Models 51, 51-S and 53 Boiler
Water Feeders
Models 51-2, 51-S-2 and 53-2
Feeder Cut-Off Combinations
OPERATION
Maximum Water Supply Pressure
Models 51/51-2 and 53/53-2: 150 psi (10.5 kg/cm
Models 51-S/51-S-2: 100 psi (7 kg/cm
Maximum Boiler Pressure
Models 51/51-2 and 51-S/51-S-2: 35 psi (2.5 kg/cm
Models 53/53-2: 75 psi (5.3 kg/cm
Electrical Ratings
Motor Switch Rating (Amperes)
Voltage
Full Load
120 VAC
10.2
240 VAC
5.1
• Before using this product read and understand instructions.
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application, instal-
lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.
• To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be
0 psi (0 bar) before servicing.
• To prevent electrical shock, turn off the electrical power before making electrical connections.
• This low water cut-off must be installed in series with all other limit and operating controls
installed on the boiler. After installation, check for proper operation of all of the limit and
operating controls, before leaving the site.
• We recommend that secondary (redundant) Low Water Cut-Off controls be installed on all
steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi of
steam pressure. At least two controls should be connected in series with the burner control
circuit to provide safety redundancy protection should the boiler experience a low water
condition. Moreover, at each annual outage, the low water cut-offs should be dismantled,
inspected, cleaned, and checked for proper calibration and performance.
• Boiler manufacturer schematics should always be followed. In the event that the boiler
manufacturer's schematic does not exist, or is not available from the boiler manufacturer,
refer to the schematics provided in this document.
• To prevent a fire, do not use this low water cut-off to switch currents over 10.2A, 1/2 Hp at
120 VAC or 5.1A, 1/2 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.
Failure to follow this warning could cause property damage, personal injury or death.
2
)
2
)
Locked Rotor
Pilot Duty
61.2
125 VA at
120 or 240 VAC
30.6
McDonnell & Miller
®
2
)
Series 51
2
)
Series 51-2
WARNING
!
Instructions
MM-315(C)
Series 51-S/53
Series 51-S-2/53-2