5.3 Pipe length and the elevation

The pipe length and refrigerant amount:
Model
YM9FXC030BAA--FX + YM9FYC030BAA-A-X
YM9FXH030BAA--FX + YM9FYH030BAA-A-X
YM9FXC036BAA--FX+ YM9FYC036BAA-A-X
YM9FXH036BAA--FX+YM9FYH036BAA-A-X
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
Standard
Pipe size
length
Gas
Liquid
3/8''
5/8''
(Ф16.0)
(Ф9.52)
3/8''
5/8''
(Ф16.0)
(Ф9.52)
3/8''
3/4''
(Ф19.0)
(Ф9.52)
3/8''
3/4''
(Ф19.0)
(Ф9.52)
Max.
Max.
Elevation
Length
(m)
B (m)
A (m)
5
10
5
10
5
15
5
15
Additional
refrigerant
(g/m)
25
40
25
40
30
40
30
40