Recessed stainless steel dialysis box with backflow preventer, trap primer, thermostatic mixing valve and waste

Advertisement

Quick Links

INSTALLATION, OPERATION & MAINTENANCE MANUAL 8194
®
Model 8194
RECESSED STAINLESS STEEL DIALYSIS
BOX WITH BACKFLOW PREVENTER, TRAP
PRIMER, THERMOSTATIC MIXING VALVE
AND WASTE
Important: Some options may slightly alter installation. To ensure proper installation review the
manual thoroughly and verify rough-ins before beginning any work. File this manual with the
owner or maintenance personnel upon completion of installation.
MGI Engineered Plumbing Products are designed in accord with applicable National Codes and
Standards, which may include UPC, ANSI, and ASSE. Installers should use industry standard
practice for details not covered within Manual. Prior to installation, supply lines must be flushed of
all foreign material such as pipe dope, chips, or solder. Debris or foreign material in water supply
may damage valve. An appropriate thread sealant is recommended on all threaded waste and
supply connections to reduce the possibility of leaks.
Industry standard wall backing, for wall hung fixtures, is required. Installer provided wall anchors
and wall anchoring hardware must be appropriate for wall construction and have a minimum pull-
out rating of 1000 lbs. (453.6 kg).
ANSI, UFAS or ADA compliance is subject to the interpretation and requirements of the local code
authority and is the responsibility of the installer for verification.
Electrical receptacle(s) must be wired to a GFCI protected circuit. Fixture must be earth grounded
per N.E.C. (National Electrical Code).
Go to
www.whitehallmfg.com
Whitehall Manufacturing Company warrants that its products are free from defects in material or workmanship under normal use
and service for a period of one year from date of shipment. Whitehall's liability under this warranty shall be discharged solely by
replacement or repair of defective material, provided Whitehall is notified in writing within one year from date of shipment, F.O.B.
Industry, California.
This warranty does not cover installation or labor charges, and does not apply to materials which have been damaged by
other causes such as mishandling or improper care or abnormal use. The repair or replacement of the defective materials
shall constitute the sole remedy of the Buyer and the sole remedy of Whitehall under this warranty. Whitehall shall not be liable
under any circumstances for incidental, consequential or direct charges caused by defects in the materials, or any delay in the
repair or replacement thereof. This warranty is in lieu of all other warranties expressed or implied. Product maintenance instructions
are issued with each fixture, and disregard or non-compliance with these instructions will constitute an abnormal use condition and
void the warranty. If you have any questions or require technical assistance, please call 800-743-8219.
NOTICE TO KEEP ORIGINAL PACKAGING- Regarding warranty claims: customer must retain original packaging for one year
upon receipt of product. If packaging is discarded, it is the customer's responsibility to provide adequate packaging. Any shipping
claims that are a direct result of customer-provided packaging materials will be handled by the shipper.
6900-217-001 Revised: 03/18/21
WARRANTY INFORMATION
to fill out eWarranty Registration, keyword search: WARRANTY.

Advertisement

loading

Summary of Contents for Whitehall 8194

  • Page 1 Whitehall Manufacturing Company warrants that its products are free from defects in material or workmanship under normal use and service for a period of one year from date of shipment. Whitehall's liability under this warranty shall be discharged solely by replacement or repair of defective material, provided Whitehall is notified in writing within one year from date of shipment, F.O.B.
  • Page 2: Technical Detail

    Thermostatic Mixing Valve is certified for the following: NSF/ANSI 61 ASSE 1070 Certified CSA B125.70 WHITEHALL MANUFACTURING • P .O. BOX 3527 • City of Industry, CA 91744-0527 U.S.A Phone (800) 782-7706 • (626) 968-6681 • Fax (626) 855-4862 • Web: www.whitehallmfg.com...
  • Page 3 NCT COLD WATER SUPPLY, AND TO 2” IPS (2-3/8” OD) WASTE OUTLET. TEST FIXTURE FOR LEAKS AND OPERATION. WHITEHALL MANUFACTURING • P .O. BOX 3527 • City of Industry, CA 91744-0527 U.S.A Phone (800) 782-7706 • (626) 968-6681 • Fax (626) 855-4862 • Web: www.whitehallmfg.com...
  • Page 4: Operation And Maintenance

    Ÿ Ensure you have a proper connection from the dialysis machine supply hose and the male hose thread connection on the 8194, prior to opening the second valve on the backflow preventer. Ÿ Fold the drip tray (7) down to help eliminate any spills onto cabinetry or finished surfaces from the dialysis machine discharge line.
  • Page 5: Parts Breakdown

    5. Re-check temperature. 5/8" WRENCH LOCKNUT ADJUSTMENT STEM DETAIL B DETAIL C WHITEHALL MANUFACTURING • P .O. BOX 3527 • City of Industry, CA 91744-0527 U.S.A Phone (800) 782-7706 • (626) 968-6681 • Fax (626) 855-4862 • Web: www.whitehallmfg.com...