set connection to the cased coil as shipped. CCA Series cased coils that are intended for HEAT/COOL or COOL ONLY applications, are shipped with the matching TXV Kit that must be field installed to enable operation of the system in the cool mode.
The TXV control box is field positioned external to the vertical (upflow or downflow) cased coil and fastened to a solid mounting surface immediately adjacent to the cased coil as shown typically in Figure 8a. Locate the TXV control box to allow a service access of at least 12 inches in front of the box to adjust the TXV control.
For horizontal cased coil applications (left or right air flow), the TXV control box is field positioned external to the cased coil and can be fastened to a solid mounting surface immediately adjacent to the cased coil as shown typically in Figure 8b. Important! The TXV control box must be located no more than 3-1/2 feet from the suction tube stub out on the cased coil.
For mounting purposes, the physical dimensions for the TXV Control Box are shown in figure 8c. The preferred mounting position for the TXV Control Box is vertical with the liquid line tube connections on the bottom. However, as shown in Figure 8d, the Control Box can be mounted from vertical to any angle up to 90 degrees (horizontal).
Figure 8d. TXV Control Box Mounting Positions The following steps and positioning requirements apply to installing the TXV Control to the cased coil for vertical and horizontal applications. The vertical installation provides an illustrated example. Step 1: Relieve the nitrogen holding charge on the air handler using the valve on the liquid line stub out. Locate the TXV Control box within the 3-1/2 feet of the suction line stub out on the cased coil.
Step 2: Position the Pressure Equalizer Tee on the suction tube at least 10 inches downstream from the 90° ell as shown in Figure 9. Remove the core from Schrader valve on the Tee. Figure 9. Positioning the Pressure Equalizer Tee CCA-410-IM (03/15) Page 16...
Step 3: The Thermal Bulb must be positioned and clamped to the suction tube as shown in the example illustrated in Figure 10. The Thermal Bulb and suction tube must be horizontal regardless of the cased coil application (vertical or horizontal). The Thermal Bulb must be positioned at the 3:00, 4:00, 8:00 or 9:00 positions on the suction tube, as illustrated in Figure 10.
Step 5: Measure and cut copper tubing to connect the liquid line from the TXV control box to the liquid line stub out on the cased coil as shown in Figures 7 and 13. Run the other liquid line from the connection on the TXV control box to the compressor unit, also shown in Figure 13.
Airflow CCA Cased Coils are designed to operate at 400 cfm/Ton, nominal capacity. For system design purposes, Figure 14 provides the airflows for each CCA cased coil model and the associated coil pressure drops. Coil Pressure Drop, Cased Coil Model Airflow, cfm in W.C.