Inca PSJ2 User Manual

Pressure controller

Advertisement

Quick Links

INCA
CONTROL PTY LTD
UNIT 14/62 OWEN ST
GLENDENNING NSW 2761
Design & Manufacture of:
Custom-built switchboards
Electronic control equipment
AC/DC pumping controls
Installation & service
INCA MODEL
PSJ2
PRESSURE
CONTROLLER
USER MANUAL
Inca Reference PSJ2
Software Version 1.0
Technical Support
Pumps & Mechanicals –
Controls – Inca Control & Engineering Pty Ltd
Phone 02 9632 2837
Phone:
(02) 9675 3815
Fax:
(02) 9675 1381
Email:
sales@incacontrol.com.au
Web:
www.incacontrol.com.au
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PSJ2 and is the answer not in the manual?

Questions and answers

Summary of Contents for Inca PSJ2

  • Page 1 Electronic control equipment AC/DC pumping controls Installation & service INCA MODEL PSJ2 PRESSURE CONTROLLER USER MANUAL Inca Reference PSJ2 Software Version 1.0 Technical Support Pumps & Mechanicals – Controls – Inca Control & Engineering Pty Ltd Phone 02 9632 2837...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS Control Panel Overview………………………………………………. Features………………………………………………………… Description……………………………………………………... Installation…………………………………………………………….. Mechanical installation………………………………………… Sensor installation……………………………………………… Electrical installation…………………………………………… Maintenance…………………………………………………….. Start- up………………………………………………………………… Notes on value entry…………………………………………... Power up display………………………………………………. Screen display layout………………………………………….. Calibration……………………………………………………………. Setting low pressure shutdown…………………………………. Setting low pressure time delay………………………………… Setting high pressure shutdown……………………………….. Setting high pressure time delay………………………………..
  • Page 3: Control Panel Overview

    Control Panel Overview Features  JAZZ HMIPLC with user friendly setup & display  Display of system pressure  Low & high pressure pump shutdown with reset button  Low level pump shutdown with automatic reset  Manual/off/auto selectors on JAZZ Face ...
  • Page 4: Installation

    Locate the pressure transducer in the discharge pipe work as close as practical to the control panel. Electrical Installation Note: All cable entries must enter via the bottom of the cabinet. If cables are entered via the roof Inca Control Pty Ltd reserve the right to withdraw warranty because of the possibility of shaving entering sensitive electronic equipment.
  • Page 5: Start Up

    Start up Notes on Value Entry When entering a numeric value, the cursor can be backspaced to correct mistakes by pressing the LEFT ARROW button. Decimal points can only be entered on entries with decimal points in the display line. The decimal point is entered by pressing the +/- .
  • Page 6: Calibration

    Calibration The calibration of the controller is carried out on pages accessed by pressing & holding in the RIGHT ARROW Button for 5seconds. The first calibration page will appear. You can move through the calibration pages by pressing the RETURN ARROW button & then the RIGHT ARROW button to move on. Continuing this process will move you through the pages with out making any changes.
  • Page 7: Pressure Sensor Calibration

    Pressure Sensor Calibration Calibrate Sensor will now be displayed. The Cursor will be flashing under the first digit of the CALIBRATE SENSOR setting. Simply type in the 20mA scale of the pressure transducer to be used, example 1000kPa (10bar) Press 1, Press 0, press 0, press 0 & then press Return Arrow button.
  • Page 8: Operation

    Operation 5.1 System Operation The system is designed to maintain a pressure in the discharge line of a pumping system relating to the settings entered by the operator. The pump will start when the pressure falls to the duty start set point & will run until the pump stop set point is reached If the pressure continues to fall &...
  • Page 9: Trouble Shooting

    Trouble Shooting Condition Do This 1. Unit does not power up. Check that power supply is on to panel and isolator is on. Check that control circuit breaker is on. 2. PLC Controller does not power up Check that 24VDC power supply is operating, & power is on.
  • Page 10: Controller Settings Sheet

    Controller settings sheet User Setting Parameter Description Factory settings Low pressure Pressure at which pumps are Shutdown shutdown for low discharge pressure 100kPa Low pressure Timer Time delay before pump shuts down 5sec High pressure Pressure at which pumps are Shutdown shutdown for high discharge pressure 600kPa...
  • Page 11: Warranty Statement

    In addition to the above, equipment manufactured, installed & commissioned by Inca Control Pty Ltd, within the Sydney Metropolitan Area, includes onsite replacement. In any event Inca Control Pty Ltd has no other obligation or liability beyond replacement or repair of this product. NOTES:...