(Remember, this also decreases the maximum output by the same amount.)
Step 7) Final Adjustments
If you require a current input, set the "J1" IN jumper shunt in the "I" position. Check operation of the ASA for
desired signal rescaling and operation.
PRODUCT SPECIFICATIONS
NON-SPECIFIC INFORMATION
Supply Voltage:
Supply Current:
Input Voltage Signal Range (@
Impedance):
Input Current Signal Range (@
Impedance):
Input Resistance Signal Range:
Output Voltage Signal Range:
Output Voltage Signal O set:
Output Voltage Signal Gain:
Output Load Impedance:
Output Signal O set (Jumper
Selectable):
Input-Output Tracking Accuracy:
Power Range:
Connections:
Wire Size:
Terminal Block Torque Rating:
Operating Temperature Range:
Operating Humidity Range:
Storage Temperature:
WARRANTY
The ASA Series is covered by ACI's Two (2) Year Limited Warranty, which is located in the front of ACI'S SENSORS &
TRANSMITTERS CATALOG or can be found on ACI's website: www.workaci.com.
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling
centre. Do not dispose of with household waste. Do not burn.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
24 VAC +10%/-5% (0-20 VDC out), 24 VDC +/- 10% (0-18 VDC out) 25-30 VDC (0-20 VDC out)
50A nominal with no load, 2.05A maximum (Dependent on Load Impedance)
0 to 20 VDC @ 200,000
0 to 44 mA @ 250
0 to 500,000
0 to 20 VDC
+/- 0 to 20 VDC
1-20 times (output can't exceed 20 VDC)
10 minimum
Zero O set, Positive O set, Negative O set
+/- 2% Full Scale Output
2A or 30 Watts maximum
45° Captive screw Terminal Blocks
12 (3.31 mm ) to 22 AWG (0.33 mm )
0.5 Nm (Minimum); 0.6 Nm (Maximum)
-40 to 150°F (-40 to 65°C)
5 to 95% non-condensing
-40 to 150°F (-28.9 to 65.5°C)
Page 4
Version: 6.0
I0000602