Summary of Contents for Epcom RT Series

  • Page 1 Epcom Power Line RT Series TRUE ONLINE UPS 1KVA-3KVA User Manual RT Series True Online UPS |...
  • Page 2: Battery Safety Information

    Note: Symbol Instructions Caution Danger! High Turn on Turn off Standby or Voltage! Shutdown Protective Disable/mute Overload Battery Repeat Display screen Battery earth audible alarm inspection repeat key | RT Series True Online UPS...
  • Page 3: Product Overview

    > 150% load: transfer to bypass in 300 ms; Load crest From mains mode 0 ms (transfer time) to BAT mode From mains mode 4 ms (typical) to bypass Line mode Efficiency BAT mode ECO mode RT Series True Online UPS |...
  • Page 4 0*88 0*88 0*88 40*88 Weight (kg) 12.26 13.78 7.58 22.73 25.86 9.66 29.26 9.45 10.04 * Derate capacity to 70% in CUCF mode and to 90% when the output voltage is adjusted to 208Vac. | RT Series True Online UPS...
  • Page 5: Front Panel Features

    Note: The figure is for reference only. Due to the technology upgrading and development, the real unit might be different from the figure. ① ① ⑤ ⑥ c. 2KVAH-RT, 3KVAH-RT and 3KVAS-RT(96V) rear panel. RT Series True Online UPS |...
  • Page 6: Unpacking Inspection

    • If install a leakage current protective switch, please install it on output cable. • For 1-3K series long backup model units, you may need to prepare wires for terminals based on the following table. | RT Series True Online UPS...
  • Page 7 • Connect long battery cable to UPS terminals with correct poles link (red is for ‘+’, black is for ‘-‘), UPS will start charging automatically. • Connect the battery pack to the battery connector. RT Series True Online UPS |...
  • Page 8: Network Functions

    Normally, pin1 and pin2 are connected so that the machine can be working normally. When some emergencies happen, and when users have to cut off the output, just need to disconnect the connection between pin1 and pin2, or just pulling it out. | RT Series True Online UPS...
  • Page 9: Intelligent Card (Optional)

    ON: UPS is malfunctioning PIN2 ON: Alarm (system failure) PIN3 Ground PIN4 Remote shutdown PIN5 Common PIN6 ON: Bypass mode PIN7 ON: Battery low ON: Inverter mode PIN8 OFF: Bypass mode PIN9 ON: No AC power in RT Series True Online UPS |...
  • Page 10: Button Operation

    • Press the key for more than half a second (less than 2 seconds): go to the function setting options. • Press the key for more than 2 seconds: exit from this function settings interface. | RT Series True Online UPS...
  • Page 11: Display Interface

    76-100%) is indicated by the number of load bar sections illuminated. When UPS is overloaded, the load icon will flash. Mute Icon Indicates the audible alarm is disabled/mute. Press the mute key in the battery mode, the mute icon flash. RT Series True Online UPS |...
  • Page 12 Indicates UPS operation mode in 20 seconds, such as STDBY (standby Display Area mode), BYPASS (Bypass mode), LINE (AC mode), BAT (Battery mode), BATT (Battery Self Test mode), ECO (Economic mode), SHUTDN (Shutdown mode), CUCF (Constant Voltage and Constant Frequency mode). | RT Series True Online UPS...
  • Page 13: Ups On/Off Operation

    • When UPS is in BAT Mode, press the self-test/mute key for more than 1 second, the buzzer stops beeping. If you press the self-test/mute key for one more second, it will restart to beep again. RT Series True Online UPS |...
  • Page 14: Ups Settings

    100: output voltage is 100Vac. 100% 110: output voltage is 110Vac. 115: output voltage is 115Vac 120 (default): output voltage is 120Vac. 127: output voltage is 127Vac. 100% 100% 22 0 | RT Series True Online UPS...
  • Page 15 If frequency converter mode is enabled, you may 100% 100% 100% choose the following output frequency: 60 0 22 0 50 (default): presents output frequency is 50Hz. 60: presents output frequency is 60Hz. 100% 100% RT Series True Online UPS | 100% 100% 100%...
  • Page 16 ON: UPS will start up automatically and works in Line AUO Setting mode when connect mains. OFF: UPS won’t start up automatically when connect mains except EOD, it will work in standby or bypass mode (Default). | RT Series True Online UPS...
  • Page 17: Parameters Inquiring Operation

    100% 100% 100% 100% 100% 22 0 Input: Display the voltage and frequency of the input. As the following graphics shows, the input voltage is 220V, input 50 0 frequency is 50Hz. 100% 100% RT Series True Online UPS |...
  • Page 18: Operation Mode

    ECO function is on, the UPS works in ECO mode. If Ecco Mode input mains exceed the range of ECO several times within one minute but stays in inverter input range, UPS will work in inverting mode automatically. LCD displays ‘ECO’ . | RT Series True Online UPS...
  • Page 19: Fault Messages

    Communication fault unused 75, 76, 77, 78, 79 Communication fault 80, 81, 82, 83, 84 Relay fault 85, 86, 87, 88, 89 AC input SCR fault unused 90, 91, 92, 93, 94 CAN fault RT Series True Online UPS |...
  • Page 20 4 sec LCD illuminateswhen power on, and display the capacity of the UPS, some time later Power on / Switch on 6 beeps working mode displays Line or byPASS, bat icon flash all the time | RT Series True Online UPS...
  • Page 21 • The alarm code will be displayed in four digital tubes on the right of the numerical part of the LCD screen (red mark), as shown below: 100% Alarm icon Alarm code 100% • The alarm truth table during operations is shown as below: • ‘ ’ signifies the alarm occurs, blank signifies no alarm appears. RT Series True Online UPS |...
  • Page 22 Remote Battery Bypass Lost Overload Value Shutdown Disconnected The first digital tube from right to left Display Overcharging Mains Start-Up Charger Fault Value Warnings Reverse Abnormal The second digital tube from right to left | RT Series True Online UPS...
  • Page 23 Bypass Over Load Fault Mains Lost Value Abnormal The fourth digital tube from right to left Example: • If the alarm code “2000” appears on the LCD screen, it indicates loss of mains power. RT Series True Online UPS |...
  • Page 24: Troubleshooting

    Fault icon display, audible non-critical equipments, recount the buzzer alarm continually, Overload total capacity of your load and reduce the thefault code is 50-54 load to the UPS. Check whether the load equipments has fault or not. | RT Series True Online UPS...
  • Page 25 When the output is short-circuited, the action of UPS protection will show up. Before turning off the UPS, make sure to disconnect the entire loads and cut off the mains power supply, otherwiseit will make the AC inpushort circuit. CAUTION RT Series True Online UPS |...