Tyco Fire Product Alpha 4 Installation And Operating Instructions

Advertisement

Quick Links

Installation AND OPERATING INSTRUCTIONS

Applications

ALPHA 4 fire alarm systems are
the ideal choice for small to
medium size buildings such as:
 Motels
 Boarding houses
 Hostels
 Town houses
 Factories
 Warehouses
 Churches
 Community Centres

Ordering Information:

Panels and Accessories
FP0674 ALPHA 4 Fire Alarm
System
FA2438 Rear Service Index
(Spare)
FP0549 Test Probe
LT0182 ALPHA 4 Fire Alarm
System Technical
Manual
RR0038 Circuit EOLR 2k7
RR0045 Evacuation EOLR 10k
RR0048 Evacuation EOLR 18k
RR0050 Evacuation EOLR 27k
PA1028 ALPHA 4 PCB Assembly
HW0226 Spare door key
HW0213 Spare keyswitch key
Expected Times for Standby Operation (assumes a battery in good condition)
5 x 2-wire smoke detectors or 24 indicating heat detectors, 1A
sounder load.
5 x 2-wire smoke detectors or 24 indicating heat detectors, 3.5A
sounder load.
40 x 2-wire smoke detectors or 192 indicating heat detectors, 3.5A
sounder load.
Manufactured
Tyco Fire Protection Products,
by:
17 Mary Muller Drive, PO Box 19-545,
Christchurch, New Zealand
Telephone +64-3-389 5096
Facsimile +64-3-389 5938
LT0181
ALPHA 4
FIRE ALARM SYSTEM
Properly installed fire alarm systems using ALPHA 4 and approved fire
detectors and/or manual call points and alerting devices can comply with
the requirements of the NZ Building Code where fire safety precautions
types 2, 3, or 4 (non-connected), or Type 7 (non-connected) are
specified. ALPHA 4 also complies with NZS 4512:2003 and is FPA(NZ)
listed for use in automatic and manual fire alarm systems.
ALPHA 4 is compatible with indicating heat detectors, 2-wire smoke
detectors and indicating manual call points as detailed below. An
optional "legacy mode" is available for retrofit (affects all circuits),
offering compatibility with clean contact (normally closed) heat detectors
and manual call points and 2-wire smoke detectors.
Compatible Detectors
1841 Manual Call Point (indicating)
Heat Detector (clean contact) *
Manual Call Point (clean contact) *
Indi-VIGIL Indicating Heat Detector
Any clean contact normally-closed detector *
System Sensor 1151 Smoke Detector with B401 or B110 base (2-wire)
System Sensor 2151 Smoke Detector with B401 or B110 base (2-wire)
System Sensor 1400 Smoke Detector (2-wire)
System Sensor 2400 Smoke Detector (2-wire)
System Sensor 1451 Smoke Detector with B401 or B110 base (2-wire)
System Sensor 2451 Smoke Detector with B401 or B110 base (2-wire)
* Use of clean contact devices requires "Legacy Mode". See "Configuration".
(see page 3 for circuit limits)
Battery Capacity
Distributed in
Tyco Fire Protection Products,
New Zealand
6 Portage Road, PO Box 15-492,
by:
Auckland, New Zealand.
Telephone +64-9-826 1716
Facsimile +64-9-827 2288
Page 1
ALPHA 4
4Ah
83 hours
6.5Ah
83 hours
6.5Ah
75 hours
Issue 3.1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Alpha 4 and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco Fire Product Alpha 4

  • Page 1 FIRE ALARM SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS Applications Properly installed fire alarm systems using ALPHA 4 and approved fire detectors and/or manual call points and alerting devices can comply with ALPHA 4 fire alarm systems are the requirements of the NZ Building Code where fire safety precautions...
  • Page 2 ALPHA 250mm FIRE ALARM SYSTEM The location of ALPHA 4 should be chosen with these factors in mind:  Avoid excessively hot locations; this greatly reduces battery life.  Avoid humid or damp locations; condensation can cause faults or incorrect operation.
  • Page 3 manual call points is required, cut R47. This operation does not comply with NZS4512:2003 and is not compatible with indicating manual points. Cutting R47 selects this mode for all 4 detection circuits. Detector and Alerting Device Wiring This diagram shows the general format for connecting alerting devices or Mini-Gen tone generator and detectors.
  • Page 4 (0.5 seconds if in “Legacy Mode”) when any detector operates, but Alarm indicators latch. Smoke detectors are automatically reset on ALPHA 4. Also enables display of latched as well as current defects (Circuit Alarm LEDs show which circuits have or have had defects).

Table of Contents