2.0 Key Features 2.1 Case The Setra LITE Construction Kit comes in a convenient easy to carry case which is designed for the most rugged applications but still compact enough to provide pressure monitoring in a minimally invasive footprint (12” x 15” x 7”). The case is IP67 (NEMA 6) rated and includes auto venting for air travel.
Page 3
2.2 Case contents Inside the case is everything needed to set up differential pressure monitoring of your space. Details of the case contents are listed in the image below: Spare tools and accessories pocket included with calibration certificate. Pluggable AC power pack with interchangeable adapters for worldwide electrical outlets and 5 ft power cord.
3.0 Unit set up 3.1 Power Remove pluggable AC power pack from the case and snap on the plug adapter needed for your location (USA/UK/EU/Canada/Mexico/Asia). The adapters can be switched out with the quick release button on the power pack as seen in Image 1. Connect the adapter to the outer side of the case via the power jack as shown in Image 2.
Page 5
Pressure Sensing Tubing Remove the pressure sensing tubing from the case. One end of the tubing has the sintered filter to be placed inside the pressurized space and the other end has the connection for the Quick Disconnect Tubing Port. Connect to the Quick Disconnect Tubing Power as shown in Image 1.
Page 6
3.3 Monitor Interface With power connected, silicon tubing in place and power switch in the upward position, the unit will begin sensing the differential pressure between the case environment and the isolation area immediately. In order to set up the visual green / red alarming and set up the desired monitoring features proceed with the following steps: 3.4 Removal With the unit powered on, grab the lens by the left and right edge, then pull away from the unit.
3.5 Configuration menus This section will describe the function of each of the configuration menus. 3.5.1 Zero Press and hold the RIGHT button (“”) to zero the onboard pressure sensor. The unit contains an onboard valve to automatically equalize the pressure differential across the sensor. Zeroing is complete when the screen reads "ZERO DONE".
Page 8
Press and hold the RIGHT button (“”) to adjust the alarm door delay (i.e. number of seconds before the LED ring will turn red when pressure alarm limits are exceed); the screen text will flash 3 times to indicate that the setting is ready to be adjusted. Use the LEFT ("") and MIDDLE ("") buttons to adjust between 000 and 999 seconds.
Page 9
3.5.6 Digits Press and hold the RIGHT button (“”) to adjust the number of decimal places displayed on the LCD screen; the screen text will flash 3 times to indicate that the setting is ready to be adjusted. Use the LEFT ("") and MIDDLE ("") buttons to adjust between 0 ("0.000"), tenths ("0.000"), hundredths ("0.000"), or thousandths ("0.000").
Page 10
3.5.9 Units Press and hold the RIGHT button (“”) to adjust the measuring units used for the digital display and alarm thresholds; the screen text will flash 3 times to indicate that the setting is ready to be adjusted. Use the LEFT ("") and MIDDLE ("") buttons to adjust between pascals ("Pa") and inches of water ("WC").
Page 11
3.6 Monitor Signal Out The differential pressure signal can be transmitted via analog output to any central monitoring system or BAS (building automation system) if desired. Simply connect to the terminals provided on the outer side of the case as shown in Image 1. The user can select the desired analog output: 4-20 mA, 0-5V, or 0-10V via the monitor menu as described below: Note: If the monitoring signal out is being used, the battery life will be closer to 10 hrs.
No representative or person is authorized to give any warranty other than as set out above or to assume for SETRA any other liability in connection with the sale of its products. For all CE technical questions, contact Setra Systems, USA. EU customers may contact our EU representative Hengstler GmbH, Uhlandstr 49, 78554 Aldingen, Germany (Tel: +49-7424-890; Fax: +49-7424-89500).