Dimensional Drawing
PROTOCOL USAGE
Output Bits
2
No function
1
Initiate self test
0
Activate Zone reset
Interrupt
No
Analogue Value
64
Alarm
16
Quiescent
4
Zone fault
Input Bits
2
Reflects status of o/p bit 2
1
Self test confirmed
0
Zone reset active
Flag Setting
XP95 Flag
Yes
Alarm Flag
Yes
Table 1
www.acornfiresecurity.com
www.acornfiresecurity.com
SCHEMATIC DIAGRAM AND WIRING CONNECTIONS
L1
L2
+
13 1415 16
12
11
10
9
LOCALLY POWERED
+
L1
L2
ZONE MONITOR
LOOP
© Apollo Fire Detectors Limited 2008/9 TP/LC/TP
Terminals 2 (+ve) and 3 (-ve) may be used to connect a capacitor
if an active end of line device is connected.
Fig.1 Loop Connections
TECHNICAL DATA
Loop voltage
Quiescent current
Local Power
Supply voltage
Local quiescent current
(3k
End of line fitted)
Zone quiescent current
detector load
Zone voltage
Zone alarm current
Zone alarm resistance - See Table 2
IP Rating
Operating temperature
Humidity
Isolator Rating
Complies with EMC Directive 2004/108/EC
Complies with EN54-17:2005 and EN54-18:2005
EMC DIRECTIVE 2004/108/EC
The Locally Powered Zone Monitor, part no. 55000–
864, complies with the essential requirements of the
EMC Directive 2004/108/EC, provided that it is used
as described in this PIN sheet.
A copy of the Declaration of Conformity is available
from Apollo on request.
Conformity of the Locally Powered Zone Monitor
with the EMC Directive does not confer compliance
with the directive on any apparatus or systems
connected to it.
NOTE: Failure of the local supply will prevent the
device from communicating with the control panel,
resulting in a device missing fault.
LOCAL POWER
+
CONVENTIONAL ZONE
+
1
2
END OF LINE
3
DEVICE
4
-
17–28V DC
2.5mA
21–28V DC
13mA
4mA max
19 ± 1.5V DC
35mA
100
– 1k
54
–20°C to +70°C
0–95% RH
5