Technical Data PR216-219-508-01 Installation and user manual for the BiWire / Conventional Repeater Panel EFBWCV-REPEATER www.acornfiresecurity.com...
www.acornfiresecurity.com Installation and user manual for the Technical Data PR216-219-508-01 BiWire / Conventional Repeater Effective March 2017 Introduction Purpose This manual is intended as a guide for the installation and commis- sioning of the BiWire / Conventional Repeater panel . The content of this guide is intended to assist the user to install a fire alarm system and does not specify the detailed design of the product .
www.acornfiresecurity.com Technical Data PR216-219-508-01 Installation and user manual for the BiWire / Conventional Repeater Effective March 2017 Power Supply Equipment (PSE) The PSE has been specifically designed to operate the panel and may not be substituted for any other power source . The PSE is a Switch Mode Power Supply located within the cabinet as shown below .
www.acornfiresecurity.com Installation and user manual for the Technical Data PR216-219-508-01 BiWire / Conventional Repeater Effective March 2017 System Wiring As the repeater panel have integral power supplies the only wiring that is required is the mains input to the power supply unit and the data cable between the Fire Panel and each repeater panel as illustrated in Figure 3 .
Page 6
www.acornfiresecurity.com Technical Data PR216-219-508-01 Installation and user manual for the BiWire / Conventional Repeater Effective March 2017 ON (---------) Indicator lit Indicator unlit SLOW ( - - - - ) Indicator slow flashing, buzzer slow pulsing FAST ( - - - - - ) Indicator fast flashing, buzzer fast pulsing SILENT Sounders off, buzzer off...
www.acornfiresecurity.com Installation and user manual for the Technical Data PR216-219-508-01 BiWire / Conventional Repeater Effective March 2017 Repeater I/O The Fire Panel provides a monitored RS485 bus that allows for up to 3 passive repeater panels to be connected to it . The repeater panels have their own power supplies so no power connection is required from the Fire Panel .
www.acornfiresecurity.com Technical Data PR216-219-508-01 Installation and user manual for the BiWire / Conventional Repeater Effective March 2017 Installation Instructions NOTE This section of this guide explains in detail how the panel should be installed and configured to function properly . WHEN INSTALLED THIS EQUIPMENT IS SUBJECT TO Please ensure you have fully understood the components of the THE EMC DIRECTIVE 2004/108/EC.
REASONABLY WELL VENTILATED PLACE, AND NOT IN DIRECT SUNLIGHT. TEMPERATURES IN EXCESS OF 40°C AND BELOW 5°C MAY CAUSE MALFUNCTIONS, IF IN DOUBT CONSULT EATON ELECTRICAL SYSTEMS. THE PANEL SHOULD BE LOCATED AWAY FROM ANY POTENTIAL HAZARD, IN A POSITION WHERE IT IS...
Page 10
www.acornfiresecurity.com Technical Data PR216-219-508-01 Installation and user manual for the BiWire / Conventional Repeater Effective March 2017 Once the cable entry holes have been cut then fit the cable • glands to the back box . If the panel is being flush mounted, then insert the panel into •...
Page 11
www.acornfiresecurity.com Installation and user manual for the Technical Data PR216-219-508-01 BiWire / Conventional Repeater Effective March 2017 Connecting the Mains Supply Connecting the Battery Supply The mains supply should be exclusive to the fire alarm as detailed A Battery cover is supplied to prevent accidental contact with in BS5839 .
Page 12
www.acornfiresecurity.com Technical Data PR216-219-508-01 Installation and user manual for the BiWire / Conventional Repeater Effective March 2017 Battery Connections 1. Connect the BLACK battery wire to the BLACK (-) battery terminal of Battery B (Figure 23) 2. Connect the RED battery wire to the RED (+) battery terminal of Battery A (shown as grey) 3.
Page 13
www.acornfiresecurity.com Installation and user manual for the Technical Data PR216-219-508-01 BiWire / Conventional Repeater Effective March 2017 Connecting a Repeater Panel If a single Repeater panel is being connected to the Fire Panel then simply connect one end of the twisted pair cable to the Repeater I/O terminals on the Fire Panel and the other end of the cable to the Repeater I/O terminals on the Repeater Panel (see Figure 15), observing correct polarity (+ to + ., - to -) .
www.acornfiresecurity.com Technical Data PR216-219-508-01 Installation and user manual for the BiWire / Conventional Repeater Effective March 2017 Installation Testing Battery Fault Detection Check Disconnect the battery of the repeater panel . Initial Power-up Check Power up the panel by engaging the fuse spur to supply mains, After about 20 seconds check the Repeater Power Fault indicator then connect the white socket of the battery cable to the power is on .
www.acornfiresecurity.com Installation and user manual for the Technical Data PR216-219-508-01 BiWire / Conventional Repeater Effective March 2017 Operating Instructions Multi-Function Buttons The numerical value in the centre of the button is used to enter access codes for level 2 . Mute Buzzer This function is available at access level 1 and 2 .
Technical Data PR216-219-508-01 Installation and user manual for the BiWire / Conventional Repeater Effective March 2017 Technical Specification Panel Specification EFBWCV-REPEATER Power Specification Input Voltage Range 18 .75-30 .7V DC Maximum current drawn from battery 2 .7A Communication Ports...
www.acornfiresecurity.com Installation and user manual for the Technical Data PR216-219-508-01 BiWire / Conventional Repeater Effective March 2017 Manufacturers Contact Details www.acornfiresecurity.com...