PowerGATE™ Emergency Lighting Transfer Switch Introduction – This manual details the installation and use of your Lex Emergency Lighting Transfer Switch. Before installation read this manual in its entirety. Store this manual in a safe location for future reference. – How to use this manual: •...
Page 4
Emergency 3Ø Supply (Main version only) Monitored Normal 3Ø Supply Controller Supply Fuses Voltage Dropout Adjustment Programmable Logic Controller Transfer Relays Auxiliary, Fire Alarm & Generator Start Circuits from Dimmers To Load Circuits 20A Type J Fuses Contact Lex Products: 800.643.4460 info@lexproducts.com...
Page 5
• Tighten anything that has come loose • If it can’t be tightened or if something is broken, contact Lex Technical Services at 800.643.4460 5. For any of the above issues, or any other concerns, call Lex Customer Service at 800.643.4460...
• Choose a location where it will be the most likely to be secure from damage from fire, flood, or other conditions and incidents that will require its used • If there are any doubts about about a location’s suitability, contact Lex Technical Services – Do not install the cabinet inside any other electrical or confined enclosure provided •...
• Control, normal power sensing and options connect within the areas noted in the example diagram above – Do not run the control, normal power sensing, or option conductors in the same conduit used for the emergency power conductors Contact Lex Products: 800.643.4460 info@lexproducts.com...
– The output load terminal block is on the right side of the cabinet. – Connect the load conductors to the 120V Load terminal block – The terminal blocks support the following wire sizes: Wire Size Torque #22 - #10 AWG 25 lbs-in Contact Lex Products: 800.643.4460 info@lexproducts.com...
Page 9
– To connect the Generator Start signal wires, first locate the terminal block marked GEN, AUX, FA on the right side of the panel • Connect your generator control conductors to the terminals marked GEN – NOTE: Refer to your generator installation manual for start circuit wiring details Contact Lex Products: 800.643.4460 info@lexproducts.com...
4. Once the circuit transfer contactors for the normal power have latched and the green indicator lamp is illuminated, apply normal power and emergency power to the system 5. Test the system using the test key. Contact Lex Products: 800.643.4460 info@lexproducts.com...
Page 11
Technical Services Team – Lex Products is available to help answer any installation or operation inquiries – If you have questions, need technical advice or have suggestions regarding this product, please contact us at 800.643.4460 or email us at info@lexproducts.com...
Page 12
Suite Q 800.643.4460 05-30 All Rights Reserved. 203.363.3738 Pacoima CA 91331 203.363.3742 Fax 818.768.4474 WE DELIVER THE POWER Lex Products logo and lexproducts.com are 818.768.4040 Fax trademarks or registered trademarks of Lex Products in the United States, other countries, or both.