ASCO POWER TECHNOLOGIES 5010 Operator's Manual

Remote display unit

Advertisement

Quick Links

Operator's Manual
1
TABLE OF CONTENTS
Section
1 .............. Introduction ............................................................. 3
2 .............. Getting Started ........................................................ 4
3 .............. Hardware Description ............................................. 6
4 .............. Mounting ................................................................. 9
5 .............. Wiring .................................................................... 10
6 .............. Navigating through the screens ............................ 12
7 .............. Basic Configuration ............................................... 14
8 .............. Using the ASCO 5010 Remote Display Unit ......... 18
9 .............. Monitoring ............................................................. 32
10 ............. Troubleshooting .................................................... 42
11 ............. Technical Definitions ............................................. 45
12 ............. ASCO 5400 Series Website
Reference ............................................................. 48
Figure
Figure 1.
ASCO 5400 Series Basic Module Unit .................... 2
Figure 2.
ASCO 5010 Functional Display Unit ........................ 6
Figure 3
External Display Panel (Rear View) ......................... 7
Figure 4
ASCO 5010 RDU -Technical Drawing ..................... 7
Figure 5
Screw Holes for Affixing RDU to a Panel ................. 9
Figure 6
Mounting the Remote Display Device
to a Panel ................................................................. 9
Figure 7
Power Over Ethernet PoE Connection .................. 11
Figure 8
Terminals for RS485/422 on the Rear Side
of the ASCO 5010 RDU ......................................... 11
Figure 9
The ASCO 5010 RDU Main Menu ......................... 12
Figure 10
The ASCO Welcome Screen followed by the
Connection Configuration Page ............................. 14
Figure 11
The ASCO Search Utility for Finding ASCO Elements
on the LAN ............................................................. 24
Figure 12
The Two Page Configuration Menu ....................... 25
Figure 13
The Information Page ............................................ 26
Figure 14
Read-only "About" Information .............................. 26
Figure 15
Current transformer conductor inserted correctly
through the ASCO 5400 Series ............................. 28
Figure 16
PT/CT Settings- inputting the Primary
PT Value ................................................................ 28
Figure 17
The Main Menu- Default on Power Up .................. 32
Figure 18
Large Digits Display- A Typical Page Layout ......... 34
Figure 19
The Factors Summary Page: K-factor and
Crest Factor ........................................................... 36
Figure 20
Volt/Amp Summary ................................................ 36
Figure 21
The Power Summary Page .................................... 37
Figure 22
The THD Summary Page ...................................... 37
Figure 23
Waveforms Main Menu .......................................... 38
Figure 24
Navigating the Oscilloscope .................................. 39
Figure 25
A Harmonic Spectrum Screen ............................... 40
Figure 26
The Phasor Display ............................................... 41
Figure 27
The Flickering Summary ........................................ 42
Figure 28
A Detailed Flicker Summary .................................. 43
POWER
TECHNOLOGIES
Page
Page
Florham Park, New Jersey 07932-1591
For sales or service, call: 1 800-800-2726 (ASCO)
ASCO POWER TECHNOLOGIES CANADA, PO Box 1238, 17 Airport Road
Brantford, Ontario, Canada N3T 5T3
5010 Remote
ASCO 5010 Remote Display Unit
Display Unit
Installation Considerations
Installation and maintenance of the ASCO 5010 Remote
Display Unit should only be performed by qualified,
competent personnel that have appropriate training and
experience with high voltage and current devices. The meter
must be installed in accordance with all Local and National
Electrical Codes and regulations.
This equipment has no user serviceable parts.
Important Symbols Used in This Manual
DANGER
DANGER is used in this manual to warn of a hazardous
situation which, if not avoided, will result in death or
serious injury.
WARNING
WARNING is used in this manual to warn of a hazardous
situation which, if not avoided, could result in death or
serious injury.
CAUTION
CAUTION is used in this manual to warn of a hazardous
situation which, if not avoided, could result in minor or
moderate injury.
NOTICE
NOTICE is used in this manual to address practices not related
to physical injury.
www.ascopower.com
.
Series ASCO 5010 Series
IO-70051 Rev. 0 9/12
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the 5010 and is the answer not in the manual?

Questions and answers

Summary of Contents for ASCO POWER TECHNOLOGIES 5010

  • Page 1 5 ....Wiring ..............10 6 ....Navigating through the screens ......12 7 ....Basic Configuration ..........14 8 ....Using the ASCO 5010 Remote Display Unit ..18 9 ....Monitoring ............. 32 10 ..... Troubleshooting ............ 42 11 .....
  • Page 2 ASCO 5010 Remote Display Unit Acronyms Ampere Current Transformer DHCP Dynamic Host Configuration Protocol Internet Protocol (formerly OLE for Process Control), a series of standards specifications Power Factor Power over Ethernet Potential Transformer Remote Display Unit SCADA Supervisory Control and Data Acquisition...
  • Page 3 The ASCO 5010 RDU enables configuring all aspects of the ASCO 5400 Series Power Quality Meter and displays all monitored real time values. Figure 1 describes the role of the ASCO 5010 RDU in managing power quality data in a power distribution system.
  • Page 4 LCD display can offer. The ASCO 5010 RDU can be used as a hand held monitoring and configuring tool connecting to each ASCO 5400 Series Power Quality Meter in turn using a CAT 5e/6 network cable with a RJ45 plug, or optionally plugging into a network connection and alternately inputting the IP addresses of the different instruments.
  • Page 5  NOTICE Before working with the ASCO 5010 Remote Display Unit, please read this User Manual carefully. The manufacturer will not be responsible for damage or injury due to misuse. The following general safety guidelines apply to ASCO 5010 RDU installation and operation. When performing any operation with the ASCO 5010, always observe these safety precautions.
  • Page 6 ASCO 5010 Remote Display Unit Overview The ASCO 5010 Remote Display Unit shown in Figure 2 can be divided into three conceptual sections. The upper section contains the Status LEDs, the middle section contains the visual interface; a header and the monitor screen and the lower section contains the input interface;...
  • Page 7 RJ45 – used for both communication & power sourcing the unit (PoE – power over the Ethernet cable coming from ASCO 5400 Series Power Quality Meter). By factory default, the ASCO 5010 RDU is ready for connecting to any ASCO 5400 Series unit at the LCD port. A simple CAT5e/6 cable connecting directly between the ASCO 5010 RDU and ASCO 5450 and 5490 LAN2/LCD port will automatically power up, connect and open the main menu screen relevant for that specific ASCO 5400 Series PQM currently connected.
  • Page 8 ASCO 5010 Remote Display Unit ASCO Technical and Environmental Specifications 3.2.1 Physical Specifications Figure 4: ASCO 5010 RDU - Technical Drawing...
  • Page 9 ASCO 5010 Remote Display Unit 3.2.1.1 ASCO 5010 Remote Display Specifications Dimensions (H×W×D) 197×200×46 mm Panel cutout: 135×135 mm 48 VDC Power supply LAN1 PoE in LED backlight 160×128 pixels graphic screen 3.2.2 Environmental Specifications Intended use Indoor- mounted in a low voltage electrical distribution panel...
  • Page 10 Two screws are supplied for fixing the display unit to the panel from behind. A typical location for mounting the ASCO 5010 RDU is on the front panel of an electrical distribution panel. Figure 5 and Figure 6 aid in describing the method of attaching the RDU to a panel.
  • Page 11 Section 5. Wiring Connecting the Power Supply and LAN The ASCO 5010 Remote Display Unit requires 48V DC to operate. The unit can receive this power from one of two inputs: 1. 48V DC power input terminal 2. The LAN jack using PoE (Power over Ethernet) from the ASCO 5400 Series Power Quality Meter labeled LAN2/LCD.
  • Page 12 The RS485/422 serial communications hardware protocol is an industrial standard using 2 or 4 wires for communication. The wires are to be connected to the terminals marked RS485/422 on the ASCO 5010 RDU as shown in Figure 8 and to the marked terminals on the CPU module of the ASCO 5400 Series Power Quality Meter.
  • Page 13 Section 6. Navigating Through the Screens All ASCO 5010 Remote Display Unit functions are accessible through the 5 function keys located at the bottom of the panel. These function keys are context sensitive and will change functions depending on the screen being viewed. The function performed by the key at any time will be displayed on the Function Key Tag immediately above the function key.
  • Page 14 ASCO 5010 Remote Display Unit Favorites List The Favorites list contains monitored parameters often accessed by the operator. The Favorite parameters most interesting an operator are easily toggled through the F5 key from any measurement screen displaying electrical parameters, as opposed to going back to the previous menu and entering the next page of parameters.
  • Page 15 (configurable- see below "Auto connect page"), the page changes to the ASCO 5400 Series Power Quality Meter’s main entry menu page, from where the ASCO 5400 Series PQM is to be configured (Figure 9). To return to the ASCO 5010 RDU configuration page, simply push the Network Key or use the right arrow ( ) and left arrow ( ) to navigate to and select the Log option, that will return to the 'Connection Configuration' page.
  • Page 16  DHCP- This value may be toggled ON or OFF. If this parameter is toggled on, then the IP address, Subnet mask and Gateway cannot be configured manually. The ASCO 5010 RDU is factory set with the DHCP set to off, and the network parameters set as defined in the following sections.
  • Page 17 Changing the ASCO 5010 RDU IP Address Changing the IP address of the ASCO 5010 RDU is necessary to connect to a network in order to enable connection to one or more ASCO 5400 Series Power Quality Meter via the network.
  • Page 18 ASCO 5010 Remote Display Unit Navigate between the 4 address elements using the right arrow. Change the address elements using the up and down arrows. Lock in the address by pushing the OK button.  Select 'Subnet mask' and change as necessary using the right, up and down arrows ...
  • Page 19 Section 8. Using the ASCO 5010 Remote Display Unit After the ASCO 5010 Remote Display Unit has been configured, it may be used to configure and display the measured parameters of the ASCO 5400 Series Power Quality Meter. One RDU can be used to configure and monitor a number of ASCO 5400 Series PQM by changing the IP address of the instrument to be monitored.
  • Page 20 Connecting a Single ASCO 5010 RDU to a Single ASCO 5400 Series Power Quality Meter If the ASCO 5010 RDU is to be used as a permanent display for a single ASCO 5400 Series Power Quality Meter, the connection is made simply from the ASCO 5010 RDU port to the ASCO 5400 Series LAN2/LCD port using a regular LAN Cat5e/6 cable with RJ45 plugs on both ends.
  • Page 21 ASCO 5010 Remote Display Unit  Due to the plug and play feature, the Main menu appears allowing configuration of all ASCO 5400 Series Power Quality Meter parameters including the network parameters:  Navigate to System configuration using right ( ) and left ( ) and...
  • Page 22 ASCO 5010 Remote Display Unit  Navigate to DHCP status toggle using the (up) and (down) and then (select-F3): The following screen appears:  Press F3 (OK) to disable DHCP. This is in order to allow the configuring of prepared and previously mapped IP addresses manually in the following steps.
  • Page 23 LAN. The Automatic Search Utility is described in section 8.3 on page 24. Once a list of ASCO 5400 Series Power Quality Meters is compiled, it is possible to plug the ASCO 5010 RDU into a network port and to configure and monitor these instruments one by one as follows: ...
  • Page 24 Automatic Search Utility One of the applications of the ASCO 5010 Remote Display Unit is to plug into a network outlet in a LAN and to communicate with any ASCO 5400 Series Power Quality Meter on the network. It could come to pass that the IP addresses for one or more of the ASCO 5400 Series PQM may become unknown.
  • Page 25 ASCO 5010 Remote Display Unit The utility is located on the CD packaged with the ASCO 5400 Series Power Quality Meter or contact CustomerCare@asco.com. A simple double click on the file name launches the utility. Figure 11 shows the user interface. Functionality includes: Search ...
  • Page 26 ASCO 5010 Remote Display Unit 8.4.1 The Setup Menu Screens This section will describe the setup menus. From the main menu: Press on the to enter the Configuration sub menu: This screen offers two menus, the is the configuration menu and the (i) is an information menu. Press on the...
  • Page 27 ASCO 5010 Remote Display Unit Figure 13: The Information Page All the pages available for viewing from the Information page are configured in the configuration menu except for one page- General Information. This page displays the version numbers for the elements of the ASCO 5400 Series Power Quality Meter as shown in Figure 14.
  • Page 28 ASCO 5010 Remote Display Unit 8.4.2 The Setup Menu Parameters Explained Site Setup: This page is used to define the site where the instrument is installed. Information available for input  includes: √ Site name √ Operator name √ Site description Power Configuration: This page is used to input the type of electrical distribution system.
  • Page 29 ASCO 5010 Remote Display Unit Figure 15: Current trasformer conductor inserted correctly through the ASCO 5400 Series Power Quality Meter Nominal values: This page allows the user to input the nominal values necessary for internal calculations and for  comparison purposes in calculating power quality compliance to the EN50160 standard. Nominal values are to be input only after configuring PT/CT ratios.
  • Page 30  Table 1 on page 16. When accessing an energized ASCO 5010 RDU, the network parameters referred to are those of the LAN1 socket of the ASCO 5400 Series Power Quality Meter to which it is connected. For more on accessing and configuring both the ASCO 5010 RDU and the ASCO 5400 Series PQM, go to 7.2 and 8.2 respectively.
  • Page 31 ASCO 5010 Remote Display Unit 8.5.1 Enabling PQZip After all electrical system and communication network parameters have been configured it is necessary to enable the PQZip compression software before the instrument begins recording. Without enabling PQZip, the instrument monitors but does not record.
  • Page 32 ASCO 5010 Remote Display Unit 8.5.2 PQZip Information The PQZip information page is read only and offers pertinent information on the current status of PQZip. The page is reached by choosing "Information" from the PQZip Main Menu shown above in section 8.5.1 and pressing on the button.
  • Page 33 ASCO 5400 Series Power Quality Meter using the ASCO 5010 RDU. The default start up menu when powering up the ASCO 5010 RDU is the Main Menu shown in Figure 17. This menu is comprised of icons pointing to the monitoring and configuration sub menus.
  • Page 34 Meters This menu, when entered, is labeled the Large Digits Menu and lists the displays available for presentation on the ASCO 5010 Remote Display Unit. These displays are the real time RMS values of measured parameters that are required by electricians and engineers on a day to day basis.
  • Page 35 ASCO 5010 Remote Display Unit 9.1.1 Meters- Large Digit Display A typical Large Digits page is arranged to display pertinent data for the selected electrical parameter in an efficient manner. Figure 18 represents an example of the Large Digits display, in this case Line to Line voltages are displayed. This type of display is used for most of the Meter menu and much of the Energy Measurement menu.
  • Page 36 ASCO 5010 Remote Display Unit  The System or average power factor with Lag/Lead (Cap/Ind) √ Line to Line Voltage shows:  Voltage L1/L2 in volts or PU  Voltage L2/L3 in volts or PU  Voltage L3/L1 in volts or PU √...
  • Page 37 ASCO 5010 Remote Display Unit 9.1.2 Meters- The Summary Pages The last 4 meters listed on the Large Digits meter page are summaries. The following figures display the screens in the order of their appearance. Figure 19: The Factors Summary Page: K-factor and Crest Factor...
  • Page 38 ASCO 5010 Remote Display Unit Figure 21: The Power Summary Page Figure 22: The THD Summary Page...
  • Page 39 ASCO 5010 Remote Display Unit Oscilloscope The Oscilloscope page allows the user to see the real time current and voltage wave forms. Upon entering the Waveforms Main Menu, as shown in Figure 23, the user can select to view current, voltage or both current and voltage waveforms together on the same screen.
  • Page 40 ASCO 5010 Remote Display Unit Figure 24: Navigating the Oscilloscope Element These are the values of the voltage and current at the position ruler (#2) The position ruler; allows observation of simultaneous voltage and current. The ruler is moved left and right using the F4 and F5 arrows.
  • Page 41 ASCO 5010 Remote Display Unit L1 current  L2 current  L3 current  The Voltage harmonic spectrums that may be chosen are: L1-L2 voltage  L2-L3 voltage  L3-L1 voltage  L1 voltage  L2 voltage  L3 voltage ...
  • Page 42 10 minutes. Similarly, ASCO offers long time values of 1, 10 and 24 hours, as well as a 7 day long time value in addition to the EN50160 two hour value for P The ASCO 5010 RDU displays the EN50160 values of P and P...
  • Page 43 ASCO 5010 Remote Display Unit Selecting and entering the screens in the menu will produce a Large Digit Display as explained in section 9.1.1 portrayed in Figure 18 on page 35, or a summary as described below. The parameters displayed in Large Digit Display include the following: The ASCO Real Time P ...
  • Page 44 ASCO 5010 Remote Display Unit The Detailed summary is organized by voltage type, as shown below. When the voltage type is selected, the detailed summary is displayed, as shown in Figure 28. Figure 28: A Detailed Flicker Summary...
  • Page 45 ASCO 5010 Remote Display Unit Section 10. Troubleshooting The following table lists the various error messages issued by the ASCO 5010 Remote Display unit. Error Explanation Troubleshooting Invalid parameter→ Invalid password Wrong password, Not the Admin password Re enter admin password. If problem...
  • Page 46 ASCO 5010 Remote Display Unit Section 11. Technical Definitions Subject group, Term Explanation V, I RMS values of voltage (V) and current (I) parameters. The values are calculated from the measured discrete sampling of the waveform at the declared resolution of the instrument.
  • Page 47 ASCO 5010 Remote Display Unit Total Harmonic Distortion. The contribution of all harmonic frequency currents to the delta between the fundamental harmonic- a pure sine wave- and the actual wave form. THD=√(Σn(h )); where n is the order of the harmonic and h is the value of the measured parameter.
  • Page 48 ASCO 5010 Remote Display Unit Harmonics Harmonics refer to the inherent elements of a cyclic wave that exist as multiples of the fundamental harmonic frequency. In electrical power distribution systems, the fundamental frequency is usually (hn) 50 or 60 hertz, delivered in a sine wave. In practice, this sine wave gets distorted. The distorted sine...
  • Page 49 The website on each ASCO 5400 Series Power Quality Meter acts as both a monitoring and configuring interface through the internet connectivity. The following table cross references the actions performed through the ASCO 5010 Remote Display Unit and the website on the ASCO 5400 Series PQM.
  • Page 50 ASCO 5010 Remote Display Unit Measurement: Ii Main→ Large digits menu→ Line currents Monitoring→ Voltage/Current Measurement: Crest factors V,I; Main→ Large digits menu→ Factors summary Monitoring→ Voltage/Current K-factors I Measurement all V,I Main→ Large digits menu→ Volt/Ampere summary Monitoring→ Voltage/Current Measurement: power P,Q,S,PF Main→...
  • Page 51 ASCO 5010 Remote Display Unit Main→ PQZIP information PQZIP enable/disable Main→ PQZIP information→ PQZIP enable/disable Service→ PQZIP status PQZIP information Main→ PQZIP information→ Information Service→ PQZIP status Main→ Flickering measurement Flickering Psst2sec Main→ Flickering measurement→ Real-time Pst Power Quality→ Voltage Flickering→...