- Only qualified personnel should work on this equipment, and only after becoming familiar with all safety instructions regarding installation, operation and maintenance procedures contained in this manual. In case of doubts, contact Rowan Elettronica srl. ROWAN ELETTRONICA s.r.l. - Via Ugo Foscolo, 20 - 36030 CALDOGNO - VI - ITALY 2 / 20...
The fan and the heat probe must be connected by the terminal board outside the PVC grid (lower side). ROWAN ELETTRONICA s.r.l. - Via Ugo Foscolo, 20 - 36030 CALDOGNO - VI - ITALY 3 / 20...
Note: in case supply voltage allows motor connection with delta configuration, it is possible to use the 6-wire type of connection (see setting on page 7 and diagram on page 4); with this type of connection the maximum power of cod. 310S can be multiplied by 1,73.
13-14 = 24VDC - 50mA “phase failure” emergency relay coil power supply . NOTE: for relay with incorporated diode, connect the positive to 13 and the negative to 14. ROWAN ELETTRONICA s.r.l. - Via Ugo Foscolo, 20 - 36030 CALDOGNO - VI - ITALY 6 / 20...
The regulation is activated by closing microswitches S17 and S18 (clockwise rotation increases maximum limit). ROWAN ELETTRONICA s.r.l. - Via Ugo Foscolo, 20 - 36030 CALDOGNO - VI - ITALY 7 / 20...
(typical application of ventilation control with temperature probe feedback); standard setting: regulation not activated. ROWAN ELETTRONICA s.r.l. - Via Ugo Foscolo, 20 - 36030 CALDOGNO - VI - ITALY 8 / 20...
Fans: INDUCTIVE LOAD CODE 310S actuation can be used to control the speed of fans driven by normal motors of unit power of up to approximately 0.75kW. Its use with more powerful fans would cause normal motors to dangerously sustain overcurrent at intermediate speeds;...
HIGH SLIP MOTOR SERVICE TERMINAL BOARD CONNECTION WITH TACHOMETER 1 - 2 TACHOMETER (normally not used with C310 regulator) 3 - 4 TEMP. TACHO PROBE 5 - 6 TEMPERATURE PROBE ROWAN ELETTRONICA s.r.l. - Via Ugo Foscolo, 20 - 36030 CALDOGNO - VI - ITALY 11 / 20...
P12 affects the gain and therefore closed-loop control precision. If it were necessary to modify the set-point setting range, regulate the minimum with trimmer P8 and the maximum with trimmer P9. ROWAN ELETTRONICA s.r.l. - Via Ugo Foscolo, 20 - 36030 CALDOGNO - VI - ITALY 12 / 20...
POWER TERMINAL BLOCK CONTROL TERMINAL BLOCK In this application the CODE 310S operates at current CLOSED-LOOP control through TA. The controlled current, and therefore the torque, is that of the Rowan motor that must wind and unwind material, maintaining a constant pull as coil diameter varies.
(terminals 6-9) 0VDC at 0°C and +10VDC at 40°C. At the CODE 310S control terminal block it is moreover possible to connect a minimum ventilation potentiometer with which you can set fixed minimum ventilation and fixed maximum ventilation to limit maximum cooling - this is done independently of automatic temperature control.
Page 15
CODE 251/92 acts as a transducer for the NI100 probe and supplies at output (terminals 6-9) 0VDC at 0°C and +10VDC at 40°C. At the CODE 310S control terminal block it is moreover possible to connect a minimum ventilation potentiometer with which you can set fixed minimum ventilation and fixed maximum ventilation to limit maximum cooling - this is done independently of automatic temperature control.
CURRENT SET-UP VOLTAGE SET-UP CODE 310S in this case is used as an OPEN-LOOP voltage regulator at the primary of a three-phase transformer. The voltage command is supplied to board CODE 310S by two CODE 268 instruments which operate in closed- loop control with direct voltage and current supplied at the load;...
- Connect one end of each screen singly to the common earth point of the control panel. - Avoid earth rings. - Equipment cod. 310S has been designed to operate in industrial area, complying with requirements of ; for this purpose, the general standard CEI EN 60204-1 has been applied, which complies with the essential safety requirements of standard 89/392/CEE, modified by standards CEE 91/368 - 93/44 - 93/68.