Setup and Programming
Configuration Wizard
The MATE3 Configuration Wizard allows quick setup of parameters that apply to all systems. The Configuration Wizard is reached from
the MATE3 Main Menu as shown below.
CAUTION: Equipment Damage
!
These procedures should be done by a qualified installer who is trained on programming inverter power systems. Failure to set
accurate parameters for the system could potentially cause equipment damage. Damage caused by inaccurate programming is
not covered by the limited warranty for the system.
IMPORTANT
Check the firmware revision of all OutBack devices before use. The MATE3 system display must be revision 003.002.xxx or
higher. If the revision is lower, the MATE3 and inverter may not communicate or operate correctly.
Main Menu
Settings
>>
Configuration Wizard
Configuration Wizard
>>
Grid Tied
Device Data Logs
>>
Event Logs
>>
Firmware Update
>>
Wizard System Type
System Type
Grid Tied
System Voltage
48 VDC
Array Wattage
1000
Configuration Wizard
Battery Type
FLA
Capacity
New Configuration
New Configuration
>>
Back
Existing Configuration
>>
Restore Configuration
>>
Wizard Battery Charging
Absorb Voltage
57.6 VDC
Float Voltage
54.4 VDC
Equalize Voltage
60.0 VDC
Re-Float Voltage
44.0 VDC
Configuration Wizard
Back
New Configuration Initialized
Wizard AC Configuration
Back
Continue
AC Output Voltage 230 VAC
AC Phase
Single
AC Input Breaker Size 50 A
Maximum Output Load
30 A
Back
Off Grid
Wizard Generator Configuration
Generator Installed
N
Generator Type
AC
Generator Start
Manual
Wizard System Type
AUX Output Device Port 1
System Type
Off Grid
System Voltage
48 VDC
Back
Array Wattage
1000
Battery Type
FLA
Capacity 500 Ah
Back
Continue
Wizard Grid Use Schedule
Period 1 Enable
Weekday Use 0:00
Drop 0:00
Wizard Battery Charging
Weekend Use 0:00
Drop 0:00
Absorb Voltage
57.6 VDC
Time
1.0
Float Voltage
54.4 VDC
Time
1.0
Back
Equalize Voltage 60.0 VDC
Time
3.0
Re-Float Voltage 44.0 VDC
Back
Continue
Wizard Grid Use Schedule
Period 2 Enable
N
Weekday Use 0:00
Drop 0:00
Wizard AC Configuration
AC Output Voltage 230 VAC
AC Phase
Single
Back
AC Input Breaker Size 50 A
Maximum Output Load
30 A
Back
Continue
Wizard Grid Use Schedule
Period 3 Enable
N
Weekday Use
0:00 Drop 0:00
Wizard Generator Configuration
Generator Installed
Y
Generator Type
AC
Size 5.0 kW
Back
Generator Start
Manual
AUX Output Device Port 1
Back
Continue
Wizard High Battery Transfer
Note: See the MATE3
Mode Disabled
Grid Connect
48.0 VDC
manual for details on
Grid Disconnect
52.0 VDC
Grid Connect SOC 60%
Disconnect SOC 95%
generator control.
Back
The Continue key advances the display
to the Setup Complete screen if the
Wizard Battery Monitor
Shunt A
FLEXnet DC is not installed. If the
Connection
Inverter
FLEXnet DC is installed, the display
Back
advances to the Shunt screens.
Supports the OPTICS RE™ online tool for a cloud-based remote monitoring and control application.
Please refer to the OPTICS RE setup instructions, or visit www.outbackpower.com to download.
900-0158-01-00 REV B.vsd
©2013 OutBack Power Technologies. All Rights Reserved.
Backup
The firmware revision of all
Wizard System Type
System Type
Backup
System Voltage
48 VDC
devices can be confirmed by
Array Wattage
1000
500 Ah
Battery Type
FLA
Capacity 500 Ah
navigating from the MATE3
Continue
Back
Continue
Main Menu as shown below.
Wizard Battery Charging
Upgrades to the firmware
Time
1.0
Absorb Voltage
57.6 VDC
Time
1.0
Time
1.0
Float Voltage
54.4 VDC
Time
1.0
revision can be downloaded
Time
3.0
Equalize Voltage 60.0 VDC
Time
3.0
Re-Float Voltage 44.0 VDC
from the OutBack website
Continue
Back
Continue
www.outbackpower.com.
Wizard AC Configuration
AC Output Voltage 230 VAC
AC Phase
Single
AC Input Breaker Size 50 A
Firmware Revision
Maximum Output Load
30 A
Continue
Back
Continue
Wizard Generator Configuration
Generator Installed
N
Size
5.0 kW
Generator Type
AC
Size 5.0 kW
Generator Start
Manual
AUX Output Device Port 1
Continue
Back
Continue
Wizard Grid Use Schedule
N
Period 1 Enable
N
Weekday Use
0:00 Drop 0:00
Weekend Use
0:00 Drop 0:00
Continue
Back
Continue
System Configuration
Wizard Grid Use Schedule
Period 2 Enable
N
Weekday Use
0:00 Drop 0:00
Continue
Back
Continue
Wizard Grid Use Schedule
Period 3 Enable
N
Weekday Use
0:00 Drop 0:00
1:
2:
Back
Continue
Continue
Wizard High Battery Transfer
Mode Disabled
Delay 60 Min
Grid Connect
48.0 VDC
Delay 60 Min
Delay 60 Min
Grid Disconnect
52.0 VDC
Delay 60 Min
Grid Connect SOC 60%
Disconnect SOC 95%
Continue
Back
Continue
Wizard Battery Monitor
Shunt B
Shunt C
Connection
Charge Controller
Connection
Continue
Back
Continue
Back
Components
System Display
and
Controller
(MATE3)
AC Enclosure
Surge Protector
HUB
Communications
Manager
Major Components
FLEXpower System Products
Inverter/Chargers (x2)
Main Menu
Settings
Settings
>>
Configuration Wizard
>>
Device Data Logs
>>
AC Conduit Box
Event Logs
>>
Firmware Update
>>
(with Bypass Assembly)
DC Enclosure Box
Settings Menu
System
System
>>
Inverter
>>
(with Inverter Circuit Breaker)
Charge Controller
>>
Battery Monitor
>>
MATE3
>>
System Display and Controller
Charge Controller
System Information
>>
Save / Store Information
>>
Firmware Version
>>
Date and Time
>>
Communications Manager
LCD Display
>>
Balancing Transformer
Firmware Versions
MATE3
003.002.005
VFXR3048E 001.006.002
VFXR3048E 001.006.002
FLEXnet DC Monitor (FN-DC)
Surge Protector
Remote Temperature Sensor (RTS)
FN-DC LED Indicators
Wizard Battery Monitor
Color
Battery State-of-Charge
Charge Controller
Green
> 90% (blinks if charge parameters are met)
Continue
≥ 80%
Yellow
≥ 70%
Yellow
≥ 60%
Yellow
≥ 60% off, < 60% solid, < 50% blinks
Red
Inverter/Charger x2
(Inside)
Battery Status and Inverter Status
LED Indicators
Customer-Supplied Components
AC Source
Main Electrical Panel (or overcurrent device for the AC source)
Electrical Distribution Subpanel (Load Panel)
Battery Bank
Photovoltaic (PV) Array (with PV Combiner Box)
LED Indicators on the Inverter
Battery Status LED Indicators
Color
12 V Inverter
24 V Inverter
Green
12.5 Vdc or higher
25.0 Vdc or higher
Yellow
11.5 to 12.4 Vdc
23.0 to 24.8 Vdc
Red
11.4 Vdc or lower
22.8 Vdc or lower
Inverter Status LED Indicators
Green
Inverter on (solid) or standing by (flash)
Yellow
AC source in use (solid) or standing by (flash)
Red
Inverter error or warning (see manual)
Contact Technical Support:
Telephone: +1.360.618.4363
Email:
Support@outbackpower.com
Website:
www.outbackpower.com
Charge Controller
(FLEXmax 80 x2)
DC Enclosure
FLEXnet DC
Battery Monitor
Utility Grid or AC Generator
Surge Protector LEDs
Active
Error
Phase
Yellow
Red
DC
48 V Inverter
Yellow
Red
AC IN
50.0 Vdc or higher
Yellow
Red
AC OUT
46.0 to 49.6 Vdc
45.6 Vdc or lower
IMPORTANT:
Not intended for use with
life support equipment.

Advertisement

loading

Summary of Contents for FLEXPOWER TWO VFXR Series

  • Page 1 AC Output Voltage 230 VAC AC Phase Single AC Phase Single AC Input Breaker Size 50 A AC Input Breaker Size 50 A Firmware Revision FLEXpower System Products Customer-Supplied Components Maximum Output Load 30 A Maximum Output Load 30 A Back Continue...
  • Page 2 Wire Sizes/Torque Mounting Requirements WARNING: Fire/Explosion Hazard Do not place combustible or flammable materials within 3.7 m (12 feet) of the equipment. This unit employs mechanical relays and is not ignition-protected. Fumes or spills from flammable materials could be ignited by sparks. WARNING: Personal Injury Use safe lifting techniques and standard safety equipment when working with this equipment.
  • Page 3 Energize/Startup De-energize/Shutdown Procedures Procedures SHUNT B SHUNT C AC IN AC HOT OUT AC NEUTRAL OUT CHASSIS GROUND/ CHASSIS GROUND/ NEGATIVE AC NEUTRAL IN AC HOT IN AC IN SHUNT A AC OUT GROUND ARRA ARRA FAULT FNDC NORMAL I/ON I/ON I/ON I/ON...
  • Page 4 General Wiring IMPORTANT: Example only. Actual wiring may vary depending on local electric code. Factory wiring is not shown. MATE3 SHUNT B SHUNT C AC IN Charge AC OUT Charge Controller #1 Controller #2 NEGATIVE AC HOT OUT AC NEUTRAL OUT CHASSIS GROUND/PE CHASSIS GROUND/PE AC NEUTRAL IN...