Page 1
AND UNDERSTAND ALL OF THESE REQUIREMENTS. FAILURE TO DO SO COULD CREATE A HAZARD RESULTING IN PROPERTY DAMAGE, BODILY INJURY, OR DEATH. Manual No.: 2100-376L Bard Manufacturing Company, Inc. Supersedes: 2100-376K Bryan, Ohio 43506 File: Volume III, Tab 20 Since 1914...Moving ahead just as planned.
CONTENTS Page Page 20. Checking Gas Input Rate ......26 & 27 Getting Other Information and Publications ....4 21. Standard Orifice Sizing & High WG Series Model Nomenclature ....... 5 Altitude Derate ..........28 Ventilation Options ............ 5 22. Conversion of Gas Input BTUH From High Air Conditioning Module Options .......
Canadian Electrical Code ......CSA C22.1 Canada. M9W 1R3 Telephone: (416) 447-4044 Canadian Installation Code……………CAN/CGA B149 COPYRIGHT SEPTEMBER 2003 BARD MANUFACTURING COMPANY, INC. BRYAN, OHIO 43506 USA Manufactured under the following U.S. patent numbers: 5,485,878; 5,002,116; 4,924,934; 4,875,520; 4,4825,936 Manual 2100-376L...
WALL MOUNT GAS/ELECTRIC GENERAL MODEL NUMBER NOMENCLATURE VENT REVISION MODEL CONTROL OPTIONS (See Table Below) Wall Mount Gas/Electric See Table page 6 COOLING CAPACITY COIL OPTIONS VOLTAGE 24 = 2 ton X = Standard A = 230/208-60-1 30 = 2½ ton 1 = Phenolic coated evaporator B = 230/208-60-3 COLOR...
AIR CONDITIONING MODULE OPTIONS STD = Standard equipment. CCM Compressor control module has adjustable 30 second to 5 minute delay-on-break timer. On initial power up, or any time the power is interrupted, the delay-on-make will be 2 minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit.
Any grille that meets with the 5/8 inch louver criteria on heat loss/heat gain calculations made according to may be used. It is recommended that Bard Return Air methods of Air Conditioning Contractors of America Grille or Return Filter Grille be installed when no (ACCA).
7. WALL MOUNTING INFORMATION WARNING 1. Two holes for the supply and return air openings must be cut through the wall as detailed in Figure 4. Failure to provide the one inch clearance 2. On wood-frame walls, the wall construction between the supply duct and a combustible must be strong and rigid enough to carry the surface for the first three feet of duct can...
FIGURE 3 COMBUSTIBLE CLEARANCE FOR WG24, WG30 AND WG36 MODELS FIGURE 3A COMBUSTIBLE CLEARANCE FOR WG42, WG48 AND WG60 MODELS WARNING minimum of one (1) inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first three (3) feet of ducting. It is important to insure that the one (1) inch minimum spacing is maintained at all points.
9. CLEARANCES TABLE 2 MINIMUM INSTALLATION CLEARANCES Minimum clearances, as specified in Table 2, must be maintained from adjacent structures to provide t e l ) s l r i f adequate fire protection, adequate combustion air, and ) s l room for service personnel.
11. OPTIONAL VERTICAL VENTING 10. VENT TERMINAL AND COMBUSTION AIR INLET HOOD With the optional vertical venting kit (VVK-5) this unit may be vented vertically through a roof or overhang. The vent terminal is shipped in the burner compartment. The kit includes a stainless steel transition drain tee, See Figure 7.
12. VENT RESIZING INSTRUCTIONS 13. FRESH AIR INTAKE All units are built with fresh air inlet slots punched in When an existing furnace is removed from a venting the service panel. system servicing other appliances, the venting system is likely to be too large to properly vent the remaining If the unit is equipped with a fresh air damper attached appliances.
15. WIRING – MAIN POWER ELECTRICAL GROUNDING When installed, the furnace must be electrically grounded in accordance with local codes or in the WARNING absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or Canadian Electrical Code, CSA22.1, latest edition. Use a copper wire from green For your personal safety, turn off electric ground wire on the furnace to a grounded connection in power at service entrance panel before...
FIGURE 10 INSTALLATION OF FLEXIBLE CONDUIT 16. WIRING – LOW VOLTAGE WIRING Direct Digital Controls (DDC) For total and proper control using DDC, a total of 5 Low Voltage Connection controlled outputs are required (4 if no ventilation is These units use a 24-volt AC low voltage circuit. installed).
18. GAS SUPPLY AND PIPING 8. Refer to Table 6 for Gas Pipe Sizes for natural gas. If more than one appliance is supplied from a single line size, capacity must equal or exceed the GENERAL RECOMMENDATIONS combined input to all appliances, and the branch 1.
5. Slowly open equipment shut off valve in gas supply PROPANE (LP) GAS CONVERSION line just ahead of furnace. Start furnace following “Operating Instructions” on front door. This unit may be converted in the field for 6. Slowly open 1/8" NPT manual shut off valve leading use with Propane (LP) gas.
Page 27
NATURAL GAS INPUT RATE 9. If you left water heater, dryer or range pilots on, allow for them in calculating correct furnace gas Natural gas heating value (BTU/cu. ft.) can vary input. A quick way is to allow 1,000 BTU per hour significantly.
It is the installer’s responsibility to see that the furnace 21. STANDARD ORIFICE SIZING AND HIGH ALTITUDE DERATE input rate is adjusted properly. Derating must be achieved by reducing the size of the main burner This furnace is shipped with fixed gas orifices for use orifices.
TABLE 8 NATURAL GAS ORIFICE TABLES FOR MODELS WG24, WG30 AND WG36 f i r f i r c t i i t l f i r f i r f i r f i r c t i i t l f i r f i r , y r...
Page 30
TABLE 8A NATURAL GAS ORIFICE TABLES FOR MODELS WG42, WG48 AND WG60 f i r f i r c t i i t l f i r f i r f i r f i r i t l c t i f i r f i r , y r...
22. CONVERSION OF GAS INPUT BTUH 2. Set balancing dampers in supply duct system. FROM HIGH TO LOW RATING 3. Check duct work for obstructions or leaks. All the derated WG series units are produced with 4. Make sure filters are clean and in place. maximum BTUH input orifices installed.
FIGURE 14 ACCESS INTERNAL FILTER THROUGH UPPER SERVICE DOOR 24. FILTERS HIGH PRESSURE SWITCH AND LOCKOUT SEQUENCE (Standard Feature) A 2" thick throwaway filter is supplied with each unit. If the high pressure switch opens, the compressor This filter is installed by opening the main service door. contactor will de-energize immediately.
Page 33
ALARM OUTPUT PHASE MONITOR Alarm terminal is output connection for applications All units with three phase scroll compressors are where alarm signal is desired. This terminal is powered equipped with a three phase line monitor to prevent whenever compressor is locked out due to HPC or LPC compressor damage due to phase reversal.
27. SERVICE AGENCY PROCEDURES FIGURE 16 TOP VIEW OF GAS CONTROL CAUTION Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. WARNING MIS-165 Follow these procedures before inspecting furnace.
ROUTINE MAINTENANCE WARNING 1. Air Filters – Check the condition at least monthly when the unit is in use, and replace as necessary. 2. Lubrication Requirements – The indoor circulating Disconnect electrical power before servicing air blower motor and outdoor circulating air fan unit.
31. SEQUENCE OF OPERATION – 30. SEQUENCE OF OPERATION – HEATING COOLING On a call for cooling from the room thermostat, the high On a call for heat from the thermostat, the induced draft speed blower relay will be energized as well as the blower is energized.
FIGURE 18 FURNACE CONTROL BOARD AND BLOWER CONTROL 32. INDOOR BLOWER OPERATION If it is desirable to have both HEAT/COOL blower motor speed at the same speed, install a jumper wire All models have multiple speed direct drive blower between “HEAT” and “COOL” terminals of the motors.
TABLE 10 WG24 INDOOR BLOWER PERFORMANCE 230 AND 460 VOLTS Recommended WG24 cooling airflow range at rated 800 CFM @ 0.15 ESP (WC) is 680 - 920 CFM Factory set on Low Speed for cooling and High for heating. Voltage adjustment – Reduce airflow by 100 CFM for 208 Volt Dehumidification coil adjustment –...
TABLE 11 WG30 INDOOR BLOWER PERFORMANCE 230 AND 460 VOLTS Recommended WG30 cooling airflow range at rated 1000 CFM @ 0.35 ESP (WC) is 820 - 1150 CFM Factory set on Medium Speed for cooling and for heating. Voltage adjustment – Reduce airflow by 100 CFM for 208 Volt Dehumidification coil adjustment –...
TABLE 12 WG36 INDOOR BLOWER PERFORMANCE 230 AND 460 VOLTS Recommended WG36 cooling airflow range at rated 1100 CFM @ 0.250 ESP (WC) is 935 - 1265 CFM Factory set on Medium Speed for cooling and for heating. Voltage adjustment – Reduce airflow by 100 CFM for 208 Volt Dehumidification coil adjustment –...
TABLE 13 WG42 INDOOR BLOWER PERFORMANCE 230 AND 460 VOLTS Recommended WG42 cooling airflow range at rated 1300 CFM @ .35 ESP (WC) is 1500 - 1030 CFM Factory set on Medium Speed for heating and cooling Voltage adjustment – Reduce airflow by 130 CFM for 208 Volt Top outlet adjustment –...
TABLE 14 WG48 INDOOR BLOWER PERFORMANCE 230 AND 460 VOLTS Recommended WG48 cooling airflow range at rated 1550 CFM @ .38 ESP (WC) is 1750 - 1280 CFM Factory set on High Speed for cooling and Medium Speed for heating. Voltage adjustment –...
TABLE 15 WG60 INDOOR BLOWER PERFORMANCE 230 AND 460 VOLTS Recommended WG60 cooling airflow range at rated 1650 CFM @ .30 ESP (WC) is 1910 - 1340 CFM Factory set on High Speed for cooling and Medium Speed for heating. Voltage adjustment –...
This relay completes the “Y” or compressor signal to the CCM (Compressor Control Module) during either a call for Cooling or a call for Dehumidification. Part of the Bard Manufacturing Company, Inc. control strategy on Dehumidification units is that Cooling always takes precedence over Dehumidification. This relay opens the circuit to the Dehumidification Solenoid Valve on a call for Cooling, effectively overriding the Dehumidification function in favor of the Cooling call.
34. PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Table 17 outlines expected pressures at various indoor and outdoor temperatures. TABLE 17 COOLING PRESSURE TABLE Low side pressure ±...
35. DEHUMIDIFICATION CIRCUIT separate desuperheating condenser circuit, which reheats the conditioned air before it is delivered to the The dehumidification circuit incorporates an room. The refrigerant gas is then routed from the independent heat exchanger coil in the supply air desuperheating condenser to the system condenser for stream.
36. REFRIGERANT CHARGE The nameplate charge quantity is optimized for thermal performance and efficiency of this self-contained The correct system R-22 charge is shown on the unit package system. rating plate. The system operating pressures in Table 18 are based You can reference Table 18 to validate proper system upon rated airflow across the evaporator during cooling cycle.
38. LOW-NOX BURNER ASSEMBLY “N” 37. FAN BLADE SETTING DIMENSIONS SUFFIX MODELS ONLY – U.S. Shown in Figure 20 is the correct fan blade setting INSTALLATIONS ONLY dimension for proper air delivery across the outdoor coil. NATURAL GAS MODELS ONLY Model numbers designated with an “N”...
TABLE 20 APPLICATION DATA FOR WG24*DA f r i Values shown in ( ) are BTUH of heating available at these conditions. Latent BTU = Lbs/Hr water * 1060 Sensible BTU = Total - Latent TABLE 21 APPLICATION DATA FOR WG30*DA f r i Values shown in ( ) are BTUH of heating available at these conditions.
TABLE 22 APPLICATION DATA FOR WG36*DA f r i Values shown in ( ) are BTUH of heating available at these conditions. Latent BTU = Lbs/Hr water * 1060 Sensible BTU = Total - Latent TABLE 23 APPLICATION DATA FOR WG42*DA f r i Values shown in ( ) are BTUH of heating available at these conditions.
TABLE 24 APPLICATION DATA FOR WG48*DA f r i Values shown in ( ) are BTUH of heating available at these conditions. Latent BTU = Lbs/Hr water * 1060 Sensible BTU = Total - Latent TABLE 25 APPLICATION DATA FOR WG60*DA f r i Values shown in ( ) are BTUH of heating available at these conditions.
Need help?
Do you have a question about the WG242DA and is the answer not in the manual?
Questions and answers