INPUT MODULE NAM-AS3
INTRODUCTION
DESCRIPTION
The NAM-AS3 forms part of the Nittan (UK)'s
SENSORTEC-ANALOGUE range of Analogue
Addressable Devices.
This module is designed to perform a loop powered,
addressable input module function from the detection
signalling loop of an analogue-addressable fire detec-
tion system.
The NAM-AS3 may be used for a variety of purposes
such as monitoring a 'relay contact input' or monitor the
operation of a 'sprinkler flow monitoring switch'.
OPERATION
The fire alarm control equipment must be capable of
communicating with the NAM-AS3 input module. If in
doubt, check with panel manufacturer.
The NAM-AS3 is a loop powered, two-wire signalling de-
vice, it is connected onto the detection signalling loop's
SIG+ and -S wires, exactly as any other 'AS' sensor or
device.
FEATURES
* Monitoring a relay contact input.
* Monitoring the operation of a sprinkler flow switch.
NAM-AS3 Input Module is made up as
follows:-
1 x Metal enclosure c/w 20mm knockouts
1 x NAM-AS3 PCB c/w internal plastic PCB enclosure
with hinged lid.
1 x Earth point (on lid)
1 x Earth point (inside of enclosure)
1 x 200mm Earth Strap
1 x Label inside lid for product identification and
device address identification.
www.acornfiresecurity.com
NAM-AS3 LOOP POWERED
INPUT MODULE
INSTALLATION & TECHNICAL
MANUAL
www.acornfiresecurity.com
No:
DATE:
PAGE:
SENSORTEC-ANALOGUE FAMILY:-
SENSORS:-
ST-I-AS - Analogue Ionisation Smoke Sensor
ST-P-AS - Analogue Photoelectric Smoke Sensor
ST-H-AS - Analogue Heat Sensor
STB-4 - Standard Base for above sensors
DEVICES:-
ST-NCP-AS - Addressable Call Point
BACK BOX - Back Box for ST-NCP-AS
MCM-AS4 - Zone Monitor/Control Unit
SCM-AS4- Addressable Sounder Control Module
NAM-AS3 - Addressable Input Module
OCM-AS3 - Output Control Module
SCI-5 - Base mounted Short Circuit Isolator
SCI-6 - Plate mounted Short Circuit Isolator
1-Gang Box - Single gang box for SCI-6
ADDRESSABLE SOUNDERS:-
VCT-03-AS-NB - Addressable Wall Sounder
c/w Vector Plate/Cap (R = Red, W = White Plate/Cap).
VCT-03-CP(W) - Spare Vector Plate/Cap (White)
VCT-03-CP(R) - Spare Vector Plate/Cap (Red)
VCT-03-NT-AS - Addressable Sounder c/w STB-4 Base
pre-wired to the sounder.
VPR-SA2-NTAS - Addressable Sounder, IP65 rated,
wall mounted.
NISM/NAMAS3/02
OCTOBER 2006
ISSUE:
02
1
of 9

Advertisement

loading

Summary of Contents for Nittan NAM-AS3

  • Page 1 ST-NCP-AS - Addressable Call Point BACK BOX - Back Box for ST-NCP-AS The NAM-AS3 may be used for a variety of purposes MCM-AS4 - Zone Monitor/Control Unit such as monitoring a 'relay contact input' or monitor the SCM-AS4- Addressable Sounder Control Module operation of a 'sprinkler flow monitoring switch'.
  • Page 2 Using the template on page 5 of this manual, mark and drill the main enclosure screw positions in the wall. c) Position the NAM-AS3 enclosure to the wall and screw the 4 x fixing screws through the rear of the enclosure.
  • Page 3: Side View

    ENCLOSURE FIXING SCREW 20.0mm PLK1 KNOCKOUTS LED INDICATIONS DIL/Address COMMS TRIGGERED Setting Switch NITTAN (UK) LTD - NAM-AS3 2 X LOWER PCB ENCLOSURE FIXING SCREWS PCB & PCB/ CABLE TERMINALS ENCLOSURE TOP VIEW WITH LID REMOVED SIDE VIEW 1 20.0mm...
  • Page 4 NISM/NAMAS3/02 NAM-AS3 LOOP POWERED INPUT MODULE DATE: OCTOBER 2006 INSTALLATION & TECHNICAL PAGE: ISSUE: MANUAL of 9 ENCLOSURE OUTER DIMENSIONS 130mm 44mm 163mm 20.0mm NOT TO SCALE www.acornfiresecurity.com...
  • Page 5 NISM/NAMAS3/02 NAM-AS3 LOOP POWERED INPUT MODULE DATE: OCTOBER 2006 INSTALLATION & TECHNICAL PAGE: ISSUE: MANUAL of 9 ENCLOSURE DIMENSIONS (INTERNAL MOUNTING HOLES) 110mm 4.0mm 20.0mm NOT TO SCALE www.acornfiresecurity.com...
  • Page 6 NISM/NAMAS3/02 NAM-AS3 LOOP POWERED INPUT MODULE DATE: OCTOBER 2006 INSTALLATION & TECHNICAL PAGE: ISSUE: MANUAL of 9 ENCLOSURE MOUNTING TEMPLATE www.acornfiresecurity.com...
  • Page 7 INPUT MODULE DATE: OCTOBER 2006 INSTALLATION & TECHNICAL PAGE: ISSUE: MANUAL of 9 ENCLOSURE (INTERNAL ASSEMBLY DIMENSIONS) 48mm PLK1 LED INDICATIONS DIL/Address COMMS TRIGGERED Setting Switch NITTAN (UK) LTD - NAM-AS3 30mm 30mm 22mm 22mm 20.0mm 163mm NOT TO SCALE www.acornfiresecurity.com...
  • Page 8 9 CONNECTION WIRING DETAILS NAM-AS3 N/O FIRE CONTACT LOOP WIRING Screen SIG+ CONNECTION DETAILS (PCB) AND ADDRESS SETTING ADDRESS SETTING CONNECTIONS TO NAM-AS3 PCB = ON = OFF Address: PLK1 LED INDICATIONS DIL/Address COMMS TRIGGERED Setting Switch Example address switch is set to 37 Decimal .
  • Page 9 Loop Powered, No external PSU required. LED Indications:- On Board LED Indication Red 'COMMS.' LED:- ('Pulses' when polled). Red 'TRIGGERED' LED:- ('Pulses' when NAM-AS3 Operate's. Note: 'COMMS' & 'TRIGGERED' LEDs both 'Pulse' simultaneously when the NAM-AS3 operates). General Specifications:- Mass 50g (PCB only).
  • Page 10 www.acornfiresecurity.com Document No.: NISM/NAMAS3/02 Date: OCTOBER 2006 Pages: 10 inc. cover. SENSORTEC..comes www.acornfiresecurity.com...