When schedule is set then the unit will operate according to the defined settings when you leave the Schedule sub-
menu by touching button Return to previous page.
Setpoints
In this menu the setpoints are defined for Schedule when it is Enable. To set (un)occupied cooling or heating
setpoints, along with indoor fan mode (Auto/ON) and a possibility of minimal cooling setpoint and maximal heating
setpoint as a global limit range value.
When the unit works in manual mode (schedule disable or override mode) then change the setpoints directly on the
home screen by a touch on the value under snowflake (Cooling mode) or above heat (Heating mode). The setpoints
defined for Schedule will not be rewritten. Occupancy mode is permanently set as occupied in manual or in override
mode.
Minimal temperature difference about 2 K between cooling and heating
setpoint is taken into account automatically.
Cooling setpoint ≥ Heating setpoint + 2 K
Heating setpoint ≤ Cooling setpoint - 2 K