Electromagnetic Compatibility; Ex Areas; The Type Plate - Ebmpapst W3G990-GZ02-91 Operating Instructions Manual

Table of Contents

Advertisement

W3G990-GZ02-91
`
II 2G Ex d e ib IIB T3 Gb
IBExU14ATEX1123 X /05

4.6 Electromagnetic compatibility

If several devices are switched in parallel on the mains side so
that the line current of the arrangement is in the range of 16 - 75
A, then this arrangement conforms to IEC 61000-3-12 provided
that the short-circuit power S
customer system to the public power system is greater than or
equal to 120 times the rated output of the arrangement.
It is the responsibility of the installation engineer or operator/
owner of the device to ensure, if necessary after consultation
with the network operator, that this device is only connected to
a connection point with a S
to 120 times the rated output of the arrangement.

4.7 Ex areas

The device may only be used according to the specifications in the
operating instructions; see chapter 3. Proper use.
Zone classification
The zones describe how long an explosive atmosphere may be present.
Zones 1 and 2 permit only gases, vapours and mist (no dust) which
occur occasionally to seldom in normal operation.
Device categories
The device is approved for Category 2 of Equipment Group II. The
categories define the degree of safety.

4.8 The type plate

Fig. 1: Specifications on the type plate
Serial number
Designation
YY
WW
Six-digit number, e.g. 000003
Ex identification
`
II 2 G Ex d e ib IIB T3 Gb
Element
`
II
2
G
Ex d e ib
IIB
Item no. 54008-5-9970 · ENG · Revision 87791 · Release 2016-04-29 · Page 7 / 16
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
at the connection point of the
sc
value that is greater than or equal
sc
Explanation
Year Year, e.g. 11 for 2011,
model year
Week Week, calendar week of
the model year
Sequential serial number
Explanation
Ex marking according to 2014/
34/EU
Device group (II --> use above
ground (not mining))
Category 2 --> Zone 1,
Category 3 --> Zone 2
Ex atmosphere (G --> Gas) (no
dust pollution permissible)
Ignition protection class (d -->
flameproof enclosure, e -->
increased safety, ib --> intrinsic
safety with protection level)
Explosion group (for gases of
Group IIB)
T3
Gb
Certificate number IBExU14ATEX1123 X /xx
Element
IBExU
14
ATEX
1123
X
\xx
Special conditions for safe use
The design specifications of the manufacturer must be observed when
repairing flame-proof joints. Repair work based on the values of EN
60079-1 is not permissible.
The cable glands used are only to be employed for fixed installation.
Appropriate strain relief must be ensured on installation.
When replacing cable entries, make sure that these are suitable for a
sustained usage temperature of -55°C to +80°C.
At ambient temperatures below -20°C the connection lines must be
suitable for the corresponding usage temperature.
The heating element should only remain switched on at ambient
temperatures up to max. +30°C.
`
Temperature class T3, see EN
60079-0
Equipment protection level
Explanation
Certification body
Year of approval
In accordance with ATEX
product directive 2014/34/EU
Certificate number
The "X" symbol after the
certificate number indicates
special conditions for safe use of
the motors, which can be found
in these operating instructions.
Supplement to EC type
examination certificate for the
type concerned

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ibexu14atex1123

Table of Contents