FREEZE STATS SERIES
Installation & Operation Instructions
GENERAL INFORMATION
The FS Series are low limit controllers, also
known as "Freeze Stats". These devices were
designed for use on HVAC equipment that
require low-temperature cutout protection to
prevent cooling coils from freezing. They should
be mounted between the heating and cooling
coils on the supply side of the fan unit and
respond to the lowest temperature sensed
along any one foot section of the sensing
element. The FS Series has manual and
automatic reset versions, as well as, models that
feature one or two sets of SPDT contacts.
Numerous capillary lengths are also available.
MOUNTING INSTRUCTIONS
• Do not uncoil more element or capillary
than is required for the application.
• Do not sharply bend the element or
capillary more than necessary bending
hardens the element and makes it brittle. If
the element or capillary can be subjected to
vibration, protect any surface that makes
contact.
Strap the element on a coil; for example, in an
area where freezing can occur, or mounted in a
duct. Use as much of the element as necessary
for maximum protection. Use metal straps to
fasten the element to the coil to be controlled.
Use clips for mounting the element in a duct.
Locate the sensing element where it can sense
the average temperature of the space to be
controlled.
Locate the thermostat case where the ambient
temperature is always warmer than the set
point.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
FIGURE1: DIMENSIONS
FS-1
FS-2
FS-3
FS-4
FS-50
4.35" (110.49mm)
2.18"
(55.25mm)
FS-5
FS-6
3.65"
(92.71mm)
2.18"
(55.25mm)
4.35" (110.49mm)
Page 1
Phone: 1-888-967-5224
Website: workaci.com
4.53"
(115.01mm)
Available with 6' , 10' , 20'
& 50' Capillary Lengths
4.53"
(115.01mm)
Ø0.375"
(9.53mm)
Version: 10.0
I0000298