Summary of Contents for Water Furnace ENVISION 2 NKW Series
Page 1
NKW 30 TO 150 KW Commercial Reversible Chiller - 50 Hz Submittal Data English Language IP/Metric Units SD2552WNB 09/16...
Page 2
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Model Nomenclature 10 11 14-15 Vintage Vintage Model Type * – Factory Use * – Factory Use NKW – Envision nvision Series eries 50 Hz Reversible Chiller 0 Hz R evers rsible Chiller Non-Standard Options...
Page 3
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: HydroLink Supervisory Control Box Nomenclature 9-10 Family Vintage HSC – HydroLink Supervisory Control * - Internal Factory Use Only Voltage Non-Standard Option Details SS – Standard Option HydroLink Control Future A –...
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: EN 14511-2 2011 Ratings NKW Envision2 Heat Pump Heating Performance Data EN 14511-2 2011 B0/W35 W10/W35 B0/W45 B5/W35 W10/W45 Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Model Output...
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Physical Dimensions Dimensional Data Dimensional Data for unit with enclosure Model 120-180 240-360 WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi...
Page 6
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Physical Dimensions. cont. Dimensional Data Dimensional Data for unit with enclosure Model 120-180 240-360 WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi...
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Vibration Isolators Rubber Isolators Part Color Max Load, 8.64 14.2 Type Deflection, mm Number Code 99S502-01 Green 12.7 • Compatible with 030-045 60.5 85.9 Part Color Max Load, Type Deflection, mm Number...
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Reference Calculations Heating Calculations: Cooling Calculations: LWT = EWT - LWT = EWT + L/S x 4.2* L/S x 4.2* NOTE: * When using water. Use 4.1 for 15% methanol/water or Environol solution. Legend ABBREVIATIONS AND DEFINITIONS: COP = coefficient of performance...
Page 11
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Antifreeze Correction Catalog performance can be corrected for antifreeze use. Please use the following table and note the example given. Heating Cooling Antifreeze % Pressure Antifreeze Type by wt Drop Load Source...
Page 25
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Wiring Schematics cont. Reversible Chiller HydroLink Aurora 150 Series Legend CPM1 Black 72A CC-A Black (68) Factory Low voltage wi ri ng Thermistor Factory Line vol tage wiring Black (71A) Fi eld l ow voltage wiring...
Page 26
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Wiring Schematics cont. Reversible Chiller HydroLink Aurora 150 Series Black/White (99) Yellow (100) Compressor Compressor Prote c on Prote c on M odule #1 M odule #2 (CPM1) (CPM2) Unit Power Supply Di sconne ct (fus ed disc onne ct op ona l)
Page 27
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Wiring Schematics cont. HydroLink Aurora Control NET+ NET- NET+ NET- WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi...
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Engineering Guide Specifi cations PART 1 - GENERAL Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components SUMMARY of chillers that fails in materials or workmanship within The liquid source, water-to-water heat pump shall be specified warranty period.
Page 29
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Engineering Guide Specifi cations cont. Heat Exchangers: Controls: The water to refrigerant heat exchangers shall be The unit shall be controlled using a microprocessor dual circuit, copper-brazed 316 stainless steel channel which sequences all functions and modes of operations.
Page 30
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: PART 3 - EXECUTION Evaporator Fluid Connections: Connect to evaporator inlet with shutoff valve, strainer, flexible connector, thermometer, CHILLER INSTALLATION and plugged tee with pressure gage. Connect to evaporator Install chillers on support structure indicated.
Page 31
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Notes WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi...
ENVISION Contractor: P.O.: REVERSIBLE CHILLER - 50Hz Engineer: Project Name: Unit Tag: Revision Guide Pages: Description: Date: Removed FX10 Control Option, Added HydroLink Aurora Controls 25 Aug 2016 Added Energy Labelling 18 Mar 2016 Inserted Updated MCS/KIWA Logo 14 Oct 2015 First Published 06 Nov 2014 All Envision2 Series 50Hz product is safety tested to CE standards and...