AKO -575 N Series Quick Manual

AKO -575 N Series Quick Manual

Gas transmitter with nbiot communication

Advertisement

Quick Links

GB
5750H072 Ed.02
Gas transmitter with
NBIoT communication
V2
Quick guide
AKO-575xxxNx / AKO-575xxxV
akonet.cloud
AKO ELECTROMECÁNICA , S.A.L.
Avda. Roquetes, 30-38
08812 • Sant Pere de Ribes.
Barcelona • Spain.
Tel.: +34 902 333 145
Fax: +34 938 934 054
www.ako.com
We reserve the right to supply materials that might vary slightly to those described in
our Technical Sheets. Updated information is available on our website.
Warning
-Transmitters / detectors should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical data.
-The transmitters / detectors are not suitable for areas classified as potentially explosive.
-Transmitters/detectors supervise a point and not an area. If the gas leak does not reach the sensor, or the level of concentration in that point does not reach the foreseen values according to the type of gas no alarm will be activated.
If perimeter supervision is required, several sensors should be installed around that area.
-Avoid installing the device on metal walls or near devices that may produce radio emissions.
-This device must be installed in a location where a minimum distance of 20 cm to the human body can be guaranteed, in order to ensure compliance with standards on human exposure to electromagnetic fields.
-The AKO-575400NE device must NEVER be operating without having installed the external antenna. This device can be fitted with any antenna provided it has a gain of less than 9.2 dBi and there is a minimum distance of more than 20 cm between it and any person or animal. Any
type of antenna used with this device must comply with the limits established for the radio interface in Member States and the following documents: Comission Decision 2010/267/EU of 6 May 2010,ECC Decision (09)03 of 30 october 2009 and CEPT Report 30 of 30 October 2009.
Working conditions:
-Avoid handling refrigerant gases near the sensor. If this is unavoidable, use Set Hold or Maintenance mode. Do not paint the sensor or place it near solvents or paints. Exposure to acetone vapours may generate false alarms.
-The sensor should be installed away from: -Smoke outlets located in confined spaces or from engines, generators or motorised machinery (fork-lift trucks, etc.).
-Particularly damp areas or areas with strong ventilation.
-The detector should usually be installed in an area where gas may concentrate, near places where gas leaks could start
-The gases currently used in industrial refrigeration, for which this transmitter has been designed, are heavier than air. They are therefore always concentrated in the lowest part of the refrigerated room or space. Please take this into consideration when choosing the
installation site. It is advisable to leave a distance of around 50 cm free.
A
DIG. IN
A
B
Mute
Set Hold
remoto
remoto
1N{=1: Connection to alarm station
RS485 Pre-Alarm Alarm
NC
C
NO
NC
C
NO
B
Gas
Gas
Pre-Alarm
Alarm
Descripción
Display
Gas sensor
Fixed: Gas pre-alarm activated.
Flashing: Gas alarm activated.
Fixed: Set Hold mode activated
Flashing: Maintenance mode activated
The display shows the type of gas detected.
Keyboard
If the gas Pre-Alarm or Alarm sounds, pressing once will mute the alarm tone (See parameter b03).
In the programming menu, it exits the parameter without saving changes, returns to previous
level or exits programming.
Pressing for 3 seconds activates or deactivates Set Hold mode.
Pressing for 6 seconds activates or deactivates maintenance mode.
In the programming menu it allows scrolling around the different levels, or during the setting of
a parameter, changing its value.
+
Forces data transfer to the cloud via NBIoT connectivity.
Always disconnect the power supply to do the wiring.
The wiring between the transmitter and the station must
conduit together with power, control or power supply cables.
Cables for wiring the relay contact should have an adequate section depending on the unit
to be connected.
Certain international standards maintain that the power supply of the alarm should originate
from a different circuit to that used by the refrigeration and ventilation system. Please ensure
that you comply with current local regulations.
If connecting to a MODBUS network the double connection strips included must be used
(see box)
Alarm station
1N{=2: Independent operation
RS485 Pre-Alarm Alarm
Input x
NC
C
NO
NC
C
NO
GAS
B
Gas
Gas
Pre-Alarm
Alarm
Constant: NBIoT module in operation
Flashing: Malfunction in NBIoT module
Constant: Connected to the NBIoT network (Narrow band)
Switched off: NOT connected to the NBIoT network or expired license.
The display shows the current gas concentration in ppm (parts per million).
The value displayed should be multiplied by 10.
Pressing once (< 1 second) will show the type of gas detected, the date and time in
sequential order.
Pressing for 3 seconds displays the Pre-Alarm and Alarm levels that have been configured.
In the programming menu it allows scrolling around the different levels, or during the
setting of a parameter, changing its value.
Pressing for 3 seconds accesses the configuration of alarm and pre-alarm levels.
Pressing it for 6 seconds accesses the advanced programming menu.
In the programming menu, it accesses the level shown on the display or, during the
setting of a parameter, accepts the new value.
Operation
NEVER
be installed in a
Without alarms
The display shows the current gas concentration in ppm.
Parameter b02 allows you to fix a value below which the display will
always show zero.
The transmitter regularly sends to the cloud (akonet.cloud) the gas
concentration data and other operation information at specific
intervals based on the akonet.cloud parameter "continual log
interval".
Any change in the configuration of the transmitter or its operation
(mode changes, errors, etc.) are sent to the cloud instantly.
Detail of MODBUS connection
(Wire ferrules included)
Alarms
The transmitter emits an acoustic alarm, the alarm indicator
flashes and activates the relays when certain gas concentration
levels are exceeded. If the transmitter is connected to a station,
the station will emit the acoustic alarm. The relays will be
activated in both devices.
There are two alarm levels depending on the concentration of gas
detected: Pre-Alarm and Alarm. These have a factory setting of 500
12 - 30 Vdc
and 1000 PPM respectively. These values comply with domestic and
international regulations. However, please ensure that these values
comply with current local regulations. In order to modify these
values, parameter AL1 should be configured to 1.
Activations and deactivations of pre-alarms and alarms are sent
to the cloud instantly.
Gas alarm on mute
Simplified declaration of
Unit in programming mode.
conformity
AKO Electromecánica S.A.L. hereby declares that the radioelectric
device types AKO-575xxxx (Gas transmitter with NBIoT
communication) conform to the provisions set forth by Directive
2014/53/EU.
The full text of the EU conformity declaration is available at the
following internet address:
http://help.ako.com/manuales/declaracion-ue-de-conformidad

Advertisement

loading
Need help?

Need help?

Do you have a question about the AKO-575 N Series and is the answer not in the manual?

Questions and answers

Summary of Contents for AKO AKO-575 N Series

  • Page 1 -The AKO-575400NE device must NEVER be operating without having installed the external antenna. This device can be fitted with any antenna provided it has a gain of less than 9.2 dBi and there is a minimum distance of more than 20 cm between it and any person or animal.
  • Page 2 2: Independent operation gc1 Type of gas to be measured (Reading only) It is advisable to reset to zero on start-up. For further information, refer to the user manual available on www.ako.com PU Programme version Gas to be measured with the Universal sensor (Only if Gc1=brd1) ALL;...

This manual is also suitable for:

Ako-575 v series