Installation instructions for ER shell ER EC flush-mounted exhaust air systems (according to DIN 18017-3) ER GH flush-moun- ted box for ER EC systems www.maico-ventilatoren.com...
Table of contents ER GH ceiling installation, Table of contents second room....... Preface ........... Electrical connection ......22 Scope of delivery ........Electrically connecting the unit ... 23 Overview of ER EC system ....Final mounting ........23 Intended use.......... Attaching fan insert.....
Preface • Plastic shutter Preface • Plaster protective cover Please read these instructions carefully before in- • Installation and operating instructions stalling the flush-mounted housing. Before the fi- nal assembly (fan insert and cover), please read ER EC fan insert (final assembly) the instructions for the ER covers.
Specialist installer qualifications ER GH flush-mounted housing with plastic Specialist installer qualifications shutter Installation may only be carried out by trained specialists who have the necessary knowledge 1 ER GH housing with housing floor seal and 3 and experience in ventilation engineering. The snap-fit fasteners for fan insert.
3 Safety instructions 3.2 Safety instructions regarding in- DANGER Explosion hazard due to explos- stallation, operation, cleaning and ive substances in the lab extraction units. Explosive substances in lab extraction units may maintenance ignite and cause serious explosions or fire. Aggressive substances may damage the unit.
Page 7
3 Safety instructions DANGER Danger if the relevant regula- WARNING Risk to health if filters are not tions for electrical installations are not ob- replaced or if there are no air filters. served. Heavily soiled or moist air filters can accumulate Before removing the housing cover or removing harmful substances (mould, germs, etc.).
4 System and product information 4.4 Possible combinations NOTICE Non-intended operation/impermiss- ible operation due to incorrectly mounted unit. Only install unit in accordance with the planning documents. In particular, note the information on ventilation channels and sound deadening. Observe planning instructions regarding unit pos- ition and distance to other façade components.
Page 9
4 System and product information • Electrical connection at side or rear. Cable • Energy-saving EC motor. feedthrough with stepped grommet. • Motor not speed controllable. • Can be mounted simply in the shaft with mount- • Air outlet adapter (scope of delivery) for conver- ing support or the mounting grooves.
5 Technical data 4.5 Covers: Functions ER-A ER-AK ER-AH ER-AB Filter change indicator ● (6 months) with TimeStrip Filter change indicator ● ● ● (6 months) with LED Control with time module ● ● ● Control with fully automatic humidity control: Extraction ●...
Power consumption air cross section of at least 150 cm², e.g. with ER EC and ER-A 3/5 W* Maico MLK door ventilation grille. • ER EC units have resistance to interference in ER-AK, ER-AH and ER- 2/2.5/3/5/17W* line with EN 55014-2 (depending on pulse type and an energy factor of 1000 to 4000 V).
Only store unit horizontally in a suitable, dry proval room. Ambient temperature – 10 °C to + 60 °C. Approval provisions Maico accepts no liability for corrosion damage caused by improper storage, e.g. storage in a Approval provision ER GH damp environment.
6 Mounting preparations 6.2 Preparations for wall installation 12 Suction duct for second room connection on Preparing the shaft ER GH: AFR 75/AFR 80 flexible aluminium 1. Produce opening in shaft or alternatively pro- duct duce a wall facing. Ensure a suitable, flat sur- face for the housing so that the fan insert can 14 Main duct: Steel folded spiral-seams duct be safely inserted in the housing later on.
6 Mounting preparations 8. Lay power cable in shaft and allow to protrude 9. Lay power cable: Electrically connecting the by around 30 cm above the shaft opening. unit [} 23]. 6.3 Ceiling installation preparations Preparing the shaft and suspended ceiling 12 Suction duct for second room connection on ER GH: AFR 75/AFR 80 flexible aluminium 1.
Page 15
6 Mounting preparations Main duct (steel folded spiral-seams Duct attachment with duct clamp, alternatively duct) duct attachment with clamping band ER GH connection duct: Flexible alu- minium duct Floor ceiling Steel threaded rod / stair bolt Duct fastener Duct clamp / clamping band Ceiling compound Shaft wall Wall/board seal...
6 Mounting preparations For wall installation with air outlet direction DANGER Risk of incorrect installation if (exhaust socket) to the left or right, install the non-permitted mounting material is used. shutter rotated by 90°, see following figures. Only secure connection duct to ceiling with per- mitted mounting material (duct clamp or clamping band).
6 Mounting preparations 5. Push the 4 push buttons into the housing 6.6 Conversion of exhaust socket for holes on the upper side of the housing at posi- air outlet towards rear tions [Y]. These must audibly engage. NOTICE If the air exhaust socket is installed incorrectly, the function of the unit is im- paired.
7 Housing installation 2. Push the exhaust socket into the slot on the • Ceiling installation and suspended ceiling: spiral housing until it audibly engages with the Installation with UPM 60/100 mounting support two locking tabs. or directly with the ceiling with ER-MS installa- tion kit (hammer head screws and brackets) in 3.
7 Housing installation 7.4 ER GH wall installation, single room 3. Mark fixing holes for mounting support on rear 2 Exhaust socket with plastic shutter shaft wall, produce holes and insert dowels. 4 Plaster protective cover Suitable mounting material is to be provided 14 Main duct, steel folded spiral-seams duct by the customer.
7 Housing installation 7. Provide unit with electrical connection: Elec- DANGER Danger of short-circuits and trically connecting the unit [} 23]. damage to the unit. 8. Insert the plaster protective cover in the hous- If the stepped grommet is not installed correctly, ing.
7 Housing installation 7.6 ER GH wall installation, second room 11.1 Installation socket for second room extrac- NOTICE The unit will be damaged/function tion DN 75/80 will be impaired by incorrect air if the installa- tion socket is inserted incorrectly [11.1]. 11.2 Adapter Degree of protection is no longer guaranteed.
8 Electrical connection 2. Mount housing on ceiling as described: ER GH Secure housing and the connection cable ceiling installation, single room [} 20]. with 2 mounting supports and/or clamping bands/ threaded rods each. 3. Mount ER-ZR second room connection set on ceiling as described in: ER GH wall installation, second room [} 21].
9 Final mounting • if the power cable is properly inserted through • with the cover screwed, closed and locked in the stepped grommet place • with the fan insert correctly engaged in the flush-mounted housing 8.1 Electrically connecting the unit 1.
9 Final mounting 9.1 Attaching fan insert S Central screw No tools are needed for the final assembly of 9 Air filter the fan insert. 9.3 Key lock 1. Plug the fan insert directly into the 3 studs in If a key lock is desired, activate the key lock on the interior of the flush-mounted housing.
1. Fit ER-AS extraction socket as described Con- AEH ER EC E059.2054.0000 version of exhaust socket for air outlet towards air outlet element rear [} 17]. In case of questions, please contact: Maico Elektroapparate-Fabrik GmbH Steinbeisstraße 20 78056 Villingen-Schwenningen, Deutschland...
• Air volume 30 m³/h, 60 m³/h according to fact- Fax +49 7720 694 175 ory setting. Further volumetric flows that can be set: base load: 20 m³/h, 30 m³/h, 40 m³/h, full E-mail: ersatzteilservice@maico.de load: 60 m³/h, 100 m³/h • Installation and operating instructions for ER Spare parts can be ordered at covers www.shop.maico-ventilatoren.com.
14 Dismantling • 2x replacement permanent filters for covers of Air filter ER EC fan unit (filter class G2) ZF EC+ replacement air filter for ER-A • 10x filter change indicator (TimeStrip) Article no. 0093.0610 14 Dismantling • 5x ZF EC+ replacement air filter (filter class G2) Dismantling may only be undertaken by a •...