EMU ALLROUNDER EMU PROFESSIONAL • • MANUAL...
Page 2
Access via web browser • Plug and Play • Designed for gas, water, head, and electricity • M-Bus to BACnet IP • M-Bus to OPC UA Suitable to the data logger EMU Electronic offers a Web-based energy monitoring solution. Web-based energy monitoring...
Your benefits: • Various locations monitored centrally • Web-based software MENU NAVIGATION • User-friendly operation • Worldwide access Go to next unit Blue key Active energy, active power etc. More information of unit E.g. phase L1, L2, L3, total, Min. / Max values Service key, on the right side bellow the red Yellow terminal cover.
Page 4
VIDEO ANIMATION COMMISSIONING / CHECK-UP You can find a video about the configuration and menu navigation on www.emuag.ch. To check for operation: • Phase rotation • Current per phase Negative energy direction • Sequence of phase (L1 L2 L3) • Current Transformer ratio •...
TECHNICAL DATA Nominal voltage U 3x230/400V (+/- 20%) Accuracy class B (1%) Nominal frequency f 50Hz, 60 Hz on request Operating temperature -25° C...+55° C Storage temperature -30° C...+70° C Clamps: IP20 Protection class Case: IP51 Mechanical: M1 Environmental class Electro-magnetic: E1 Safety class 3-phase static...
Page 6
Direct connection Installation instruction Current (I 0.02 A / 0.25 A / 0.5 A / 5 A / 75 A (5(75)) Current /5A (I 0.01 A / 0.05 A / 0.25 A / 5 A / 6 A (5(6)) Current /1A (I 0.002 A / 0.01 A / 0.05 A / 1 A / 1.2 A (1(1.2)) Torque Connection Direct...
Type: Wire (Cu) Cross-section: 35mm² DISPLAY LANGUAGE Outside-Ø: 9,55 mm Example: E-Number 105502800, available from Swiss electrical wholesale Display language can be selected between English and German (Deutsch). Blue key to Adjustments Red key to Language (Sprache) Push Service-Key briefly Cable requirement >65A Adjust Language by blue key Saving: Push Service key for 5 seconds,...
TARIFF CONTROL Tariff changeover takes place by 230V to corresponding terminal. Tarif 2 = 230V on terminal E4 and E5 (N) Double-tariff Four-tariff 0 = No voltage 1 = Voltage...
CURRENT TRANSFORMER RATIO Current transformer ratio can be adjusted from 5/5 to 20‘000/5A and 1/1 to 4’000/1A Left (blue) key = Change of digit / number Right (red) key = Go to next digit / number AABCC : adjustable in steps of 1 adjustable in steps of 1 adjustable in steps of 5 YYYY :...
Page 10
Blue key to Transformer ratio Push service key briefly Adjust secondary current by blue key Go to primary current by red key Adjust first two digits by blue key Go to next digit by red key Adjust digit by blue key Go to next digit by red key.
Page 11
(8 + 9) S0 Output = Reactive Energy Export (6 + 7) Current transformer meter 10 Impulse / kWh Direct meter 1000 Impulse / kWh EMU Allrounder The EMU Allrounder only has one pulse-output for active energy import. Default settings ex-factory...
Page 12
Blue key to Adjustments Red key to S0 Pulse Rate Push service key briefly Move decimal place by blue key Example 1000.000 = 1000 Impulse Saving: Push Service key for 5 seconds, until digits are not blinking Blue key to Adjustments Red key to S0 Pulse Duration Push service key briefly Adjust pulse length by blue key...
Page 13
Length Opto Power MOSFEET 5 – 230 VAC or VDC, max. 90mA 0.001, 0.01, 0.1, 1, 10, 100, 1000, 10‘000 Adjustable from 4 to 250 milliseconds in steps of 2 ms S0 pulse-output Rate per kWh / kvarh...
Page 14
Primary address Baud rate = 2400 Primary and secondary address, baud rate and read-out data can be configured by the free EMU MB-Connect software or by the keys. The M-Bus interface is designed according to EN 13757-2,-3 (formerly EN1434-3). Recommended cable...
Page 15
Blue key to Adjustments Red key to MBUS Primary address (or Sec.) Push service key briefly Adjust first digit by blue key Go to next digit by red key Saving: Push Service key for 5 seconds, until digit is not blinking. Blue key to Adjustments Red key to MBUS Baud rate Push service key briefly...
TCP/IP INTERFACE IP-Adresse = 192.168.1.100 Subnet = 255.255.255.0 Gateway = 0.0.0.0 Blue key to Adjustments Red key to IP Address Push service key briefly Adjust first digit by blue key Go to next digit by red key Saving: Push Service key for 5 seconds, until digits are not blinking Default settings ex-factory Configuration of IP address...
Page 17
Blue key to Adjustments Red key to Subnet Push service key briefly Adjust first digit by blue key Go to next digit by red key Saving: Push Service key for 5 seconds, until digits are not blinking Values on the TCP/IP module are updated in the following interval: Current per phase and total: second...
Page 18
By factory reset (menu point Adjustments) the TCP / IP module is set to the default settings. For a successful connection between an EMU Professional TCP / IP (not connected to network) and a computer, please consider the following points: Counter and computer must be in the same subnet.
RELAY OUTPUT The S0 pulse-outputs can be configured as a relay-output and can be switched via TCP/IP module or special M-Bus protocol. Blue key to Adjustments Red key to Assignment output X Push service key briefly Adjust to Relay Output by blue key Saving: Push Service key for 5 seconds, until digits are not blinking Configuration of relay-output...
Page 20
Threshold PEAK-CONTROL / THRESHOLD The following values can be chooses as a threshold: Active Power, Reactive power, Apparent power Current total Current per phase L1 / L2 / L3 Threshold: 5.000 kW Status: Not active The response and release time is adjustable between 0 and 9999 seconds.
Page 21
Blue key to Adjustments Red key to Assignment Output X Push service key briefly Adjust to Threshold by blue key Saving: Push Service key for 5 seconds, until digits are not blinking Red key to Unit Threshold Select desired unit by blue key Next by red key Adjust Threshold by blue key Go to next digit by red key...
Page 22
Adjust digit by blue key DATE / TIME Go to next digit by red key Saving: Push Service key for 5 seconds, until digits are not blinking Blue key to Date Push service key briefly Adjust first digit by blue key Go to next digit by red key Saving: Push service key for 5 seconds Blue key to Date...
Page 23
MAXIMUM ACTIVE POWER: MEASUREMENT PERIOD Blue key to Adjustments Red key to Measurement period Push service key briefly Adjust time by blue key Saving: Push service key for 5 seconds Blue key to Reset Register Red key to Max. Active Power Push service key briefly Set to RESET by blue key Perform reset: Push service key for 5 seconds...
Page 24
• Synchronization takes place by using a 230VAC control signal. • In normal operation mode, voltage is connected to input E1, input E2 is dead (without voltage). • To start a new measurement period, disconnect voltage from E1 and connect voltage to E2. •...
Page 25
Push service key briefly Set to RESET by blue key EMU ALLROUNDER Perform reset: Push service key for 5 seconds The EMU Allrounder has a resettable tariff register. The resettable register is indicated by and arrow above the unit (kWh). Reset power outages...
Blue key to Reset Register Rote Taste bis Active energy NO RESET ERROR MESSAGES Push service key briefly Set to RESET by blue key Perform reset: Push service key for 5 seconds If an internal error appears, an error message is dis- played.
Page 27
DATA BACKUP / POWER FAILURE • To prevent data loss in case of power failure, all relevant data are stored in non-volatile EEPROM. • This takes place if voltage is falling below a defined level. CALIBRATION PULSE / • Also automatically every 24 hours to save all relevant data CALIBRATION CONSTANT in non-volatile EEPROM.
(Mode A or C) or as a unidirectional (D0 mode) communication interface. The EMU Professional / Allrounder should only be used for measuring electrical energy and can not be operated outside the specified technical data.
The installation of the meter must be carried out by qualified and trained personnel. The EMU Professional / Allrounder is maintenance free. In case of damage (for example shipping, incorrect connection or storage) repairs may only be done by EMU Electronic AG.
Page 30
The operator / project engineer has to take care that im- proper operation / planning and malfunctions can not cause further damage. For defects or damage caused by improper use of the EMU energy meter or by not following the manual, no warranty is given.
DECLARATION OF CONFORMITY We, EMU Electronic AG, CH-6340 Baar, declare under our sole responsibility that the products: • 3-phase polyphase static meter • EMU Professional / EMU Allrounder, accuracy class B To which this declaration relates is in conformity with the...
Page 32
• • EMU Electronic AG Jöchlerweg 2 +41 (0)41 541 10 00 CH-6340 Baar support@emuag.ch Switzerland www.emuag.ch Version 1.4 | Part no. 870132...