CO NTRO L MANUAL
EC Mono Box
42AM - 42AMA
Original instructions FR7515390-00, 03.2017

Advertisement

Table of Contents
loading

Summary of Contents for United Technologies Carrier 42AM

  • Page 1 CO NTRO L MANUAL EC Mono Box 42AM - 42AMA Original instructions FR7515390-00, 03.2017...
  • Page 3: Table Of Contents

    CONTENTS PAGE 1 - MONITORING AND REGULATION 1.1 Controller 1.2 The pLDPRO terminal 1.3 The controller 1.4 Description of the air handling units 1.5 Controller inputs and outputs 2 - CONFIGURING THE CONTROLLER 2.1 Configuring with master EC Mono Boxes only: 2.2 Configuring with slave EC Mono Boxes only: 2.3 State of the pLAN 3 - MANAGING A NETWORK OF MULTIPLE CONTROLLERS...
  • Page 4: Monitoring And Regulation

    1 - MONITORING AND REGULATION 1.1 Controller Each air heater is managed by the controller. In addition to its control functions, it also monitors and detects any faults with the air handling unit. IMPORTANT: To avoid any problems, the password must be known only by qualified personnel. 1.2 The pLDPRO terminal The terminal is supplied equipped with an LCD screen (8 lines x 22 characters) with six control keys.
  • Page 5: The Controller

    1.3 The controller The descriptions of the terminals on the controller are provided below. RJ11 connector for the pLDPRO J1 - power supply configuration terminal (pLAN) 230 V controller supply RX-/TX- 3-point connector to connect up +Vdc RX+/TX+ other units (pLAN) Passive sensors power supply J2 - probe supply +5 Vref...
  • Page 6: Configuring The Controller

    2 - CONFIGURING THE CONTROLLER The controller and display must be configured before the unit is commissioned. 2.1 Configuring with master EC Mono Boxes only: The value of the display's factory-set address is '32'. It is pointless to only change it in the master EC Mono Box. If the nn field is set to '0', the terminal will use the Point-to-Point Protocol (not the pLAN) to communicate with the controller and the “I/O Board address: xx”...
  • Page 7: Configuring With Slave Ec Mono Boxes Only

    2.2 Configuring with slave EC Mono Boxes only: To configure the various slaves, the pLDPRO terminal must be removed from the master unit and connected to the slave units. a) For the first slave: ● Power up the Slave EC Mono Box ●...
  • Page 8 c) Assigning pLDPRO/Master EC Mono Box display links: ● Connect the display to the Master EC Mono Box ● To switch to configuration mode, simultaneously press the , and , keys for approx. 5 seconds; the page shown below will be displayed, with the cursor flashing in the top left corner: Display address Setting …………….
  • Page 9 P:01 Adr Priv/Shared Trm1 32 Sh Trm2 None Trm3 None -- Ok?No ● Go to 'No' by pressing several times, select 'Yes' by pressing  then . The Master EC Mono Box/display connection has been made, the same operation must now be repeated on the Slave EC Mono Box(es): c) Assigning pLDPRO/Slave EC Mono Box display links: ●...
  • Page 10: State Of The Plan

    The Slave EC Box/display connection no. 1 has been made, if there are other slave boxes to be configured, repeat point d) by increasing the I/O Board address by 1 each time (e.g. for the 2nd slave: I/O Board address 3; for the 3rd slave: I/O Board address 4, etc.).
  • Page 11: Addressing The Plan

    3.2 Addressing the pLAN There is a range of 32 possible addresses (binary logic). As a result, a total of 32 controllers and terminals can be connected over the pLAN network. The pLAN network will not work if the same address is shared by two components! pLDPRO display Address: 32...
  • Page 12 "Prg" key Menu □14.Access level □16.Versions □1.Setpoints □2.Machine status □4.Machine parameters To switch to another menu, press the  or  keys to scroll through the available menus. The selected menu is opposite the arrow and on a black background. To confirm your choice, simply press  . The available menus are as follows: Setpoints Machine status...
  • Page 13: Setpoint Menu

    4.2 Setpoint menu Description Unit Min. Max. By default Increment Visibility Levels Setpoints menu P150 Cooling comfort temperature setpoint °C Comfort P151 Eco cooling temperature setpoint °C cooling stp P152 Heating comfort temperature setpoint °C P153 Eco heating temperature setpoint °C Comfort heating stp P154...
  • Page 14: Settings Parameters Menu

    4.4 Settings parameters menu Possible Description Unit Min. Max. Increment Visibility Levels default choices 0 - French P100 Language 1 - English 00:00 P101 Time 00:00 23:59 01/01/2014 P102 Date 01/01/2010 31/12/2050 0 - Cooling P110 Operating mode 1 - Heating If coil type = mixed 2 - Auto 0 - Comfort...
  • Page 15: Read-Only Parameters Menu

    4.5 Read-only parameters menu Description Unit Min. Max. By default Increment Possible choices Visibility Levels P250 Aérotherm sensor temperature °C If 42AMA P251 42AMA sensor temperature °C present = YES P255 Aérotherm fan speed If 42AMA P256 42AMA fan speed present = YES P257 Valve opening...
  • Page 16: Time Schedule

    4.7 Time schedule The time must be set for the time schedule to work correctly. The user will choose an operating mode in the operating mode parameter. When there is a time schedule active according to the periods below, the regulation will deviate from the current mode and switch into the mode selected by the time schedule.
  • Page 17: Test Mode Menu

    4.9 Test mode menu Overriding the outputs Unit off If all the controller's outputs are overridden, the alarms will not be signalled on the display. Disconnecting the display will maintain the override and may result in damage to the hardware. This menu can only be accessed in level 3 and with the unit off.
  • Page 18 If access level 2 selected and access level = 1 Access levels LEVEL 2 ACCESS Password: 0000 Re-enter the installer password If password ok Access levels LEVEL 2 ACCESS Enter new code level 2? If yes, change the installer password. If no, back to current access level page Access levels LEVEL 2 ACCESS New password:...
  • Page 19: Control

    5 - CONTROL 5.1 Starting the machine Switching from OFF/ON or ON/OFF is done locally by pressing the 2  and  keys on the display. 5.2 Aérotherm air heater control: 5.2.1 Choosing the type of operation: This setting is used to choose the regulation operation mode. CFt: Comfort ECO: Economy H.GL: Frost Protection...
  • Page 20 5.2.2 Managing the 0-10 V output for valve control 5.2.2.1 Mixed, heating and cooling coil. Used to set the control box's operating mode. This parameter only appears for mixed coils. - WINTER. Heating and fan override. - SUMMER. Cooling and fan override. - AUTO.
  • Page 21: 42Ama Control

    5.2.2.3 Cooling coil, COOLING mode "Off" position: the valve is closed "COMFORT" position: the opening of the valve will depend on the difference between the regulated temperature value (room) and the setpoint. Regulation will only start after a 30-second time delay on the fan operation feedback contact. An integral action must be entered into the parameters.
  • Page 22: The Fault Relays

    5.4 The fault relays One relay per fault summary level is provided - "Maintenance" fault summary - "Danger" fault summary "Maintenance" faults are faults which only send information to notify the operator. They can be validated by pressing the for 3 seconds if they have disappeared. The "Danger"...
  • Page 24 Order No.: EN7515390-00, 03.2017. Supersedes order No.: 10153-00, 08 2016 Manufactured for CARRIER, France. The manufacturer reserves the right to change product specifications without prior warning. Printed in the European Union.