Before connecting the burner to the gas supply, insure that the gas pipes and service
meter are large enough to permit the additional load of the gas burner (see Table 3).
Table 3: Pipe Capacity Table*( x 1,000 BTU's)
Pipe Length**
15'
30'
45'
60'
75'
90'
105'
120'
150'
180'
* Using 0.6 Specific Gravity Gas and a Pressure Drop of 0.3" of Water Column
0
** Each 90
elbow counts as 3' for the purpose of these calculations
Example 1:
There is 75 feet of 1 ¼" pipe from the meter to the burner and there are 5 elbows.
(5 elbows X 3') + 75' pipe = 15' + 75' = 90' of effective pipe length
The maximum BTU that can be fired is 310,000 BTU (see Table 3)
It is advisable to run a separate gas line from the meter to the gas burner to avoid
pressure drops. Refer to the above Pipe Capacity table for the correct sizes.
MUST CONFORM WITH LOCAL CODES.
fittings (do not use cast iron parts) with a suitable pipe dope which is resistant to liquefied
petroleum gases.
Piping should consist of:
1. A shut off valve approximately 6' away from the unit.
2. A 1/8" plugged NPT tapping for gas pressure measurement preferably on the manual shut
off valve (as shown or anywhere between the gas valve and the shut off value).
Note: The manual shut off valve and tapping are NOT part of the SU-4 Gas Burner.
Please make sure you conform to local and state codes.
3. A gas union.
4. A drip pipe.
Caution: The gas valve should not be subjected to more than ½" PSIG. Therefore, the
burner should be isolated during high-pressure gas leak tests. The appliance and its
individual shut off valve must be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in excess of ½ psig. The appliance
must be isolated from the gas supply piping by closing its individual manual shut off
valve during any pressure testing of the gas supply piping system at test pressures equal
to or less than ½ psig.
.

Gas Service and Pipe Capacity

Nominal diameter of pipe in inches
1"
1 ¼"
345
750
241
535
199
435
173
380
155
345
141
310
131
285
120
270
109
242
100
225
Gas Piping to the Burner
1 ½"
850
700
610
545
490
450
380
300
225
Use black steel pipe and malleable
6
2"
920
850
780
720
ALL PIPING