INDOOR UNIT DISPLAY SECTION
Operation Indicator lamp
The operation indicator at the right side of the indoor unit indicates the operation state.
•The following indication applies regardless of shape of the indication.
Indication
The unit is operating to
reach the set temperature
The room temperature is
approaching the set tem-
perature
Standby mode
(Only during multi system
operation)
9-1. COOL ( ) OPERATION
(1) Press STOP/OPERATE (MSZ-SF·VA-
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TEMP
1. Coil frost prevention
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the coil
from frosting.
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.
The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor
heat exchanger rises.
2. Low outside temperature operation
When the outside temperature is lower, low outside temperature operation starts, and the outdoor fan slows or stops.
9-2. DRY ( ) OPERATION
(1) Press STOP/OPERATE (MSZ-SF·VA-
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select DRY mode with OPERATION SELECT button.
(3) The set temperature is determined from the initial room temperature.
1. Coil frost prevention
Coil frost prevention works the same way as that in COOL mode. (9-1.1.)
2. Low outside temperature operation
Low outside temperature operation works the same way as that in COOL mode. (9-1.2.)
9-3. FAN ( ) OPERATION (MSZ-SF·VA-
(1) OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select FAN mode with OPERATION SELECT button.
(3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates.
Outdoor unit does not operate.
9-4. HEAT ( ) OPERATION
(1) Press STOP/OPERATE (MSZ-SF·VA-
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TEMP
1. Cold air prevention control
When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room tem-
perature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.
2. High pressure protection
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the con-
densing pressure from increasing excessively.
When the temperature of indoor heat exchanger becomes too high, the high pressure protection works.
The indoor fan operates following the cold air prevention control. This mode continues until the temperature of indoor
heat exchanger falls.
3. Defrosting
Defrosting starts when the temperature of outdoor heat exchanger becomes too low.
The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses, and the compressor re-starts.
This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.
OBH555D
Operation state
About 2°C or more away
from set temperature
About 1 to 2°C from set
temperature
,
)/OPERATE/STOP (Other models) button.
E4
ER4
or
button) to select the desired temperature. The setting range is 16 - 31°C.
,
)/OPERATE/STOP (Other models) button.
E4
ER4
,
)
E4
ER4
,
)/OPERATE/STOP (Other models) button.
E4
ER4
or
button) to select the desired temperature. The setting range is 16 - 31°C.
Room temperature
-
12
Lighted
Blinking
Not lighted