OUTPUT TRANSDUCERS
UNIVERSAL SEQUENCER CONTROL MODULE
MODEL UCS-621
DESCRIPTION
The Model UCS-621 is a solid-state device used for
multi-stage control in HVAC systems, sequencing boil-
ers or chillers, or floating control of VAV boxes from a
single analog signal. The UCS-621 can be used to
obtain a digital output from a voltage or current produc-
ing sensor. The UCS-621 is supplied with mounting
track for easy installation.
FEATURES
• 6 stages of relay control
• Voltage or current input
• 24 VAC or 24 VDC power
• LED indication of relay status
• Adjustable relay setpoints
• Adjustable relay differentials
• Snap-track mounted
OPERATION
The UCS-621 accepts a 0.5-20 mA or 0.375-15 VDC
signal to produce up to six stages of relay output. Each
relay has a multi-turn potentiometer adjustment to set
the pull-in point. Each of the six relays is jumper-selec-
table to pull in on either a rise or fall in signal. Individual
relay differential is easily adjusted by using different
value plug-in differential resistors. The UCS-621 consid-
ers an input signal below 0.5 mA or 0.375 V to be a loss
of signal and all relays will de-energize.
SPECIFICATIONS
Supply voltage
Input signal
Output
Relay rating
Accuracy & repeatability ±1%
Setpoint adjustment
Input impedance
KELE & ASSOCIATES • P O Box 34817 • Memphis, TN 38184
24 VAC ±10% @ 300 mA
24 VDC ±10% @ 150 mA
0.5-20 mA or 0.375-15 VDC
jumper-selectable
6 SPDT relays
5A @ 120 VAC
25-turn potentiometers
250 ½ (mA input),
30 k½ (V input)
DIMENSIONS
in
(cm)
1
2
3
1
2
1
3
2
4
3
5
4
6
5
6
SIG
(15.24)
Operating temp range
Humidity limit
Dimensions
Relay differential
Weight
901-937-4900 • FAX 901-372-2531 • E-mail info@kele.com
4
5
6
V
MA
6.0
32° to 158°F (0° to 70°C)
5-95% RH noncondensing
3.25"H x 6.0"W x 1.375"D
(8.25 cm x 15.24 cm x 3.49 cm)
0.5 mA or 0.375V
(adjustable by plug-in
differential resistors - see
wiring diagram)
0.7 lb (0.32 kg)
3.25
(8.25)

Advertisement

loading
Need help?

Need help?

Do you have a question about the UCS-621 and is the answer not in the manual?

Questions and answers

Summary of Contents for Kele UCS-621

  • Page 1 Setpoint adjustment 25-turn potentiometers Weight 0.7 lb (0.32 kg) 250 ½ (mA input), Input impedance 30 k½ (V input) KELE & ASSOCIATES • P O Box 34817 • Memphis, TN 38184 901-937-4900 • FAX 901-372-2531 • E-mail info@kele.com...
  • Page 2 Make all connections according to the diagram below or as shown on the job diagrams and in compliance with national and local codes. Make all connections with power removed. Failure to do so could result in circuit board damage. Use shielded #18-gauge cable for connections from the UCS-621 to the controller, shield grounded at the controller. TO CONTROLLED DEVICES...