Technical Data - SCE Enviro-Therm -AC1000B230V User Manual

Table of Contents

Advertisement

SAGINAW CONTROL & ENGINEERING • A/C USER MANUAL
B
Part Numbers
Cooling Capacity @ 95°F / 95°F
Cooling Capacity @ 131°F / 131°F
Heating Capacity
Compressor
Refrigerant
Refrigerant Charge
Max. Pressure
Operating Temperature Range
Max. Air Volume Flow
Mounting
Housing Material
Dimensions (H x W x D)
Weight
Cutout Dimensions
Rated Operating Voltage / Frequency
Rated Current @ 95°F / 95°F
Starting Current
Max. Current
Power Consumption @ 95°F / 95°F
Max. Power Consumption
Fuse Rating
SCCR
Circuit Breaker - MCB Type D or K Slow Acting
Connection
NEMA Protection Class
Approvals
Industry Standards
Sound Level at 1.5 meters
Max Voltage at Door Switch

5. Technical Data

2.5A (T) - Time Delayed [Slow Acting]
SCE-AC1000B230V
SCE-AC1000B230VSS
SCE-AC1000B230VSS6
1000 BTU (293 Watts)
875 BTU (256 Watts)
150 W
Reciprocating Compressor
R134a
115g / 4.05 oz
370 / 68 psig
-4°F - 131°F
Ambient Air Circuit: 50 cfm
Cabinet Air Circuit: 50 cfm
External
Mild Steel, Powder Coated
SS: Stainless Steel AISI 304
SS6: Stainless Steel AISI 316
18.90 x 9.84 x 7.50 inch
34.0 lbs
8.0 x 9.8 inch
230 V - 50/60 Hz
270 W
325 W
2.5A Slow Acting
Connection Terminal Block
NEMA 3, 3R, 4 & 12
SS: NEMA 3, 3R, 4, 4X & 12
CE / cURus / UL Listed
SS: IS20
65 db(A)
5 A DC
5
1.3 A
8 A
1.5 A
5kA
IS19
back to top

Advertisement

Table of Contents
loading

Table of Contents