Download Print this page

Cooper Lighting Greengate OAWC-DT-120W Installation Instructions page 2

Dual technology wall / corner mounted low voltage occupancy sensor

Advertisement

One Sensor, Multiple Switchpacks
SENSOR WIRE LEAD LEGEND
Hot
Black
(Common)
Line
Line
Red
(10-30VDC)
Neutral
Blue
(Control)
**Use Black Lead for 120VAC
Yellow
(Control)
Use Orange Lead for 277VAC
Brown
(Switch-Blue Lead Control)
Cap Unused Lead
Load 1
Brown/White(Switch-Yellow Lead Control)
Black(Common)
Sensor's Isolated Relay
Red (15VDC)
Blue
Orange
(Normally Open)
Blue (Control)
Gray
(Common)
Switchpack
Purple
(Normally Closed)
Black
Red
Blue
Optional Greengate GMDS Switch-
Yellow
Blue Control Lead- Manual on/off
Brown
Brown/White
Orange
Gray
Purple
DIP Switch Settings
Time Delay
Activation
Activation
PIR Sensitivity
Walk-Through Mode
DIP Switch
Power Pack One
Power Pack Two
(-R model only)
1
2
3
Checkout and Adjustment
Adjustments should be made with the HVAC system ON. Use only insulated tools to make adjustments.
Self-Adjust
Sensor is shipped in the Self-Adjust Mode. This applies to time delay, US, and PIR sensitivity. In preparation for the
Installer Test, the time delay is set to 15 seconds, after the sensor is installed, powered ON and has stabilized, the unit will
time-out 15 seconds after the last motion detected. Coverage and sensitivity can be confirmed by watching the Green (US)
and Red (PIR) indicator LEDs on the front of the sensor, while moving around the room.
1. Walk around the room and monitor LEDs. LEDs should only turn ON for one second with each motion. (If LEDs do not
turn ON, go to Installer Adjustments - Sensitivity Adjustments Section)
2. Stand still six to eight feet away from the sensor for five seconds. LEDs should not turn ON. (If any LED turns ON, note
LED and go to Installer Adjustments – Sensitivity Adjustment section)
3. Walk outside the room and wait 15 seconds for the lights to turn OFF. (If lights do not turn OFF go to Installer
Adjustments Section)
4. Re-enter the room to activate sensor. (If lights do not turn ON go to Troubleshooting Section)
5. The unit will remain in Test Mode for 5 minutes then automatically exit Test Mode and go for 10 min. Time Delay User
Mode setting.
Note:
To place into Test Mode, toggle DIP Switch 10 out of its current position, wait 3 seconds, and then back in to its original position. To force
into 10 min User Mode move Dip Switches 1 and 2 down. (If DIP Switches 1 and 2 are already down, toggle DIP Switch 1 out of its current position,
wait 3
seconds, and then back to its original position) While in Test Mode, the LEDs will flash once per 1/4 second.
Installer Adjustments
Sensitivity Adjustments
Ultrasonic Sensitivity (Green LED) – Using a small flathead screw driver turn the green potentiometer so that the arrow
points UP.
1. Stand in different areas of the room and wave your hands.
2. If the Green LED does not turn ON, increase the US sensitivity by turning the green potentiometer clockwise in small
increments. Repeat Step 1.
3. Stand still six to eight feet away from sensor for five seconds. LED should not turn ON.
4. If Green LED turns ON without motion or is constantly ON decrease the US sensitivity by turning the green
potentiometer counter-clock-wise in small decrements. Repeat Step 3.
PIR Sensitivity
1. Stand in different areas of the room and wave your hands.
2. If the Red LED does not turn ON, check for any obstructions.
Hot
3. Stand still six to eight feet away from sensor for five seconds. LED should not turn ON.
Neutral
4. If Red LED turns ON without motion or is constantly ON adjust PIR sensitivity to 50% by moving DIP switch 5 UP.
**Use Black Lead for 120VAC
Use Orange Lead for 277VAC
Cap Unused Lead
Load 2
Field-of-view outside the space
Black(Common)
Blue
Red (15VDC)
1. Adjust PIR sensitivity to 50% by moving DIP switch 5 UP.
Blue (Control)
Switchpack
2. Adjust Ultrasonic Sensitivity.
To Additional Switchpacks
10 switchpacks Maximum
Daylight Adjustments (-R model only)
If this feature is not needed, leave the light level at maximum (fully clockwise).
The Daylighting feature prevents the lights from turning ON when the room is adequately illuminated by natural light. If there
is enough light in the room regardless of occupancy, the sensor will hold the lights OFF. If there is not enough light in the room,
the sensor will allow the lights to turn ON when occupied.
Full and Half Logic Modes (See DIP switch legend):
In both Full and Half Logic modes, lights connected to the yellow control lead will not turn ON upon occupancy activation,
should the ambient light level exceed the preset foot-candle level.
After activation:
Full Logic Mode – should the ambient light level exceed the preset foot-candle level, the lights connected to the yellow
LEDs
Override
Lighting Sweep
Daylighting Mode
control lead will turn OFF. The lights will remain OFF, until the ambient light level falls below the set point.
Half Logic Mode – the output state of the yellow control lead will not change with ambient light changes, after occupancy
activation. If the amount of natural light available rises above the setpoint, the daylight sensor will not turn the lights OFF while
occupancy is being detected.
(-R model only)
Note: Set the light level when the ambient light is at the level where no artificial light is needed. In order for this feature to
function, the yellow control lead must be wired.
1. With the load ON, put the sensor into Test Mode. To place into Test Mode, toggle DIP switch 10 out of its current position,
wait 3 seconds and then back in to its original position.
4
5
6
7
8
9
10
2. Set DIP switch 10 to Full or Half Logic Mode.
3. Set the light level to minimum (fully CCW).
4. Leave the room and let the sensor time-out so lights are OFF. Enter the space and lights should remain OFF.
5. Make sure not to block the sensor from the daylight source and adjust the light level potentiometer CW in small increments
until the lights are ON. (Pause 5 seconds between each adjustment)
6. Once the lights are ON, the load connected to the sensor will not turn ON if light levels are above the current illumination.
Time Delay Adjustments
People who remain very still for long periods of time may need a longer Time Delay than the default setting of 10 minutes.
As long as Auto is enabled, the sensor will respond to each pair of false-OFFs with no normal OFF in between, by alternately
making slight adjustments to either time delay (by 2 minute increments) or sensitivity, so there should be no need for manual
adjustment. If manual adjustment is desired, refer to Time Delay settings in DIP switch legend.
Reset sensor time delay to factory settings by moving DIP switches 1 and 2 down. (If DIP switches 1 and 2 are already down,
toggle DIP switch 1 out of its current position, wait 3 seconds, and then back to its original position)
Automatic Mode
In Automatic ON Mode, the lights turn ON when a person enters the room. If optional momentary low voltage switches are
used along with Automatic ON Mode, activating the switch(es) while the load is ON turns the load OFF. When the load is turned
OFF manually, as long as the sensor continues to detect occupancy the loads stay OFF. After the time delay expires, the lights
stay OFF and the sensor goes back to Automatic ON Mode. For wiring information for the optional momentary low voltage
switch(es), please see the wiring section of the installation instructions.
Manual Mode
In Manual ON Mode, the optional momentary low voltage switch(es) is required to turn the load(s) ON. Once activated the
sensor will maintain the lights ON until motion ceases and the time delay expires. While the room is occupied the BAS relay
remains active. After the time delay expires, the load(s) will automatically be turned OFF and the switch(es) must be used to turn
the load(s) ON unless there is motion detected within the 10 second re-trigger period.
Lighting Sweep Option
If selected, this DIP switch option forces an initial 60 second delay upon "power-up" to prevent false activation in buildings
with computer control systems.
1. Move DIP switch 9 UP.
Override
The Override setting allows the lights to remain ON in the unlikely event of sensor failure.
1. Move DIP switch 8 UP.
While in Override Mode, the optional low voltage momentary switch(es) will toggle the lighting load(s).
Printed in Malaysia
Troubleshooting
Issue
Possible Causes
Wall Switch OFF
If low voltage switch option is used, lights
Lights
may have been turned-off manually
Will Not
Turn ON
If all lights are required to turn ON adjust DIP
automatically
Daylighting Feature Enabled
Switch 10 and/or daylight potentiometer
Power interruption
Check incoming voltage and/or wiring
Lights
If all lights are required adjust DIP switch
Daylighting Feature Enabled
Will Not
Turn ON
manually
Power interruption
Check incoming voltage and/or wiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Override
Make sure sensor is not in Override Mode (DIP Switch 8 up)
Ultrasonic Sensitivity set High
potentiometer CCW in small decrements
Sensors should be installed minimum 4 - 6 feet away
Sensor installed close to an air vent
from any air vent and out of path of heavy airflow
Sensor installed close to indirect lighting
Sensors should be mounted away from indirect lighting.
Lights
It may be possible for the unit to have self-adjusted
Will Not
Self-adjust
the time delay to a 30 minute delay. If the lights do
Turn OFF
not turn OFF after 30 minutes follow next step
automatically
Maximum time delay is 30 Minutes. Check DIP
30 Minute Delay
Switches to verify DIP Switch settings. If lights do
not turn OFF at the set time delay, check next step
PIR activated by heat
source other than occupant
Check wiring to make sure sensor or
Bypass
Lights Will Not
Turn OFF
Override
Make sure sensor is not in Override Mode (DIP Switch 8 up)
automatically
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Warranties and Limitation of Liability
Please refer to www.cooperlighting.com under the Legal section for our terms and conditions.
Suggestions
Turn Wall Switch ON
Press low-voltage switch
10 and/or daylight potentiometer
Lower sensitivity by turning green
Move DIP Switch 5 up
switchpack are not bypassed
Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, GA 30269
P:770-486-4800
www.cooperlighting.com

Advertisement

loading

This manual is also suitable for:

Greengate oawc-dt-120w-r