CONTENTS PAGE 1 - MONITORING AND REGULATION 1.1 Controller 1.2 The pLDPRO terminal 1.3 The controller 1.4 Description of the air handling units 1.5 Controller inputs and outputs 2 - CONFIGURING THE CONTROLLER 2.1 Configuring with master EC Mono Boxes only: 2.2 Configuring with slave EC Mono Boxes only: 2.3 State of the pLAN 3 - MANAGING A NETWORK OF MULTIPLE CONTROLLERS...
1 - MONITORING AND REGULATION 1.1 Controller Each air heater is managed by the controller. In addition to its control functions, it also monitors and detects any faults with the air handling unit. IMPORTANT: To avoid any problems, the password must be known only by qualified personnel. 1.2 The pLDPRO terminal The terminal is supplied equipped with an LCD screen (8 lines x 22 characters) with six control keys.
1.3 The controller The descriptions of the terminals on the controller are provided below. RJ11 connector for the pLDPRO J1 - power supply configuration terminal (pLAN) 230 V controller supply RX-/TX- 3-point connector to connect up +Vdc RX+/TX+ other units (pLAN) Passive sensors power supply J2 - probe supply +5 Vref...
2 - CONFIGURING THE CONTROLLER The controller and display must be configured before the unit is commissioned. 2.1 Configuring with master EC Mono Boxes only: The value of the display's factory-set address is '32'. It is pointless to only change it in the master EC Mono Box. If the nn field is set to '0', the terminal will use the Point-to-Point Protocol (not the pLAN) to communicate with the controller and the “I/O Board address: xx”...
2.2 Configuring with slave EC Mono Boxes only: To configure the various slaves, the pLDPRO terminal must be removed from the master unit and connected to the slave units. a) For the first slave: ● Power up the Slave EC Mono Box ●...
Page 8
c) Assigning pLDPRO/Master EC Mono Box display links: ● Connect the display to the Master EC Mono Box ● To switch to configuration mode, simultaneously press the , and , keys for approx. 5 seconds; the page shown below will be displayed, with the cursor flashing in the top left corner: Display address Setting …………….
Page 9
P:01 Adr Priv/Shared Trm1 32 Sh Trm2 None Trm3 None -- Ok?No ● Go to 'No' by pressing several times, select 'Yes' by pressing then . The Master EC Mono Box/display connection has been made, the same operation must now be repeated on the Slave EC Mono Box(es): c) Assigning pLDPRO/Slave EC Mono Box display links: ●...
The Slave EC Box/display connection no. 1 has been made, if there are other slave boxes to be configured, repeat point d) by increasing the I/O Board address by 1 each time (e.g. for the 2nd slave: I/O Board address 3; for the 3rd slave: I/O Board address 4, etc.).
3.2 Addressing the pLAN There is a range of 32 possible addresses (binary logic). As a result, a total of 32 controllers and terminals can be connected over the pLAN network. The pLAN network will not work if the same address is shared by two components! pLDPRO display Address: 32...
Page 12
"Prg" key Menu □14.Access level □16.Versions □1.Setpoints □2.Machine status □4.Machine parameters To switch to another menu, press the or keys to scroll through the available menus. The selected menu is opposite the arrow and on a black background. To confirm your choice, simply press . The available menus are as follows: Setpoints Machine status...
4.2 Setpoint menu Description Unit Min. Max. By default Increment Visibility Levels Setpoints menu P150 Cooling comfort temperature setpoint °C Comfort P151 Eco cooling temperature setpoint °C cooling stp P152 Heating comfort temperature setpoint °C P153 Eco heating temperature setpoint °C Comfort heating stp P154...
4.4 Settings parameters menu Possible Description Unit Min. Max. Increment Visibility Levels default choices 0 - French P100 Language 1 - English 00:00 P101 Time 00:00 23:59 01/01/2014 P102 Date 01/01/2010 31/12/2050 0 - Cooling P110 Operating mode 1 - Heating If coil type = mixed 2 - Auto 0 - Comfort...
4.5 Read-only parameters menu Description Unit Min. Max. By default Increment Possible choices Visibility Levels P250 Aérotherm sensor temperature °C If 42AMA P251 42AMA sensor temperature °C present = YES P255 Aérotherm fan speed If 42AMA P256 42AMA fan speed present = YES P257 Valve opening...
4.7 Time schedule The time must be set for the time schedule to work correctly. The user will choose an operating mode in the operating mode parameter. When there is a time schedule active according to the periods below, the regulation will deviate from the current mode and switch into the mode selected by the time schedule.
4.9 Test mode menu Overriding the outputs Unit off If all the controller's outputs are overridden, the alarms will not be signalled on the display. Disconnecting the display will maintain the override and may result in damage to the hardware. This menu can only be accessed in level 3 and with the unit off.
Page 18
If access level 2 selected and access level = 1 Access levels LEVEL 2 ACCESS Password: 0000 Re-enter the installer password If password ok Access levels LEVEL 2 ACCESS Enter new code level 2? If yes, change the installer password. If no, back to current access level page Access levels LEVEL 2 ACCESS New password:...
5 - CONTROL 5.1 Starting the machine Switching from OFF/ON or ON/OFF is done locally by pressing the 2 and keys on the display. 5.2 Aérotherm air heater control: 5.2.1 Choosing the type of operation: This setting is used to choose the regulation operation mode. CFt: Comfort ECO: Economy H.GL: Frost Protection...
Page 20
5.2.2 Managing the 0-10 V output for valve control 5.2.2.1 Mixed, heating and cooling coil. Used to set the control box's operating mode. This parameter only appears for mixed coils. - WINTER. Heating and fan override. - SUMMER. Cooling and fan override. - AUTO.
5.2.2.3 Cooling coil, COOLING mode "Off" position: the valve is closed "COMFORT" position: the opening of the valve will depend on the difference between the regulated temperature value (room) and the setpoint. Regulation will only start after a 30-second time delay on the fan operation feedback contact. An integral action must be entered into the parameters.
5.4 The fault relays One relay per fault summary level is provided - "Maintenance" fault summary - "Danger" fault summary "Maintenance" faults are faults which only send information to notify the operator. They can be validated by pressing the for 3 seconds if they have disappeared. The "Danger"...
Page 24