MMU2-1600GE
Malfunction Management Unit
Firmware Version 02.00.05
Operations Manual
NEMA TS 2 Amendment 4-2012 Malfunction Management Unit
16 Configuration Types of Flashing Yellow Arrows
This manual contains technical information for the
MMU2-1600GE series Malfunction Management Unit
pn 889-3819-00 Revision: April 2020

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MMU2-1600GE and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Reno A&E MMU2-1600GE

  • Page 1 Malfunction Management Unit Firmware Version 02.00.05 Operations Manual NEMA TS 2 Amendment 4-2012 Malfunction Management Unit 16 Configuration Types of Flashing Yellow Arrows This manual contains technical information for the MMU2-1600GE series Malfunction Management Unit pn 889-3819-00 Revision: April 2020...
  • Page 4 THE FOLLOWING PRODUCT WAS DESIGNED, INSPECTED, TESTED AND MANUFACTURED IN THE USA BY EBERLE DESIGN, INC. IN PHOENIX, ARIZONA. INFORMATION CONTAINED HEREIN IS PROPRIETARY TECHNICAL INFORMATION OF EBERLE DESIGN, INC. PUBLICATION, REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING. ALL REGISTERED TRADEMARKS OF EBERLE DESIGN INC.
  • Page 6: Table Of Contents

    MMU2-1600GE Series Operations Manual Table of Contents Section 1 General Description ..................1 Section 2 General Characteristics ................... 3 2.1 Inputs 3 2.1.1 AC Line ......................3 2.1.2 AC Neutral ....................3 2.1.3 Earth Ground ....................3 2.1.4 Field Terminals (Reds, Yellows, Greens, and Walks) ........3 2.1.5 Red Enable ....................
  • Page 7 2.5.11 Controller Voltage Monitor ................14 2.5.12 Local Flash ....................15 2.5.13 External Watchdog Monitoring ..............15 2.5.14 Programming Card Absent Monitoring ............16 2.6 Testing Modifiers ....................16 2.6.1 Flashing Don’t Walk Monitoring ..............16 2.6.2 PPLT5 Monitoring ..................16 2.6.3 Flashing Yellow Arrow Monitoring (FYA) ............16 2.6.4 LED Thresholds ...................17 2.6.5 Per Channel Red Enable................18 2.6.6 Modified CVM Latch ..................18...
  • Page 8 4.6.3.1 View Logs ...................43 4.6.3.2 Clear Logs ..................44 4.6.3.3 Clear All Logs ..................44 4.6.3.4 AC Logging Events Thresholds ............44 4.6.4 Date & Time Menu ..................45 4.6.4.1 View / Set Date and Time ..............45 4.6.4.2 View / Set Daylight Saving Time Ahead ..........45 4.6.4.3 View / Set Daylight Saving Time Back ..........45 4.6.4.4 View Up Time ..................45 4.6.5 Real Time Monitor Status Menu ..............45...
  • Page 10: Section 1 General Description

    Likewise, the monitor receives information from the Controller Unit corresponding to Controller Unit output commands to the 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 1 of 51...
  • Page 11 Model MMU2-1600GE (Reno Canada) For applications calling for a NEMA TS 2-2003 compliant Malfunction Management Unit with integral graphics display and Canadian Fast Flash monitoring and optional Ethernet network connector. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 2 of 51...
  • Page 12: Section 2 General Characteristics

    89V at the Red Enable input. This function is considered not enabled when the input voltage is less than 70V at the Red Enable input. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 3 of 51...
  • Page 13: Logic Ground

    Status bit (bit 79) in the Type 129 Frame to 1. At all other times, the Local Flash Status bit of the Type 129 Frame is set to 0. Typical Connection: Police Panel flash switch and/or inside cabinet flash switch 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 4 of 51...
  • Page 14: Port 1 Disable

    Programming cards supplied by Reno A&E have an integral serial EEPROM which can store the other settings for the monitor which are not programmed using soldered jumpers. See Section 3.5 for programming card connector pin assignments. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 5 of 51...
  • Page 15: Channel Compatibility

    This creates a useable range of 6 seconds to 16 seconds. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 6 of 51...
  • Page 16: Reset

    Time Clock setting differs from the Controller Time setting by more than two (2) seconds, The Real Time Clock will be synchronized to the Controller clock. In the event that the Real Time Clock setting differs 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 7 of 51...
  • Page 17: Up Time Accumulator

    Test Preformed: While a channel has a Green, Walk, or Yellow display active, the channel is tested to see if a non-permissive channel has a Green, Walk, or Yellow display active at the same time. If concurrently active 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 8 of 51...
  • Page 18: Red Fail Monitoring

    Power loss or power interruption will not reset this fault. The Reset log will record the resetting of this fault. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 9 of 51...
  • Page 19: Dual Indication Monitoring

    Load Switch Flash bit (bit 112) of the Type 0 Frame: All dual indication testing will be disabled when this bit is set to one. Feature Interactions: Field Check: Enabling dual indication monitoring will also enable field check monitoring. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 10 of 51...
  • Page 20: Gy-Dual Indication Monitoring

    2.7 seconds. When each Green turns off a 2.7 second timer is started. A Yellow must start within 1 second of the Green turning off. If the Red turns on before the Yellow, a short Yellow fault will be generated to show that 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 11 of 51...
  • Page 21: Short Clearance Monitoring

    INDICATION OFF, no MYCD jumper, and is not selected as a pedestrian channel then the unused indication (Green or Yellow) of the FYA channel is ignored for Short Clearance. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 12 of 51...
  • Page 22: Field Check Monitoring

    Port 1 Disable: Port 1 failures will be ignored when this input is below 8V Type Select: Port 1 failures will be ignored when this input is in the Type 12 mode (Unterminated or above Feature Interactions: None 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 13 of 51...
  • Page 23: Volt Monitor I

    When the CVM input is detected as improper for more than 175 milliseconds, the monitor generates a fault. A CVM failure during the programmed Minimum Flash time or during a monitor Power Failure shall not cause a fault. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 14 of 51...
  • Page 24: Local Flash

    Power loss or power interruption will not reset this fault. The Reset log will record the resetting of this fault. Modifying Inputs: None 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 15 of 51...
  • Page 25: Programming Card Absent Monitoring

    Configuration: The Wizard configures 16 types of FYA left turn configurations. To manually set up FYA in the CONFIG SETTINGS MENU select the PERM LEFT (FYA) and FYA OPTIONS. PERM LEFT (FYA) 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 16 of 51...
  • Page 26: Led Thresholds

    Red Fail: Normal red fail testing senses Greens, Yellows, and Walks as ON when their voltage is above 25V and OFF when below 15V . Reds are ON when their voltage is above 70V and OFF when below 50V 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 17 of 51...
  • Page 27: Per Channel Red Enable

    Configuration: The setting of 24V-2 to 12VDC determines if this feature is active. A low on the +24V Monitor Inhibit input inhibits the operation of the +12 Volt Monitor. The testing default for this feature is set to no. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 18 of 51...
  • Page 28: Disable Local Flash

    2.7.1 TIME CHANGE LOG The Time Change Log records the 50 most recent time changes. Data recorded: Original Date / Time Stamp, New Date / Time Stamp, and Up Time Accumulator. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 19 of 51...
  • Page 29: Monitor Reset Log

    A diagnostic failure is not reset by a monitor Power Failure. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 20 of 51...
  • Page 30: Memory

    DSP Diagnostic 4000h The DSP is indicating that it has a diagnostic error. Error During the Boot 8000h The fault identified above was found during the boot process. Process 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 21 of 51...
  • Page 31: Section 3 Specifications

    False ......> +16 VDC : Meets and/or exceeds NEMA TS 2-2003 specifications. The monitor can be manually reset by depressing ESET the RESET pushbutton on the front panel. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 22 of 51...
  • Page 32: Timing Functions

    : Flashing if state changes are > 200 msec and < 600 msec Typical ..... 500 msec LASHING No Fault ..< 1400 msec Respond ..>1600 msec Typical ... 1500 msec 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 23 of 51...
  • Page 33: Connector Pin Assignments

    Cabinet Interlock A Cabinet Interlock B Cabinet Interlock B Channel 14 Yellow Channel 6 Walk Channel 16 Green Channel 4 Walk Spare 2 Spare 2 Type Select Type Select 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 24 of 51...
  • Page 34 No Connection Not Used (Terminated) RX Data - No Connection Port 1 Disable (0 VDC = Disable) RX Clock - Earth Ground TX Data - Reserved TX Clock - 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 25 of 51...
  • Page 35: Programming Card Pin Assignments

    Jumper Open Open Jumper Jumper Open Jumper Open Jumper Open Jumper Jumper Jumper Jumper Open Open Jumper Jumper Open Jumper Jumper Jumper Jumper Open Jumper Jumper Jumper Jumper 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 26 of 51...
  • Page 36: Section 4 User Interface

    Connector A • Channel Green, Yellow, and Walk Inputs • Output Relay • • +24V Monitor I • +24V Monitor Inhibit • Cabinet Interlock • Type Select 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 27 of 51...
  • Page 37: Graphic Display Menu Structure

    ID Info Ethernet Settings Status DC Inputs Ethernet Port Stats DC Processor Com Stats Log View Config Pending Diag Stats SDLC Speed Stats Logging Thresholds Config Fault Location PC Factory 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 28 of 51...
  • Page 38: Front Panel Display And Pushbuttons

    HELP or ESCAPE pushbuttons to exit the help system. When a fault is displayed at the Run Time display, pressing the HELP pushbutton will display information about this type of fault and how to troubleshoot it. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 29 of 51...
  • Page 39: Run Time Display

    To navigate to the selected menu item, press the ENTER pushbutton. A grayed out menu item is not accessible. The item will be skipped when navigating within the menu screen. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 30 of 51...
  • Page 40: Identification Menu

    GATEWAY IP – The Gateway IP address can be user configured from 0.0.0.0 to 255.255.255.255. The factory default setting is 0.0.0.0. This field is to support future features and currently is not used. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 31 of 51...
  • Page 41: Configuration Menu

    NOTE: The monitor will provide an audible confirmation of restoration of a previous configuration by sounding the buzzer (five chirps). 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 32 of 51...
  • Page 42 Minimum Flash time used and that the jumpered value cannot be less than five seconds. If the jumpered value is less than five seconds, it will be displayed as five seconds as this will be the value used. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 33 of 51...
  • Page 43 CO-CHAN INCLUDES YEL – When this feature is enabled the monitor will include the yellow of the child channels as well as the green (and the Walk if in Type 12 mode). The factory default for this feature is NO. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 34 of 51...
  • Page 44 EASY FYA PROGRAMMING –– If NO is selected then permissive jumpers are required between the FYA channel and the associated protected channel. If YES is selected then the permissive jumpers are required between 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 35 of 51...
  • Page 45 See Section 2.6.9 for more information. ECONOLITE FRAMES – When this feature is enabled the monitor will respond to special SDLC frames requested by Econolite controllers. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 36 of 51...
  • Page 46 Bit 81 of the Type 129 Response Frame will be set to 1 to indicate a flash rate failure. If YES is selected and a FYA is on for more than 700 milliseconds the FYA will be treated as a solid yellow arrow indication. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 37 of 51...
  • Page 47 MMU2 channels available. The Red and Yellow or the Green of the Protected Left Turn has to be rewired. 11RY 15RY 2 5G 2 5G 13RY 2 11G 2 15G 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 38 of 51...
  • Page 48 Peds in the FYA Configuration Type G and H. This leaves 4 MMU2 channels available. There is also less cabinet rewiring, because the protected phase remains in 1, 3, 5, 7. 3RYG 7RYG 3RYG 7RYG 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 39 of 51...
  • Page 49 13,14,15,16 as FYAs. The MMU2 all 16 channels to monitor the 8 phases and 4 Peds. There is less cabinet rewiring, because the protected phase remains in 1, 3, 5, 7. 3RYG 7RYG 3RYG 7RYG 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 40 of 51...
  • Page 50 Press HELP at each warning to receive additional information on each warning. The wizard will not tell you which permissive jumpers to install 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 41 of 51...
  • Page 51: General Settings

    Clear individual logs. CLEAR ALL LOGS Clear all logs. LOGGING THRESHOLDS View and/or edit the AC Logging Threshold settings of high voltage alarm, low voltage alarm, and power interrupt duration. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 42 of 51...
  • Page 52: View Logs

    Use the up (▲) or down (▼) pushbutton to scroll through the list of features that are different. Press the ENTER pushbutton or the ESCAPE pushbutton to exit. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 43 of 51...
  • Page 53: Clear Logs

    NOTE: When the Clear All Logs function is used, the monitor will provide an audible confirmation by sounding the buzzer (five chirps). 4.6.3.4 AC LOGGING EVENTS THRESHOLDS See Section 4.6.2.2.1 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 44 of 51...
  • Page 54: Date & Time Menu

    NOT AVAILABLE IN TYPE 12 will be displayed. Press the ENTER pushbutton or the ESCAPE pushbutton to exit. NOTE: A more condensed version of this information is available by pressing ESCAPE at the Run Time display. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 45 of 51...
  • Page 55: Other Ac And Miscellaneous Inputs

    (BOOT1), secondary bootloader (BOOT2), main monitor code (MAIN), AC signal processor (DSP), and DC signal processor (DC). This display is view only. Press the ESCAPE pushbutton to exit. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 46 of 51...
  • Page 56: Diagnostic Statistics Menu

    The indicator for a field input will be on if the RMS voltage over the last 33 milliseconds (two cycles of AC power) is above the threshold for that type of input. (See Section 3.2 for the voltage levels for each type of input.) 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 47 of 51...
  • Page 57: Power / Type Indicators

    Any monitoring function that is disabled for any reason will display a Function Disabled indication. 4.7.5 FUNCTION DISABLED INDICATION When a function has been disabled, the associated indicator will turn on for 50 milliseconds once every two seconds. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 48 of 51...
  • Page 58: Audible Buzzer

    RESET pushbutton or Save Changes is confirmed in fault monitoring configuration on the front panel, the pending changes will be lost and the original settings will be used on power up. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 49 of 51...
  • Page 59: Section 5 Firmware Upgrade

    This ensures that the user cannot inadvertently upgrade a monitor with the incorrect firmware and that the firmware file has not been tampered with. 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 50 of 51...
  • Page 60 ID Info Ethernet Settings Status DC Inputs Ethernet Port Stats DC Processor Com Stats Log View Config Pending Diag Stats SDLC Speed Stats Logging Thresholds Config Fault Location PC Factory 889-3819-00 MMU2-1600GE series Operations Manual Rev Apr 2020 Page 51 of 51...

Table of Contents