INSTALLATION AND OPERATION MANUAL
Adjustable Frequency Drive for 3-Phase AC Motors
3-Phase and PSC
Operates from 115, 208/230, and 400/460 Volt 50/60 Hz AC Line Input
NOTE: The drive is factory set for
60 Hz motors. For 50 Hz motors, see
Section 10.4 on page 15.
The information contained in this manual is intended to be accurate.
However, the manufacturer retains the right to make changes in design which may not be included herein.
Notes: 1. UL approved as an electronic overload protector for motors. 2. Special software is available for PSC motors – contact
Technical Support. 3. Installation of a CE approved RFI (EMI) filter is required.
Copyright © 2019
Acme Engineering & Mfg. Corp.
(See Back Cover)
ASD SERIES
NEMA 4X / IP65
Variable Speed / Soft-Start AC Motor Drive
With Electronic Motor Overload Protection
Washdown and Watertight for Indoor and Outdoor Use
Rated for 208 – 230 and 400/460 Volt 50 Hz and 60 Hz
2
AC Induction Motors from Subfractional thru 10 HP
See Safety Warnings on page 5.
This Manual Covers Models
ASD-24D, 27D, 29, 29 (1P), 45, 48
1
3
LISTED
IND. CONT.
EQ. – 70ZA
RoHS

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ACME SYNC ASD Series and is the answer not in the manual?

Questions and answers

Summary of Contents for ACME ACME SYNC ASD Series

  • Page 1 Notes: 1. UL approved as an electronic overload protector for motors. 2. Special software is available for PSC motors – contact Technical Support. 3. Installation of a CE approved RFI (EMI) filter is required. Copyright © 2019 Acme Engineering & Mfg. Corp. (See Back Cover)
  • Page 2: Table Of Contents

    TABLE OF CONTENTS Section Page Quick-Start Instructions ....................................4 Mounting ......................................4 AC Line Input Fusing ..................................4 AC Line Input Connection .................................. 4 Motor Connection ....................................4 Ground Connection .................................... 4 60 Hz and 50 Hz Motor Operation ..............................4 Jumper Settings ....................................
  • Page 3 TABLE OF CONTENTS (CONTINUED) Table Page Drive Electrical Ratings ....................................7 Drive General Performance Specifications ..............................7 Drive Terminal Block Wire Size and Tightening Torque Specifications ...................... 13 Drive Operating Condition and Run/Fault Relay Contact Status ........................ 14 Drive Operating Condition and Status LED Indicator ..........................18 Signal Isolator General Performance Specifications ..........................
  • Page 4: Quick-Start Instructions

    1 – QUICK-START INSTRUCTIONS Also see Section 3 – Important Application Information on page 5. Important: You must read these simplified instructions before proceeding. These instructions are to be used as a reference only and are not intended to replace the details provided herein. You must read the Safety Warnings on page 5 before proceeding. Reconditioning the Bus Capacitors: If this drive has been in storage for over one year, it is necessary to recondition the power supply bus capacitors.
  • Page 5: Safety Warnings

    2 – SAFETY WARNINGS Definition of Safety Warning Symbols Electrical Hazard Warning Symbol: Failure to observe this warning could result in electrical shock or electrocution. Operational Hazard Warning Symbol: Failure to observe this warning could result in serious injury or death. SAFETY WARNING! –...
  • Page 6: Introduction

    4 – INTRODUCTION Thank you for purchasing the ASD Adjustable Frequency Drive. Acme Engineering & Mfg. Corp. is committed to providing total customer satisfaction by producing quality products that are easy to install and operate. The ASD is manufactured with surface mount components incorporating advanced circuitry and technology.
  • Page 7: Drive Electrical Ratings

    TABLE 1 DRIVE ELECTRICAL RATINGS Ac Line Input Output Fuse or Circuit Maximum Weight Maximum Breaker Voltage Continuous Maximum Horsepower Volts AC Phase Current Rating Range Load Current Horsepower Selection (Ф) Model No. Part No. (50/60 Hz) (Amps AC) (Amps) (Volts AC) (Amps/Phase) (HP (kW))
  • Page 8: Asd-24D Drive Layout

    FIGURE 4 ASD-24D DRIVE LAYOUT (SEE LEGEND BELOW FOR NUMBERED ITEMS)                       LEGEND: 1. Adjustable Trimpots on Drive and Signal Isolator: Maximum Speed (MAX), Minimum Speed (MIN), Acceleration (ACCEL), Deceleration (DECEL), DC Injection Brake (DECEL), Boost (BOOST), Current Limit (CL), Jog (JOG), Slip Compensation (COMP) –...
  • Page 9: Asd-27D Drive Layout

    FIGURE 5 ASD-27D DRIVE LAYOUT (SEE LEGEND BELOW FOR NUMBERED ITEMS)               LEGEND: 1. Adjustable Trimpots on Drive and Signal Isolator: Maximum Speed (MAX), Minimum Speed (MIN), Acceleration (ACCEL), Deceleration (DECEL), DC Injection Brake (DECEL), Boost (BOOST), Current Limit (CL), Jog (JOG), Slip Compensation (COMP) –...
  • Page 10: Asd-29, 29 (1P), 45, 48 Drive Layout

    FIGURE 6 ASD-29, 29 (1P), 45, 48 DRIVE LAYOUT (SEE LEGEND BELOW FOR NUMBERED ITEMS)              LEGEND: 1. Adjustable Trimpots on Drive and Signal Isolator: Maximum Speed (MAX), Minimum Speed (MIN), Acceleration (ACCEL), Deceleration (DECEL), DC Injection Brake (DECEL), Boost (BOOST), Current Limit (CL), Jog (JOG), Slip Compensation (COMP) –...
  • Page 11: Mounting

    5 – MOUNTING It is recommended that the drive be mounted vertically on a flat surface with adequate ventilation. Leave enough room below the drive to allow for AC Line, motor connections, and any other wiring that is required. Although the drive is designed for outdoor and washdown use, care should be taken to avoid extreme hazardous locations where physical damage can occur.
  • Page 12: Asd-27D, 29, 29 (1P), 45, 48 Mechanical Specifications

    FIGURE 8 ASD-27D, 29, 29 (1P), 45, 48 MECHANICAL SPECIFICATIONS (Inches / mm) *Tighten these screws, in the sequence shown, to 12 in-lbs (14 kg-cm). ASD SERIES INSTALLATION AND OPERATION MANUAL...
  • Page 13: Ac Line Input Fusing

    6 – AC LINE INPUT FUSING The drive does not contain line fuses. Most electrical codes require that each ungrounded conductor contain circuit protection. Do not fuse neutral or ground connections. It is recommended to install a fuse (Littelfuse 312/314, Buss ABC, or equivalent) or a circuit breaker in series with each ungrounded conductor.
  • Page 14: Motor Connection

    7.2 – MOTOR CONNECTION FIGURE 10 Connect the motor to Terminal Block TB1 Terminals U, V, ASD-29, 45, 48 W. See Figures 9 and 10 on pages 13 and 14. AC LINE INPUT, MOTOR, AND GROUND CONNECTIONS Motor cable length should not exceed 100 feet (30 m) – special reactors may be required –...
  • Page 15: Reconditioning The Bus Capacitors

    9 – RECONDITIONIONG THE BUS CAPACITORS If this drive has been in storage for over one year it is necessary to recondition the power supply bus capacitors. To recondition the bus capacitors, apply the AC Line, with the drive in the Stop Mode, for a minimum of one hour. Not following this procedure will cause the bus capacitors to fail.
  • Page 16: Boost Mode Selection (J6)

    10.5 – BOOST MODE SELECTION (J6) Jumper J6 is factory set to the "FIX" position for Fixed Boost. For Adjustable Boost using the FIGURE 18 BOOST Trimpot, set Jumper J6 to the "ADJ" position. See Figure 18 See Section 12.8 on BOOST MODE SELECTION page 18 for the Boost Trimpot.
  • Page 17: Trimpot Adjustments

    12 – TRIMPOT ADJUSTMENTS The drive contains trimpots which are factory set for most applications. See Figures 4 – 6 on pages 8 – 10 for the FIGURE 24 location of the trimpots and their approximate factory calibrated positions. Some applications may require MINIMIM SPEED readjustment of the trimpots in order to tailor the drive for a specific requirement.
  • Page 18: Boost Trimpot (Boost)

    CAUTION! Adjusting the current limit above 160% of the motor nameplate rated current can cause overheating of the motor. Consult the motor manufacturer. Do not leave the motor in a locked rotor condition for more than a few seconds since motor damage may occur. In order to ensure that the motor is properly protected with the I t feature, it is required that the CL Trimpot be set for 160% of the motor nameplate rated current, as described below.
  • Page 19: Wiring Instructions

    FEATURES ▪ Isolated Switching: Provides isolation for PLC open collector or contact switching. ▪ Isolated 5 Volt DC Power Supply: Used for Main Speed Potentiometer operation (25 mA DC max.). ▪ Isolated 24 Volt DC Power Supply: Used to power a transducer or auxiliary equipment (50 mA DC max.). ▪...
  • Page 20: Main Speed Potentiometer Connection

    14.1.2 – MAIN SPEED POTENTIOMETER CONNECTION The Main Speed Potentiometer (5 kΩ), that is installed on the front cover is wired to the Signal Isolator. The potentiometer is connected as follows: high side to Terminal +5V, wiper to Terminal SIG1, and low side to Terminal COM. See Figure 34. 14.1.3 –...
  • Page 21 – NOTES – ASD SERIES INSTALLATION AND OPERATION MANUAL...
  • Page 22 – NOTES – ASD SERIES INSTALLATION AND OPERATION MANUAL...
  • Page 23 – NOTES – ASD SERIES INSTALLATION AND OPERATION MANUAL...
  • Page 24: Limited Warranty

    Some states do not allow certain exclusions or limitations found in this warranty and therefore they may not apply to you. In any event, the total liability of Acme Engineering & Mfg. Corp. under any circumstance shall not exceed the full purchase price of this product.

Table of Contents