Advantage IV (A4) GTA116e-P STARTUP GUIDE
A1
A2
L2
A3
L1
C
TYPE A
TYPE B
GTA116e-P Parameters - Factory Defaults and Optional Settings/Ranges
Description
Parameter Default
System of Units
SYS
I-P (US customary)
Airflow Calculation Method
AIRFLOW
ACT (actual)
Altitude (for actual flow correction) ALT
0
Low Limit Airflow Cutoff
LLIMIT
0 FPM
Area
AREA
{Order Area}
Humidity Sensor Config. (/H opt.) H CONFIG
RH (relative humidity) ENTH (enthalpy), DPT (dew point)
Auto Pb Correct Psych. Values
Pb CORR
ON (onboard sensor) OFF
AO1, AO2 and AO3 Type
AOUT
4-20mA
AO1 Assignment
AO1 ASGN
AF (Airflow)
AO1 Unit of Measure
AO1 UM
FPM [m/s]
AO1 Minimum Scale Reading
AO1 MS
0
AO1 Full Scale Reading
AO1 FS
5000 [25.0]
AO2 Assignment
AO2 ASGN
TEMP (Temperature) ALRM (Alarm) or TRBL (System Trouble)
AO2 Unit of Measure
AO2 UM
F [C]
AO2 Minimum Scale Reading
AO2 MS
-20 [-30]
AO2 Full Scale Reading
AO2 FS
160 [70]
H CONFIG=RH (default)
AO3 Assignment
AO3 ASGN
RH
AO3 Unit of Measure
AO3 UM
%RH
AO3 Minimum Scale Reading
AO3 MS
0
AO3 Full Scale Reading
AO3 FS
100
H CONFIG=ENTH
AO3 Assignment
AO3 ASGN
ENTH
AO3 Unit of Measure
AO3 UM
Btu/lb [kJ/kg]
AO3 Minimum Scale Reading
AO3 MS
0
AO3 Full Scale Reading
AO3 FS
200 [400]
H CONFIG=DPT
AO3 Assignment
AO3 ASGN
DPT
AO3 Unit of Measure
AO3 UM
F DPT [C DPT]
AO3 Minimum Scale Reading
AO3 MS
0
AO3 Full Scale Reading
AO3 FS
100 [50]
Refer to the O&M Manual for more information and/or additional parameter defaults, settings and ranges.
STARTUP INSTRUCTIONS:
1. Verify that the sensor probes are located where they meet EBTRON published installation guides.
2. Verify that the probes are properly spaced with the airflow arrows pointing in the direction of airflow.
Improperly installed probes will compromise the installed accuracy of the device and degrade system
performance.
3. Verify that the transmitter is installed and wired in accordance with the GTA116e-P Wiring Guide
provided with the transmitter and power is provided to the transmitter.
4. Make sure the ductwork is clean and free of debris prior to fan startup.
5. Move the power switch to the "ON" position. Power-up faults, if detected, are displayed on the LCD.
If any power up faults are detected, resolve all conflicts or contact EBTRON customer service at
1-800-232-8766 before proceeding..
If extension cables have been added, the extension cable length must be entered into the transmitter.
Refer to the Operations and Maintenance Manual for more information.
Optional Settings/Ranges
Units
SI (metric)
STD (standard mass flow)
AUTO, 0 to 20000 [0 to 6000]
ft [m]
0 to 500 FPM [0.0 to 2.5 m/s]
0.00 to 9999.99 [0.000 to 999.999]
sq ft [sq m]
0-10V, 0-5 V
None
CFM [L/s]
None
FPM [m/s]
100 to 15000 [0.5 to 75.0]
FPM [m/s]
None
°F [°C]
-50 to 160 [-50 to 70]
°F [°C]
-50 to 160 [-50 to 70]
°F [°C]
None
None
0 to 100
% RH
0 to 100
% RH
None
None
-20 to 400 [-40 to 800]
Btu/lb [kJ/kg]
-20 to 400 [-40 to 800]
Btu/lb [kJ/kg]
None
None
-50 to 160 [-50 to 70]
°F [°C]
-50 to 160 [-50 to 70]
°F [°C]
Startup_GTA116e-P_r1a Page 1 of 2

Advertisement

loading

Summary of Contents for Ebtron GTA116e-P

  • Page 1 Improperly installed probes will compromise the installed accuracy of the device and degrade system performance. 3. Verify that the transmitter is installed and wired in accordance with the GTA116e-P Wiring Guide TYPE B provided with the transmitter and power is provided to the transmitter.
  • Page 2 Multiply the default full scale velocity (FPM )by the correct area of the measurement location to determine the full-scale or span (CFM ) for the B.A.S. to avoid field configuration. EBTRON airflow measurement device accuracy is percent-of-reading. Changing the full scale reading does not affect measurement accuracy.