PRODUCT INTRODUCTION
This product is an indoor combustion gas detector with high
stability , hereinafter called detector, used for combustion gas
leak detection. It uses highly stable semiconductor gas sensor
with features of
stable performance and low drift of
sensitivity. When it senses combustion gas leak that reaches
the set alarm level, it will give out alarm sound with red LED
flashing. The detector is applied in indoor places where
combustion gas leaks possibly happen.
PRODUCT PROFILE
Wire harness connection instruction for DC type detectors :
Red: DC power anode
Black: DC power cathode
White: COM (relay)
Yellow: N.C. (relay)
Orange: N.O.(relay)
Wire harness connection instruction for detectors for AC type detectors
(no wire harness attached for stand alone type detectors):
Red: anode of solenoid valve
Black: cathode of solenoid valve
White: COM (relay)
Yellow: N.C.(relay)
Orange: N.O.(relay)
FEATURES
●
Detects Natural Gas/LPG
●
Wall
Mounted
● Highly Stable Semiconductor Gas Sensor
● Adopts MCU Processing
●
Manual Test/Auto Reset Functions
● Auto Check Malfunction
●
High Capacity Relay (3A/250V)
● SMT Manufacture Technology, High Stability
● Comply to GB15322.2-2003
manual pole
control line
(connect with detector)
Solenoid Valve (optional accessory)
Combustion Gas Detector Manual
TECHNICAL SPECIFICATION
Type
DC Type
Voltage
DC9- 24V
Working Envir.
-10ºC ~ +55ºC, 10%~95%RH (no congelation)
Storage Temp.
Alarm Level
Error
1
Sensor
Highly Stable Semiconductor Gas Sensor
Reset
Auto Reset (Leaked Gas Level< Alarm Level)
Sound Level
Relay Output
Output
Relay
1C(SPDT), Contact loads: 3 A 250 VAC/30 VDC
Solenoid
Valve Signal
Indicator
Dimension
INSTALLATION
1. First identify your gas heavier or lighter than air.
Heavier gases: LPG etc. Lighter gases: natural gas, marsh
gas, artificial coal gas etc.
Choose a suitable installing position according to gas
2.
specific gravity.
Detecting heavier gases,
height 0.3-1.0m from floor , semi-diameter to gas source
<1.5m; Detecting lighter gases, installation height 0.3-
1.0m from ceiling, semi-diameter to gas source < 1.5m
(refer to the following image).
DETECTOR
Max Range:
Φ3m
GAS STOVE
3. Fix the attached base into a wall firmly with screws
and hang the detector.
4.
Do not make it close to gas stoves when installing at home
in case it is roasted by flame. Neither places with heavy oil
or smoke that may cause false alarms or block the gas
convection holes and influence the detector sensitivity.
Also it is can not be installed near to exhaust fans,
windows, doors, and places with great vapor in bathrooms.
5.
Connect the wires correctly according to the wire harness
1
M071EVer1.2
AC Type
AC220V
-25ºC ~ +55ºC
6%LEL
±3
%
LEL
75dB/1m
Relay or Solenoid Valve
Signal Output
DC12V 300ms
Power: Green LED ON
Alarm: Red LED Flashing
Fault: Yellow LED ON
110*70*40mm
installation
C E I L I N G
F L O O R