Pacific Power Source UPC-3 Operation Manual

Hide thumbs Also See for UPC-3:
Table of Contents

Advertisement

Quick Links

UPC-3 / UPC-1
PROGRAMMABLE CONTROLLERS
FIRMWARE V4.25 AND LATER
OPERATION
MANUAL
PACIFIC
δ
POWER SOURCE

Advertisement

Table of Contents
loading

Summary of Contents for Pacific Power Source UPC-3

  • Page 1 UPC-3 / UPC-1 PROGRAMMABLE CONTROLLERS FIRMWARE V4.25 AND LATER OPERATION MANUAL PACIFIC δ POWER SOURCE...
  • Page 3 CONTROLLER, MODEL: S/N: POWER SOURCE, MODEL: S/N: THE INFORMATION CONTAINED IN THIS MANUAL IS PROPRIETARY TO PACIFIC POWER SOURCE, INC. AND MAY NOT BE COPIED OR REPRINTED WITHOUT ITS EXPRESSED WRITTEN CONSENT. PACIFIC POWER SOURCE, INC. 17692 Fitch Irvine, CALIF. 92614 SECOND EDITION COPYRIGHT (C) PPSI MARCH, 2004.
  • Page 4 WAS SHIPPED FROM THE FACTORY. LIMITED WARRANTY Pacific Power Source (PPS) warrants each unit to be free from defects in material and workmanship. For the period of two (2) years from the date of shipment to the purchaser, PPS will either repair or replace, at its sole discretion, any unit returned to its factory in Irvine, California.
  • Page 5: Table Of Contents

    SECTION 1 GENERAL TABLE OF CONTENTS PAGE HOW TO... FRONT PANEL REFERENCE ........ vi REMOTE INTERFACE FUNCTION REFERENCE......vii GENERAL ............. 1 USING THIS MANUAL......... 1 SAFETY NOTICES ........... 1 GENERAL PRODUCT DESCRIPTION ......3 1.3.1 UPC DESCRIPTION ........3 1.3.2 CONTROLLER MODELS ........
  • Page 6 SECTION 1 GENERAL INSTALLATION..........21 REMOVE INPUT SERVICE ........22 REMOVE COVER AND CABLING ....... 22 REMOVE EXISTING CONTROLLER ......22 INSTALL UPC ..........22 INSTALL CABLING AND COVER ....... 23 CONNECT INPUT SERVICE ........23 CONFIGURE UPC ........... 25 3.7.1 CONFIGURE TRANSFORMER RATIO ......
  • Page 7 SECTION 1 GENERAL GPIB and SERIAL REMOTE OPERATION ......77 INTRODUCTION ..........77 CONVENTIONS..........78 PROGRAM CONTROL ........80 5.3.1 STEADY-STATE OUTPUT PARAMETERS ..... 81 5.3.2 TRANSIENT SEGMENT PARAMETERS ....... 82 5.3.3 PROGRAM MEMORY CONTROL ......83 SIGNAL CONTROL .......... 83 5.4.1 OUTPUT PARAMETERS........
  • Page 8 SECTION 1 GENERAL RS-232 SERIAL REMOTE INTERFACE OPTION ..... 115 10.1 GENERAL..........115 10.2 SERIAL PORT SPECIFICATIONS ....... 115 10.3 SETUP ........... 116 10.4 OPERATION ..........116 10.4.1 COMMUNICATION MONITORING AID ......116 10.4.2 FUNCTIONAL EXCEPTIONS........ 117 10.4.3 FUNCTIONAL ADDITIONS ......... 117 10.5 PHYSICAL CONNECTIONS .........
  • Page 9 SECTION 1 GENERAL LIST OF ILLUSTRATIONS FIGURE 1.3 SCU/UPC-3, UPC-3, UPC-1.................... 5 FIGURE 2.3.3 J3 CONTROL AND OSCILLATOR................16 FIGURE 2.3.6 J5 AUXILIARY INPUTS AND OUTPUTS ..............18 FIGURE 2.3.8 J2 METERING INPUTS....................19 FIGURE 2.4 J4 GPIB REMOTE INTERFACE ................... 20 FIGURE 3.5...
  • Page 10: How To

    SECTION 1 GENERAL HOW TO... FRONT PANEL REFERENCE This is a quick reference to commonly used FRONT PANEL functions and will aid the user in quickly learning how to use functions of interest. HOW TO SECTION CALIBRATE OUTPUT AND METERS CALIBRATE PROGRAMMABLE OUTPUT IMPEDANCE 4.6.3.1.1 CHANGE OPERATING MODES...
  • Page 11: Remote Interface Function Reference

    SECTION 1 GENERAL REMOTE INTERFACE FUNCTION REFERENCE This is a quick reference to commonly used REMOTE INTERFACE functions and will aid the user in quickly finding the functions of interest. FUNCTION SECTION CALIBRATE METERING CALIBRATE PROGRAMMABLE OUTPUT IMPEDANCE 5.4.1 CLOSE / OPEN OUTPUT CONTACTOR 5.7.5, 5.4.2 CREATE A PROGRAM 5.3, 5.7.1...
  • Page 12 SECTION 1 GENERAL THIS PAGE INTENTIONALLY BLANK viii...
  • Page 13: General

    This manual is to be used with the programmable controller models: UPC-3 or UPC-1; or the manual operation controller models: UPC-3M or UPC-1M. These may be installed in the SCU (System Control Unit), or directly into one of Pacific Power Source’s ASX models.
  • Page 14 SECTION 1 GENERAL SAFETY NOTICES (cont) WARNING THIS EQUIPMENT CONTAINS HIGH ENERGY, LOW IMPEDANCE CIRCUITS!! LETHAL POTENTIALS ARE CONTAINED WITHIN THE CABINET. CARE MUST BE EXERCISED WHEN SERVICING THIS EQUIPMENT IN ORDER TO PREVENT SERIOUS OPERATOR INJURY OR EQUIPMENT DAMAGE. VOLTAGE AT THE TERMINALS RESPONDS INSTANTLY WHEN THE OUTPUT IS ACTIVATED.
  • Page 15: General Product Description

    Pacific Power Source's ASX Series Power Sources or into a System Control Unit for use with other power sources. The UPC is designed for use with any of Pacific Power Source, Inc.’s AC Power Sources and is interchangeable with other UPC/UMC Series controllers.
  • Page 16 GENERAL 1.3.1 UPC DESCRIPTION (cont’d) The signal generation section produces one (UPC-1) or three (UPC-3) output signals representing the output phase waveforms of the power source. The UPC controllers produce steady-state signals - a base set of volts, frequency, waveforms and phase angle - and dynamic signals in which parameters change with time.
  • Page 17: Figure 1.3 Scu/Upc-3, Upc-3, Upc-1

    SECTION 1 GENERAL PA CIFIC Figure 1.3a SCU/UPC-3 Figure 1.3b UPC-3 Figure 1.3c UPC-1...
  • Page 18: Controller Models

    The complete designation for a "stand-alone" controller housing a UPC- 3 is SCU/UPC-3. Such a unit can drive some of the larger PACIFIC AMX or ASX power sources through their rear panel interface. A typical usage might be to locate the power source at the base of an instrument rack, with the controller installed in an upper slot at a more convenient eye level or even in a completely different location.
  • Page 19: Specifications

    SECTION 2 SPECIFICATIONS SECTION 2 SPECIFICATIONS SPECIFICATIONS This section states the specifications of both Output Control and Metering capabilities of the UPC. Environmental Ambient operating conditions are as follows. Temperature 0-50ºC. Humidity 0-95% R.H Non-Condensing. CONTROL SPECIFICATIONS 2.1.1 FREQUENCY CONTROL SPECIFICATIONS The UPC output frequency is variable from 15 to 1200 Hz.
  • Page 20: Voltage Control Specifications

    SECTION 2 SPECIFICATIONS 2.1.2 VOLTAGE CONTROL SPECIFICATIONS The voltage amplitude of each vector can be varied independently. There are two output coupling modes selectable in the stored programs of the UPC. 1) DIRECT COUPLED MODE: Range: 0 to 150 VAC rms Resolution: 0.1 volts Output Ratio...
  • Page 21: Current Limit Control Specifications

    SECTION 2 SPECIFICATIONS 2.1.2.1 CSC (CONTINUOUS SELF CALIBRATION) SPECIFICATIONS CSC capability is not available in the Manual versions of the controller (UPC-3M and UPC-1M) The UPC includes a user selectable “Continuous Self Calibration” function. When active, this function maintains a constant output voltage amplitude at the metering sense point, comparing the metered voltage at that point to the set value and correcting for any difference.
  • Page 22: Waveform Control Specifications

    (see 4.6.2.3) 2.1.5 OUTPUT POWER FORM CONTROL SPECIFICATIONS The UPC-3 can create single (one), split (two), or three phase waveforms with ΦB and ΦC at any phase angle referenced to phase A. The UPC-1 generates only one output vector. When used in an AMX or ASX Power Source, it may generate single (one) and split (two) phase output.
  • Page 23: Phase Angle Control Specifications

    SECTION 2 SPECIFICATIONS 2.1.6 PHASE ANGLE CONTROL SPECIFICATIONS The phase angle displacement of the UPC 3 and UPC-3M oscillator output may be independently programmed for ΦB and ΦC. The phase relation between the three output vectors can be controlled from 0 to 359 deg. in 1 deg. increments. Phase A is always assumed to be at 0º as a reference. Range: 0 - 359 º...
  • Page 24: Metering Specifications

    SECTION 2 SPECIFICATIONS METERING SPECIFICATIONS 2.2.1 VOLTMETER SPECIFICATIONS Three voltmeter inputs are provided, one per phase. Both Voltage Line-to-Neutral (VLN) and Voltage Line-to-Line (VLL) voltages are metered. Vrms Meter Range: 354 VLN, 708 VLL A.C. Display Resolution: 0.1 VAC rms. The Remote interface may provide up to 3 digits of precision (digits to the right of the decimal point).
  • Page 25: Kilowatt Meter Specifications

    SECTION 2 SPECIFICATIONS 2.2.4 KILOWATT METER SPECIFICATIONS True kilowatt power metering is provided using the voltmeter and ammeter inputs. Display range and resolution is XXX.XXX kW. The Remote interface may provide 3 digits of precision (digits to the right of the decimal point).
  • Page 26: Electrical Interface

    SECTION 2 SPECIFICATIONS 2.2.7 WAVEFORM ANALYSIS (cont’d) The harmonic data is reported using a sine series with coefficients expressed in polar format (magnitude and phase angle). Each magnitude can be represented as an absolute value or as a percentage referenced to the fundamental which is always defined as having a magnitude of 100%.
  • Page 27: Output Control

    SECTION 2 SPECIFICATIONS 2.3.4 OUTPUT CONTROL Digital outputs are ± 15 VDC, positive logic. The UPC sends the following control signals to the power source on J3: NAME FUNCTION 3Φ - CMD 3Φ output form command 1Φ - CMD 1Φ output form command NOTE: If both 3Φ...
  • Page 28: Figure 2.3.3 J3 Control And Oscillator

    SECTION 2 SPECIFICATIONS (Rear of SCU) SPARE – CMD 3Φ – CMD 1Φ – CMD CONNECTOR – CMD EXT SENSE – CMD SPARE – CMD XFMR CPLD – CMD OUTPUT 0N – CMD LV COMMON SPARE – CONF SPARE – CONF CONNECTOR –...
  • Page 29: Analog Inputs

    SECTION 2 SPECIFICATIONS 2.3.6 ANALOG INPUTS Three Auxiliary Inputs are provided on J5, one per phase. The Auxiliary Inputs are AC coupled and algebraically summed to the Oscillator signals produced by the UPC. Note that the Auxiliary Inputs can be used as external inputs simply by programming the UPC for 0 VAC output. Auxiliary Input voltage range (Vaux): ±...
  • Page 30: Figure 2.3.6 J5 Auxiliary Inputs And Outputs

    SECTION 2 SPECIFICATIONS (Rear of SCU) LV COMMON LV COMMON TRANSIENT PEDESTAL LV COMMON LV COMMON SYNC OUT ΦA AM LO ΦA AM HI ΦB AM LO ΦB AM HI ΦC AM LO ΦC AM HI ΦA AUX IN LO ΦA AUX IN HI ΦB AUX IN LO ΦB AUX IN HI...
  • Page 31: Metering Inputs

    SECTION 2 SPECIFICATIONS 2.3.8 METERING INPUTS Metering inputs are on J2. Common mode must be within ± 10 V with respect to power supply peak common. (Rear of SCU) ΦA CURRENT HI ΦA CURRENT LO ΦB CURRENT HI ΦB CURRENT LO ΦC CURRENT HI ΦC CURRENT LO 1Φ...
  • Page 32: Gpib Remote Interface

    SECTION 2 SPECIFICATIONS GPIB REMOTE INTERFACE The GPIB Remote Interface is provided on J4. It has listener and talker capabilities. The GPIB device address is set via the UPC STATUS display screen. Default address is 1. See section 4.6.3.3 for configuration and section 5 for programming information. (Rear of SCU) DI 01 DI 05...
  • Page 33: Installation

    Refer to the power source manual for installation into a Pacific Power Source, Inc. power source system. Should a question arise, call Pacific Power Source, toll free, at 1-800-854-2433.
  • Page 34: Remove Input Service

    SECTION 3 INSTALLATION REMOVE INPUT SERVICE Turn the Input Power Circuit Breaker on the front panel OFF. Then disconnect the Input Line Cord from the rear of the SCU chassis. See figure 3.5. REMOVE COVER AND CABLING • Remove six screws from the top cover then remove the top cover. •...
  • Page 35: Install Cabling And Cover

    SECTION 3 INSTALLATION INSTALL CABLING AND COVER NOTE: Most users will not need to concern themselves with the following installation issue if the UPC is packaged with a power source. • Connect J2A of the UPC to P2A of the SCU. •...
  • Page 36: Figure 3.5 Installation

    SECTION 3 INSTALLATION ATTACH J4 TO ATTACH J5 TO REAR PANEL REAR PANEL J2A METERING CONNECT 133070 J6A TO P6A CONNECT J2A HEADER TO P2A SOCKET OSC B, OSC C, & GPIB DISPLAY KEYBOARD CONNECT - 2 PLACES - 133071 P3A TO ATTACH CIRCUIT...
  • Page 37: Configure Upc

    SECTION 3 INSTALLATION CONFIGURE UPC The UPC TRANSFORMER RATIO and AMPS TO VOLTS RATIO must be configured to operate with the Power Source. Setting the GPIB device address or RS-232 SERIAL Interface parameters is optional depending on whether the user intends to use the REMOTE interface. 3.7.1 CONFIGURE TRANSFORMER RATIO NOTE: Most users will not need to concern themselves with the unit configuration as it is set at the factory if the UPC is packaged with a power source.
  • Page 38: Configure Serial Port Settings

    SECTION 3 INSTALLATION 3.7.3 CONFIGURE SERIAL PORT SETTINGS After installing the UPC (or after erasing all program memory or after system RESET), the RS-232 communication parameters must be set (BAUD RATE, PARITY and EOS Terminator) as follows: Press the fn key, select GENERAL SETUP then UPC STATUS. Press the EDIT key and enter the desired BAUD RATE numerically, selected from the list above.
  • Page 39: Front Panel Operation

    This section describes the front panel operation of an UPC Controller installed a power source. The UPC controllers are used with Pacific Power Source, Inc’s AMX, ASX, G, and MS series equipment. The UPC Controller allows the user to control all output parameters of the power source via the front panel keyboard as well as through the REMOTE interface (see Section 5 for REMOTE operation).
  • Page 40 SECTION 4 OPERATION 4.1.1 QUICK OVERVIEW (cont) The PROGRAM OPERATE mode attempts to simplify certain test operations by allowing the operator to execute pre-stored programs (combinations of Volts, Frequency, Output Coupling, Transformer tap selection if any, Phase angle, Waveform, and Current limit. A stored program can be executed simply by pressing PROGRAM, entering a program number, then EXECUTE.
  • Page 41 SECTION 4 OPERATION 4.1.1 QUICK OVERVIEW (cont) SELECTING OPERATING MODES On first turn-on the system will operate using a set of default parameters stored in memory. The display will be the V/I METER display. This is the default - and most frequently used - display. It shows all basic operating parameters, and in the lower left portion shows the operating mode.
  • Page 42: Quickly Putting The Unit To Use

    SECTION 4 OPERATION 4.1.2 QUICKLY PUTTING THE UNIT TO USE The following steps provide a quick method (using MANUAL MODE) for setting Voltage and Frequency and applying power to a load. To set other parameters, such as phase angle, waveform, current limit, power form and output coupling mode (transformer or direct), use the PROGRAM EDIT MODE.
  • Page 43: Figure 4.1 Power Source Front Panel

    SECTION 4 OPERATION FIGURE 4.1 POWER SOURCE FRONT PANEL...
  • Page 44: Front Panel Controls And Indicators

    SECTION 4 OPERATION FRONT PANEL CONTROLS AND INDICATORS This section shows the locations and defines the functions of the front panel controls and indicators of the UPC as installed in an AMX/ASX Series power source. Operation of an UPC installed in an SCU is identical except the SCU has no Output Power Switch.
  • Page 45: Upc Front Panel

    SECTION 4 OPERATION 4.2.2 UPC FRONT PANEL LIQUID CRYSTAL Gives pertinent information to the user relating to front panel DISPLAY operation. (LCD) LOCAL / REMOTE When the REMOTE INTERFACE is in control of the UPC and has (KEY and LED) not issued a local lockout command, this key will return control to the keyboard.
  • Page 46 SECTION 4 OPERATION 4.2.2 UPC FRONT PANEL (cont’d) ENTER Is used to enter numeric values then move the cursor to the next (KEY) data field. PROGRAM When pressed from any meter display causes PROGRAM (KEY) OPERATE MODE to be active. EDIT When pressed from the PROGRAM display causes PROGRAM (KEY)
  • Page 47: Manual Mode

    SECTION 4 OPERATION MANUAL MODE This section describes operation in Manual Mode. In this mode you may slew or directly enter voltage or frequency values. Parameters other than volts and frequency can only be changed by editing and executing a steady-state Program. The V/I METER display will indicate MANUAL MODE in the lower left corner of the display.
  • Page 48 SECTION 4 OPERATION 4.3.1 METERING DISPLAYS (cont) 4.3.1.1 WAVEFORM ANALYSIS (OPTION- Harmonic Analysis and Synthesis) Waveform analysis functions are optionally available to report both magnitude and phase angle (relative to 0º of the fundamental voltage waveform) of each harmonic for metered voltage and current waveforms.
  • Page 49 SECTION 4 OPERATION 4.3.1.1 WAVEFORM ANALYSIS (cont’d) (OPTION- Harmonic Analysis and Synthesis) The default harmonic content is displayed based upon the percentage of the fundamental. The EDIT key displays a setup screen that allows selection of the harmonic content display as absolute value, rather than percentage.
  • Page 50: Voltage Entry

    SECTION 4 OPERATION 4.3.2 VOLTAGE ENTRY To achieve MANUAL MODE and change voltage, from any meter display light the Va, Vb, Vc LEDs by pressing those keys. Pressing an ARROW key (︿ or ﹀) causes selected voltages to slew up or down. Entering a number then pressing EXECUTE causes selected voltages to change to the new value.
  • Page 51: Program Execution

    SECTION 4 OPERATION 4.4.1 PROGRAM EXECUTION To achieve Program Operate Mode, from any meter display press the PROGRAM key. This will cause the PROGRAM display to become active. The last or currently executing program will be displayed. You may enter a new program number then press ENTER to view it. PROGRAM: #1 FORM=3 COUPLING=DIRECT FREQ=60...
  • Page 52 SECTION 4 OPERATION 4.4.2 TRANSIENT EXECUTION (cont’d) The basic process of creating a transient program is as follows. 1. From the V/I meter, press PROGRAM, enter the program number, press ENTER. 2. Press EDIT. Change steady-state values if desired, pressing ENTER after each entry. 3.
  • Page 53 SECTION 4 OPERATION 4.4.2.1 MIL-STD-704D TRANSIENT PROGRAMS (cont) OVER-VOLTAGE TRANSIENT (Program #100) The power source will produce the over-voltage transient excursion as defined by MIL-STD-704D (Paragraph 5.2.3.2.1). The power source must be configured for a voltage range of at least 180Vrms to perform this test.
  • Page 54 SECTION 4 OPERATION 4.4.2.1 MIL-STD-704D TRANSIENT PROGRAMS (cont) OVER-FREQUENCY TRANSIENT (Program #102) The power source will produce the over-frequency transient excursion as defined by MIL-STD-704D (Paragraph 5.2.3.2.1). The power source must be configured for a voltage range of at least 115Vrms to perform this test.
  • Page 55 SECTION 4 OPERATION 4.4.2.1 MIL-STD-704D TRANSIENT PROGRAMS (cont) UNDER-FREQUENCY TRANSIENT (Program #103) The power source will produce the under-frequency transient excursion as defined by MIL-STD-704D (Paragraph 5.2.3.2.1). The power source must be configured for a voltage range of at least 115Vrms to perform this test.
  • Page 56: Program Edit Mode

    SECTION 4 OPERATION PROGRAM EDIT MODE This section describes the Program Edit Mode which allows program and transient definition and editing. 4.5.1 PROGRAM EDITING To achieve Program Edit Mode, from any meter display press the PROGRAM key, program number, ENTER key then EDIT key. The cursor will move to FORM. PROGRAM: #1 FORM=3 COUPLING=DIRECT FREQ=60...
  • Page 57 SECTION 4 OPERATION 4.5.1 PROGRAM EDITING (cont) FREQ: Any desired output frequency from 15.00 to 1200 Hz. may be entered. The FREQUENCY SPAN must be set for the correct range before the Program can be EXECUTED. RANGE RESOLUTION 15.00 - 99.99 Hz. 0.01 Hz.
  • Page 58 SECTION 4 OPERATION 4.5.1.1 PROGRAM EXAMPLE The following is an example of how to create and execute a 3 phase, 108/187 volt, 400 Hz. program. From any metering display press the PROGRAM key. PROGRAM: #1 FORM=3 COUPLING=DIRECT FREQ=60 Va=120 Vb=120 Vc=120 WFa=1 WFb=1...
  • Page 59 SECTION 4 OPERATION 4.5.1.1 PROGRAM EXAMPLE (cont) Press 108, ENTER, 108, ENTER, 108, ENTER, to select 108 volts line to neutral on all three phases. PROGRAM: #4 FORM=3 COUPLING=DIRECT FREQ=400 Va=108 Vb=108 Vc=108 WFa=1 WFb=1 WFc=1 #SEGS=0 Ilim=50 PHb=120º PHc=240º Press 1, ENTER, 1, ENTER, 1, ENTER, to select Waveform 1 on all three phases.
  • Page 60: Transient Editing

    SECTION 4 OPERATION 4.5.2 TRANSIENT EDITING Before beginning to create a transient, the sequence of the voltage, frequency, and waveform changes should be fully defined. The UPC allows transient events to be defined in two ways: Time-based transients and Cycle-based transients. Transient event timing always begins at 0 degrees of ΦA (the rising 0 volt crossing), and will proceed based on defined Segments.
  • Page 61 SECTION 4 OPERATION 4.5.2 TRANSIENT EDITING (cont’d) The following may be programmed: SEGMENT #: Segments define each “event” of a transient. Each segment provides a linear transition in volts and/or frequency in the time indicated. Different waveforms may also be switched in during each segment. Normally don't enter a number here.
  • Page 62 SECTION 4 OPERATION 4.5.2.1 TIME BASED TRANSIENT EXAMPLE The following is an example of how to create a MIL-STD-704D time based transient. (See section 4.4.2 regarding pre-stored transients) Start with the previous program #4 example as shown in section 4.5.1. From any metering display press PROGRAM, 4, ENTER, EDIT, EDIT, and you should see the following display: TRANSIENT: PRGM #4 SEGMENT #1...
  • Page 63 SECTION 4 OPERATION 4.5.2.1 TIME BASED TRANSIENT EXAMPLE (cont) Press 1, ENTER, 1, ENTER, 1, to select Waveform 1 on all three phases. TRANSIENT: PRGM #4 SEGMENT #1 OF 1 T=0.0002 Va=80 Vb=80 Vc=80 F=400 WFa=1 WFb=1 WFc=1 Press ENTER, now we are starting segment 2 of 2. TRANSIENT: PRGM #4 SEGMENT #2 OF 2...
  • Page 64 SECTION 4 OPERATION 4.5.2.1 TIME BASED TRANSIENT EXAMPLE (cont) Press 1, ENTER, 1, ENTER, 1, to select Waveform 1 on all three phases. TRANSIENT: PRGM #4 SEGMENT #2 OF 2 T=0.01 Va=80 Vb=80 Vc=80 F=400 WFa=1 WFb=1 WFc=1 Press ENTER, now we are starting segment 3 of 3. TRANSIENT: PRGM #4 SEGMENT #3 OF 3...
  • Page 65 SECTION 4 OPERATION 4.5.2.1 TIME BASED TRANSIENT EXAMPLE (cont) Press 1, ENTER, 1, ENTER, 1, to select Waveform 1 on all three phases. TRANSIENT: PRGM #4 SEGMENT #3 OF 3 T=0.07 Va=108 Vb=108 Vc=108 F=400 WFa=1 WFb=1 WFc=1 Press STORE, to save the transient sequence. TRANSIENT EVENTS: ENTER # OF TRANSIENT EVENTS 1 0 FOR INFINITE OR 1-65535.
  • Page 66 SECTION 4 OPERATION 4.5.2.2 CYCLE BASED TRANSIENT EXAMPLE The following is an example of how to create a cycle based transient. This example presumes the user has loaded the program information as described in the previous examples. Start with program #4 example as shown in section 4.5.1.1. From any metering display press PROGRAM, 4, ENTER, EDIT, EDIT, and you should see the following display: TRANSIENT: PRGM #4 SEGMENT #1...
  • Page 67 SECTION 4 OPERATION 4.5.2.2 CYCLE BASED TRANSIENT EXAMPLE (cont) Press 15, ENTER, 15, ENTER, 15, to select waveform #15 on all three phases. TRANSIENT: PRGM #4 SEGMENT #1 OF 1 T=1 CYCLE Va=122 Vb=122 Vc=122 F=400 WFa=15 WFb=15 WFc=15 Press STORE, to save the transient sequence. TRANSIENT EVENTS: ENTER # OF TRANSIENT EVENTS 1 0 FOR INFINITE OR 1-65535.
  • Page 68: Figure 4.5.2.1 Mil-Std-704D Undervoltage Transient

    SECTION 4 OPERATION START OF TRANSIENT END OF TRANSIENT SEGMENT 1 SEGMENT SEGMENT 108 VAC MIN STEADY-STATE LIMIT TIME, MILLISECONDS FIGURE 4.5.2.1 TIME BASED TRANSIENT - MIL-STD-704D UNDERVOLTAGE TRANSIENT WAVEFORM #2 WAVEFORM #3 WAVEFORM #1 SEGMENT 1 USES WAVEFORM #15 CYCLE BASED TRANSIENT FIGURE 4.5.2.2 SPIKE TRANSIENT...
  • Page 69: Setup Mode

    SECTION 4 OPERATION SETUP MODE SETUP MODE is used to: • Copy and Delete Programs • Copy, Edit, and Create Waveforms • Set Min. and Max. Voltage Limits • Set Min. and Max. Frequency Limits • Engage and Disengage CSC (Continuous Self Calibration) •...
  • Page 70 SECTION 4 OPERATION 4.6.1.1 COPY PROGRAM COPY PROGRAM is used to copy Program data. From any METER display (V/I, AMPS or POWER), press the fn key to enter SETUP MODE. From the SETUP display, press 1 to enter PROGRAM SETUP. From the PROGRAM SETUP display, press 1 to enter COPY PROGRAM.
  • Page 71: Waveform Setup

    SECTION 4 OPERATION 4.6.1.3 ERASE ALL RAM AND RESET CPU ERASE ALL RAM AND RESET CPU is used to erase edited programs 1-99 and edited waveforms 2-22. This will reset everything in the UPC including calibration values. Only do this if the UPC is acting abnormally or to restore all default settings.
  • Page 72 SECTION 4 OPERATION 4.6.2.1 EDIT WAVEFORM EDIT WAVEFORM is used to change or modify waveforms. From any METER display (V/I, AMPS or POWER), press the fn key to enter SETUP MODE. From the SETUP display, press 2 to enter WAVEFORM SETUP. From the WAVEFORM SETUP display, press 1 to enter EDIT WAVEFORM.
  • Page 73 SECTION 4 OPERATION 4.6.2.1 EDIT WAVEFORM (cont) Press 2, ENTER, to select waveform 2. EDIT WAVEFORM: NUMBER=2 RANGE=2-22 STARTING PHASE ANGLE =0 0-359.9º ENDING PHASE ANGLE 0-359.9º VOLTAGE IN PERCENT =100 (+/-)0-100% Press 85, ENTER, to select the start angle. EDIT WAVEFORM: NUMBER=2 RANGE=2-22 STARTING PHASE ANGLE =85...
  • Page 74: Figure 4.6.2.1 Edited Waveform

    SECTION 4 OPERATION 100% 85° 95° 100% 0° FIGURE 4.6.2.1 EDITED WAVEFORM...
  • Page 75 SECTION 4 OPERATION 4.6.2.2 COPY WAVEFORM COPY WAVEFORM is used to copy waveforms from one waveform number to another. From any METER display (V/I, AMPS or POWER), press the fn key to enter SETUP MODE. From the SETUP display, press 2 to enter WAVEFORM SETUP. From the WAVEFORM SETUP display, press 2 to enter COPY WAVEFORM.
  • Page 76 SECTION 4 OPERATION 4.6.2.3 WAVEFORM SYNTHESIS (Option: Harmonic Analysis and Synthesis) WAVEFORM SYNTHESIS creates waveforms by using a sine wave series defined by Harmonic Magnitude and Phase Angle coefficients expressed in polar format (magnitude and phase angle). Each magnitude percentage is referenced to the fundamental which is always defined as having a magnitude of 100%.
  • Page 77 SECTION 4 OPERATION 4.6.2.3 WAVEFORM SYNTHESIS (cont’d) (Option: Harmonic Analysis and Synthesis) The harmonic synthesis feature uses the formula: WAVEFORM = Σ α sin(nwτ + δ) to calculate the finished waveform values. Where: n = harmonic number = harmonic amplitude (% of fundamental) α...
  • Page 78: General Setup

    SECTION 4 OPERATION 4.6.3 GENERAL SETUP GENERAL SETUP is used for UPC SETUP, UPC STATUS and POWER SOURCE STATUS. From any METER display (V/I, AMPS or POWER), press the fn key to enter SETUP MODE. From the SETUP display, press 3 to enter GENERAL SETUP 1. GENERAL SETUP 1: 4 POWER SOURCE STATUS 1 UPC SETUP...
  • Page 79 SECTION 4 OPERATION 4.6.3.1 UPC SETUP (cont’d) PROG.Zo: Programmable Output Impedance (OPTION) - Press EDIT to access the PROG.Zo menu (para 4.6.3.1.1). This option is used to compensate for dynamic loss in the output circuit or to control the output impedance of the power source by responding in real time to changes in the output current.
  • Page 80 SECTION 4 OPERATION 4.6.3.1.1 PROGRAMMABLE OUTPUT IMPEDANCE SETUP MENUS (cont) CAUTION USE THIS FUNCTION WITH CARE CARELESS OR IMPROPER USE OF THE PROGRAMMABLE OUTPUT IMPEDANCE FUNCTION MAY RESULT IN OVER-VOLTAGE OR UNDER-VOLTAGE BEING PRESENTED TO THE LOAD, AND MAY CAUSE DAMAGE TO THE LOAD. REACTIVE LOADS MAY CAUSE THE OUTPUT POWER TO BECOME UNSTABLE (OSCILLATE) AND MAY CAUSE DAMAGE TO THE LOAD IF EXCESSIVE NEGATIVE IMPEDANCE IS USED! 4.6.3.1.1.1 PROGRAMMABLE OUTPUT IMPEDANCE CALIBRATION MENU...
  • Page 81 SECTION 4 OPERATION 4.6.3.1.1.1 PROGRAMMABLE OUTPUT IMPEDANCE CALIBRATION MENU (cont’d) Ø column: indicates the Power Form of operation (1, 2 or 3 phase). Z direct column: accepts the Direct coupled impedance of the power source (per phase) for each Power Form listed on the far left. During DIRECT coupled operation, the proper Z direct value is used to calibrate the PROG.Zo function based upon the Power Form selected in the Program being executed.
  • Page 82 SECTION 4 OPERATION 4.6.3.2 FREQUENCY SPAN FREQUENCY SPAN sets the available frequency range and resolution of the output waveform and the number of samples per cycle used for metering data. From any METER display (V/I, AMPS or POWER), press the fn key to enter SETUP MODE. From the SETUP display, press 3 to enter GENERAL SETUP.
  • Page 83 SECTION 4 OPERATION 4.6.3.3 UPC STATUS (cont’d) For systems equipped with a manual controller (UPC-3M or UPC-1M), the display will be: UPC STATUS: FIRMWARE 141999 v4.25 TRANSFORMER RATIO 2.00 PAs=3 AMPS:VOLTS RATIO 4.00A=1 V PRI To change any of these settings, press ENTER to move the cursor to each data field. Press EDIT when the cursor is positioned on the value to be changed.
  • Page 84 SECTION 4 OPERATION 4.6.3.4 POWER SOURCE STATUS POWER SOURCE STATUS indicates the state of internal control signals between the UPC and the Power Source circuits. See para 2.3.4 OUTPUT CONTROL and para 2.3.5 INPUT CONTROL for a description of these signals. This display is only used for technical diagnostics. From any METER display (V/I, AMPS or POWER), press the fn key to enter SETUP MODE.
  • Page 85 SECTION 4 OPERATION 4.6.3.5 RANGE CONTROL (cont’d) SELECT OUTPUT RANGE: 1, 2, 3, 4. The following ranges are applicable. PROGRAMMED OUTPUT AC VOLTS RANGE # < 110 110 - 120.9 121 - 130.9 > 131 NOTE: The above Output voltages are for Single phase operation. If split (2) phase operation is used, the listed Output voltage ranges are doubled.
  • Page 86 SECTION 4 OPERATION 4.6.3.7 CT XFMR LOCATION Selecting CT XFMR LOCATION from the General Setup 2 menu (fn,3,7,1) allows you to specify the location of the current transformer used for the current metering display. From any METER display (V/I, AMPS or POWER), press the fn key to enter SETUP MODE. From the SETUP display, press 3 to enter GENERAL SETUP.
  • Page 87 SECTION 4 OPERATION 4.6.3.8 TRANSIENT WFs (cont’d) If DISABLED, the RMS calculation of substituted waveforms does not occur. The amplitude of all waveforms used in the transient will then be based on the system gain factor for each phase, as calculated for the Program which contains the transient. This facilitates constant-amplitude transients, such as partial cycle dropouts or sub-cycle spike transients.
  • Page 88 SECTION 4 OPERATION 4.6.3.10 KEYBOARD LOCK Selecting KEYBOARD LOCK from the General Setup 2 menu (fn,3,7,4) allows you to control the keyboard lock feature. From any METER display (V/I, AMPS or POWER), press the fn key to enter SETUP MODE. From the SETUP display, press 3 to enter GENERAL SETUP.
  • Page 89: Gpib And Serial Remote Operation

    SECTION 5 REMOTE OPERATION SECTION 5 GPIB and SERIAL REMOTE OPERATION GPIB and SERIAL REMOTE OPERATION This section describes remote control functions of the UPC over the IEEE-488 BUS or RS-232 Serial Remote Interface. It is strongly recommended that the user read Section 4 (Front Panel Operation) to become familiar with the capabilities of the UPC.
  • Page 90: Conventions

    SECTION 5 REMOTE OPERATION CONVENTIONS COMMANDS are shown in the left hand column in BOLD, beginning with an asterisk ( * ) or colon ( : ) text with NO underline. Command DESCRIPTIONS appear in the right hand column. SCPI is "Standard Commands for Programmable Instruments -1992". Refer to the SCPI 1992 standard for more information.
  • Page 91 SECTION 5 REMOTE OPERATION CONVENTIONS (cont) Multiple data parameter names and values must be separated by commas. 'Multiple keyword' messages may be sent without duplicating the first level SCPI keyword (i.e., SOURce). e.g., :SOURce:VOLTage1,120; VOLTage2,120; VOLTage3,120. A keyword is a single word beginning with a colon (:). Program Messages MUST be terminated with a LINE FEED (0Ahex, 10dec) or END (EOI) signal.
  • Page 92: Program Control

    SECTION 5 REMOTE OPERATION PROGRAM CONTROL :PROGram:NAME <nn> Command: selects program “nn” for executing, deleting or copying. nn = <0> to <99> Query: returns the program number last selected. :PROGram[:SELected]:DEFine <program> Command: defines the values stored in program “nn”. Both steady- state and transient segment parameter names and values may be sent.
  • Page 93: Steady-State Output Parameters

    SECTION 5 REMOTE OPERATION 5.3.1 STEADY-STATE OUTPUT PARAMETERS FORM,<n> sets Output Power Form of selected program. n = <1>Single Φ, <2>Split Φ, or <3>Three Φ COUPLing,<s> sets Output coupling of selected program. s = <DIRECT> or <XFMR> XFMRRATIO,<n.nn> sets Output XFMR ratio (n.nn:1) of selected program. n.nn = <0.05>...
  • Page 94: Transient Segment Parameters

    SECTION 5 REMOTE OPERATION 5.3.2 TRANSIENT SEGMENT PARAMETERS SEGment,<n> selects transient segment “n” of the presently selected Program to be edited. n = <1> to <100> FSEG,<n> sets objective Frequency of selected segment. n = <:SOUR:FREQ:LIM:MIN> to <:SOUR:FREQ:LIM:MAX> Hz. VSEG,<n> sets objective voltage ΦA, ΦB, ΦC of selected segment.
  • Page 95: Program Memory Control

    SECTION 5 REMOTE OPERATION 5.3.3 PROGRAM MEMORY CONTROL :PROGram:[SELected:]DELete Command: (No query) deletes selected program. :PROGram:DELete:ALL Command: (No query) deletes all programs, waveforms, calibration data and setup values. Performs device RESET, loads Program #1 with *RST default values, executes MANUAL MODE with *RST values. Waveforms (1-16) are re-loaded from ROM.
  • Page 96 SECTION 5 REMOTE OPERATION 5.4.1 OUTPUT PARAMETERS (cont) :[SOURce:]FREQuency <n> sets Output Frequency. n = <:SOUR:FREQ:LIM:MIN> to <:SOUR:FREQ:LIM:MAX> Hz. Also query Frequency display with :MEASure:FREQuency?. Returns the set value only, as UPC does not measure Frequency. :[SOURce:]CURRent:LIMit <n> sets Output Current Limit. n = <0>...
  • Page 97 SECTION 5 REMOTE OPERATION 5.4.1 OUTPUT PARAMETERS (cont) :[SOURce:]RANGe <n> sets Output Range Control (for power sources with Range Control). n = <0> to <4>. 0 sets the mode to AUTO. See 4.6.3.5 :[SOURce:]IMPEDance:STATE <b> Enables or disable optional Programmable Output Impedance function. b = <OFF>, <0>...
  • Page 98: Signal Routing

    SECTION 5 REMOTE OPERATION 5.4.2 SIGNAL ROUTING :[SOURce:]FORM <n> Sets Output power form. n = <1>Single Φ, <2>Split Φ, or <3>Three Φ :[SOURce:]COUPLing <s> Sets Output coupling. s = <DIRECT> or <XFMR> :[SOURce:]VOLTage:ALC[:STATE] <b> The ALC keyword controls CSC enable/disable. b = <OFF>...
  • Page 99: Query Functions

    SECTION 5 REMOTE OPERATION QUERY FUNCTIONS The following are 'query only' functions sent to the UPC through the communication bus. 5.5.1 CONFIGURATION QUERIES These query parameters cannot be set via the remote communication port. The values of each are specific to the hardware configuration of the individual power source. :[SOURce]:XFMRRATIO? Query: Output XFMR ratio.
  • Page 100 SECTION 5 REMOTE OPERATION 5.5.2 METERED DATA QUERIES (cont) :MEASure:FREQuency? Query: for programmed Frequency. The returned value is only an indicator of the set Frequency. The UPC does not actually measure Frequency. Returns <15.00> to <1200> Hz. :MEASure:CURRent[:RMS]1? Query: metered RMS current ΦA. Returns <0>...
  • Page 101 SECTION 5 REMOTE OPERATION 5.5.2 METERED DATA QUERIES (cont) :MEASure:PF1? Query: metered power factor (KW/KVA) ΦA. Returns <0> to <1.0> :MEASure:PF2? Query: metered power factor (KW/KVA) ΦB. Returns <0> to <1.0> :MEASure:PF3? Query: metered power factor (KW/KVA) ΦC. Returns <0> to <1.0> :FETCh[:WAVEform]:VOLT1? :FETCh[:WAVEform]:CURRent1? Query: metered waveform data (line-to-neutral voltage only).
  • Page 102: Event And Status Reporting

    SECTION 5 REMOTE OPERATION 5.5.3 EVENT and STATUS REPORTING Events and device Status may be queried by the Bus Controller through the following registers and queues. Query commands are explicitly shown in this section for clarity. NOTE: It is recommended that reading EVENT and STATUS registers and queues occur in the following order.
  • Page 103: Figure 5.1 Status Byte Model

    SECTION 5 REMOTE OPERATION QUEUE READ BY NOT-EMPTY ADDRESSIN G UPC AS A TALKER OUTPUT QUEUE RESERVED SHUTDOWN READ BY SERIAL POLL SERVICE STATUS BYTE REQUEST REGISTER GENERATION READ BY *STB? & & & & & & & SERVICE REQUEST ENABLE REGISTER *SRE <NRf>...
  • Page 104: Figure 5.2 Standard Event Register Model

    SECTION 5 REMOTE OPERATION 5.5.3.1 IEEE-488.2 STATUS REPORTING (cont) STANDARD EVENT STATUS REGISTER (ESR) Events reported by the STANDARD EVENT STATUS register may be queried via the *ESR? command. Reading the ESR register clears it. The EVENT STATUS summary bit in the STATUS BYTE (STB) will be set when an unmasked EVENT STATUS bit goes true.
  • Page 105 SECTION 5 REMOTE OPERATION 5.5.3.1 IEEE-488.2 STATUS REPORTING (cont) IEEE-488.2 STATUS REPORTING COMMANDS NAME DEFINITION *IDN? Device Identification query. Returns <PPSC,UPC-M,vN.NN,1419XX> where M is the model number (1 or 3), N.NN is the firmware version number XX is the firmware assembly indicating installed options *CLS Clears the ESR and the STB registers as well as the SCPI :EVENt registers and ERROR/EVENT queue...
  • Page 106 SECTION 5 REMOTE OPERATION 5.5.3.2 SCPI STATUS REPORTING (cont) The STATus:OPERation and STATus:QUEStionable registers provide information about the present mode of operation. See fig. 5.3. • Transition of a CONDition bit to the true state causes the EVENt bit to be set true. •...
  • Page 107: Figure 5.3 Scpi Status Registers Model

    SECTION 5 REMOTE OPERATION ERROR/EVENT QUEUE Queue To EEQ bit of Not Empty STATUS BYTE (bit 2) [SYSTem:ERRor?] FED INTO OUTPUT QUEUE QUEStionable status (enabled events) VOLTage CURRent TIME POWer TEMPerature Logical OR FREQuency PHASe To SQS bit of MODulation STATUS BYTE CALibration (bit 3)
  • Page 108: Device Control

    SECTION 5 REMOTE OPERATION DEVICE CONTROL :SYSTem:BEEPer Command: sounds the front panel beeper once. No query. :SYSTem:KLOCK <b> Command: sets the keyboard lock enable state (para. 4.6.3.10). b = .<1> enables keyboard lock; <0> disables keyboard lock. Query: returns present lock enable state. :CALibrate:ZERO Command: resets all Metering correction factors.
  • Page 109: Ieee-488.1 Interface Functions

    SECTION 5 REMOTE OPERATION 5.6.1 IEEE-488.1 INTERFACE FUNCTIONS The following lists the IEEE-488.1 capabilities of the UPC. Refer to the ANSI/IEEE-488.1 1987 standard for more information. FUNCTION MNEMONIC REMOTE MESSAGE RECEIVED / Description Source handshake functions Acceptor handshake functions MTAnn - Talker subset 6. nn is GPIB device address 0-30 MLAnn - Listener subset 3.
  • Page 110: Ieee-488.2 Device Control Commands

    SECTION 5 REMOTE OPERATION 5.6.2 IEEE-488.2 DEVICE CONTROL COMMANDS The following lists the IEEE-488.2 Common Commands for Device Control of the UPC. Refer to the ANSI/IEEE-488.2 1987 standard for more information. *RST Command: RESET. Initialize the UPC with the following parameters: CURRENT LIMIT CURRENT METERING RANGE INITIAL VOLTAGE...
  • Page 111: Remote Control Examples

    SECTION 5 REMOTE OPERATION REMOTE CONTROL EXAMPLES The REN (remote enable) line on the bus interface must be kept true to maintain REMOTE CONTROL. REMOTE CONTROL can only be initiated while the UPC is displaying a Metering display or while in the UPC STATUS display, not while editing.
  • Page 112: Example Of Storing A Program

    SECTION 5 REMOTE OPERATION 5.7.1 EXAMPLE OF STORING A PROGRAM Step A. Address the UPC as a listener. :PROGram:NAME 1 <eos> Step B. Select Program 1. NOTE: <eos> is a LINE FEED (0Ahex, 10dec). Step C. Define program 1. Program 1 consists of steady-state and optional transient segment parameter names and values.
  • Page 113: Example Of Program Query

    SECTION 5 REMOTE OPERATION 5.7.2 EXAMPLE OF PROGRAM QUERY Step A. Address the UPC as a listener. :PROGram:NAME 1 <eos> Step B. Select Program 1. NOTE: <eos> is a LINE FEED (0Ahex, 10dec). :PROGram:DEFine? <eos> Step C. Query Program 1. Program 1 consists of steady-state and optional transient segment parameter names and values.
  • Page 114: Example Of Executing A Stored Program

    SECTION 5 REMOTE OPERATION 5.7.3 EXAMPLE OF EXECUTING A STORED PROGRAM Step A. Address the UPC as a listener. :PROGram:NAME 1 <eos> Step B. Select Program 1. NOTE: <eos> is a LINE FEED (0Ahex, 10dec) :PROGram:EXECute <eos> Step C. Execute Program. Step D.
  • Page 115: Example Of Voltage And Current Measurement Query

    SECTION 5 REMOTE OPERATION 5.7.6 EXAMPLE OF VOLTAGE and CURRENT MEASUREMENT QUERY How to query the UPC for three phase RMS volts (Line to Neutral) and RMS current metered values. LINE to LINE volts, KVA, KW, Power Factor, CURRENT Crest Factor, and Peak Current may also be queried in the same way.
  • Page 116: Examples Of Voltage And Current Waveform Query

    SECTION 5 REMOTE OPERATION 5.7.7 EXAMPLES OF VOLTAGE and CURRENT WAVEFORM QUERY This is an example of how to query the UPC for metered waveform values for phase A voltage and current. Step A. Address the UPC as a listener. Step B.
  • Page 117: Maintenance

    SECTION 6 MAINTENANCE SECTION 6 MAINTENANCE MAINTENANCE No maintenance is required for the UPC controller. See the AMX, ASX, G, or MS series power source Operator’s Manual for proper maintenance of the power systems.
  • Page 118: Service

    SERVICE SERVICE There are no user serviceable components in the UPC assembly. Pacific Power Source maintains a staff of highly trained technicians which are able to assist with diagnosing abnormal operation of the UPC. If questions arise, please call the factory at 1-800-854-2433 (8am to 5pm PST, California, U.S.A.).
  • Page 119: Calibration

    SECTION 8 CALIBRATION SECTION 8 CALIBRATION CALIBRATION This section describes calibration of a UPC. To fully calibrate the SYSTEM for output voltage and metering accuracy, it is necessary to perform a complete EXTERNALLY REFERENCED CALIBRATION. The Exterally Referenced Calibration requires NO manual adjustment or access of internal circuits. Externally Referenced Calibration achieves high calibration accuracy of the oscillator and metering circuits.
  • Page 120 SECTION 8 CALIBRATION EXTERNALLY REFERENCED CALIBRATION (cont’d) Since the UPC display can show both PROGRAM (Command) and METERED voltages, these errors will be apparent - if they occur - as a slight difference between the two voltages. Only basic metering inaccuracy will not reveal itself on the display.
  • Page 121 Operate the power source in FORM 1 to calibrate I1 (single phase). b. Operate the power source in FORM 2 to calibrate Ia and Ib (single/split phase). UPC-3 Operate the power source in FORM 1 to calibrate I1 (single phase).
  • Page 122: K Factors Display

    SECTION 8 CALIBRATION 8.2.1 K FACTORS DISPLAY The correction factors (kFactors) created during EXTERNALLY REFERENCED CALIBRATION may be displayed or modified directly, from the kFactors display screen. Activate the CALIBRATION Menu (fn, 4), press 3 and the kFactor display appears as shown below. (FORM 3 display shown).
  • Page 123: User Diagnostics

    SECTION 9 DIAGNOSTICS SECTION 9 USER DIAGNOSTICS USER DIAGNOSTICS This section is intended to aid the user in solving common problems that may occur while using the UPC. PROBLEM Incorrect or illogical operation, PROBABLE CAUSE – or program values invalid, Battery backed RAM information corrupt.
  • Page 124 SECTION 9 DIAGNOSTICS USER DIAGNOSTICS (cont’d) PROBLEM ERROR Message states PROBABLE CAUSE – RMS content of selected Waveform is not great enough to "ERROR - PROGRAMMED OUTPUT VOLTAGE produce programmed voltage, requiring more system gain VALUE EXCEEDS OUTPUT VOLTAGE RANGE. than is available.
  • Page 125 SECTION 9 DIAGNOSTICS USER DIAGNOSTICS (cont’d) PROBLEM KEYS do not respond at all. PROBABLE CAUSE – Keyboard is locked SUGGESTED CURE: Press fn and EDIT keys to unlock keyboard. Refer to section 4.6.3.10 PROBLEM UPC does not respond to the GPIB PROBABLE CAUSE –...
  • Page 126 SECTION 9 DIAGNOSTICS USER DIAGNOSTICS (cont’d) PROBLEM UPC does not respond to the RS-232, PROBABLE CAUSES – or responds with a COMMAND ERROR message. Incorrect communication parameters, i.e., Serial baud rate, parity or number of data/start/stop bits. Handshaking signals may not be wired correctly SUGGESTED CURE: Verify parameter settings match that of host computer.
  • Page 127: Serial Remote Interface Option

    5 of this Operation Manual. 10.1 GENERAL The RS-232 REMOTE interface of the UPC is the standard communication port for the UPC-3 and UPC- 1. See paragraph 10.3 for setup information. An optional GPIB/IEEE-488 parallel communication port may be installed in place of the serial port.
  • Page 128: Setup

    SECTION 10 SERIAL REMOTE INTERFACE 10.3 SETUP After installing RS-232 interface into the UPC (or after erasing all program memory or after system RESET), the RS-232 communication parameters must be set (BAUD RATE, PARITY and EOS Terminator) as follows: Press the fn key, select GENERAL SETUP then UPC STATUS. Press the EDIT key and type the desired BAUD RATE numerically, selected from the list above.
  • Page 129: Functional Exceptions

    SECTION 10 SERIAL REMOTE INTERFACE 10.4.2 FUNCTIONAL EXCEPTIONS Some functions applicable with the IEEE-488 interface are NOT applicable with the RS-232 interface. Specifically they are the following: All IEEE-488.1 interface functions (see UPC MANUAL sect. 5.6.1). IEEE-488.2 commands: *SRE and *SRE?, are ignored, as Service Requests and Serial Polls are not applicable.
  • Page 130: Testing The Rs-232 Remote Interface

    SECTION 10 SERIAL REMOTE INTERFACE 10.6 TESTING THE RS-232 REMOTE INTERFACE Connect the UPC RS-232 serial interface to a DTE serial port of a PC using a DB-25 cable. Most 25 pin connectors on PC's are DTE type. The UPC is a DCE type and must connect to a DTE port.
  • Page 131: Index

    INDEX INDEX accuracy Section 2, 37,107 damage 1-3, 23, 68 ALC 86 data 20, 26, 36, 70, 71, 77, 79, 83, 86-89, ambient 7 92, 96, 104, 113-118 amplitude data buffer 79, 97 harmonics 36, 65 DDE 92 modulation (AM) 3,17 delete 58, 83 transient 48, 60, 74 diagnostic 72, 111-114...
  • Page 132 INDEX *IDN 93 query 78-90, 92-94, 96, 98, 116 IEEE-488 70, 71, 78, 79, 90-93, 97, 98, queue 90, 93 115, 117 QYE 92 impedance 17 limit 85 Remote 20, 33, 112 programmable 67-69, 85 Interface 12-15, 70, 77, 97, 98, 115, Initial Voltage 75, 98, 114 117, 118 input...
  • Page 133 INDEX temperature 7, 69 terminator, <eos> 113, 115, 116 THD 10, 36, 65, 89 TIME Response 9, 11 Transient segment 48, 49, 82 Transition 4, 9, 67, 84, 98 transformer 8, 15, 25, 32, 44, 45, 49, 69, 71, 85 current 71, 74, 87 transient 3, 4, 9, 17, 18, 27, 29, 34, 39, 40, 48, 49, 80-83, 97, 98...
  • Page 134: Notes

    NOTES NOTES...
  • Page 135: Modifications

    MODIFCATIONS MODIFICATIONS MODIFICATIONS This section is reserved for any modifications that may be made.

This manual is also suitable for:

Upc-1

Table of Contents