This chart is sourced from NFPA-54 2015 with the BTU ratings for the material, length, and diameter of gas pipe.
INTENDED USE: Pipe Sizing Between Natural Gas Meter, or Propane Single - or Second-Stage (Low-Pressure) Regulator and
Appliance.
INTENDED USE: Pipe Sizing Between Natural Gas Meter, or Propane Single- or Second-Stage (Low-
Pressure) Regulator and Appliance.
Schedule 40 Metallic Pipe
Gas:
Inlet Pressure:
Pressure Drop:
Specific Gravity:
Nominal ID (inches):
Length (ft)
Corrugated Stainless Steel Tubing (CSST) w/ pressure drop of 0.5 inches w.c.
Gas:
Inlet Pressure:
Pressure Drop:
Specific Gravity:
Tube Size (inches):
Flow Designation (EHD):
Length (ft)
7 - GAS SUPPLY PIPING
3/4
Capacity in Thousands of Btu per
360
10
247
20
199
30
170
40
151
50
137
60
117
80
100
104
23
Capacity in Thousands of Btu per
10
161
20
116
30
96
40
83
50
75
60
68
80
60
100
54
Natural
Less than 2 psi
0.5 in. w.c.
0.60
1
Hour
678
466
347
320
284
257
220
195
Natural
Less than 2 psi
0.5 in. w.c.
0.60
3/4
1
25
30
31
Hour
192
330
383
137
231
269
112
188
218
97
162
188
87
144
168
80
131
153
69
113
132
62
101
118
39
Undiluted Propane
11.0 in. w.c.
0.5 in. w.c.
1.50
3/4
Capacity in Thousands of Btu per
Hour
608
1,150
418
787
336
632
287
541
255
480
231
434
212
400
197
372
Undiluted Propane
11.0 in. w.c.
0.5 in. w.c.
1.50
3/4
23
25
30
Capacity in Thousands of Btu per
Hour
254
303
521
183
216
365
151
177
297
131
153
256
118
137
227
107
126
207
94
109
178
85
98
159
240013354 REV A [07/01/2021]
1
1
31
605
425
344
297
265
241
208
186

Advertisement