EGS Sola Hevi Duty MCR Installation And Operation Manual

EGS Sola Hevi Duty MCR Installation And Operation Manual

50 hz mini/micro computer regulator

Advertisement

Quick Links

50 Hz Mini/Micro Computer Regulator (MCR)
Installation and Operation Manual
Operating & Service Instructions
Sola Minicomputer Regulators
UL White Card Listed – Power Supply Classification
CSA Certified – Transformer Classification
General Description and Specifications
The Sola Micro/Minicomputer Regulator (MCR) provide
virtually instantaneous voltage regulation, and isolation from
both transverse and common mode noises for any type
of load. It also suppresses transients with ferroresonant,
protects overloads, and serves as a dedicated line. It is the
ultimate in AC power conditioning equipment.
Operating Temperature Range: -20° to +50°C.
Phase: Single
Input Voltage and Frequency: See Table 3
Output Voltage and Frequency: 110/120/220/240 VAC
Output Voltage Regulation: +3% for an input line variation of
+15%
Output Harmonic Distortion: Less than 3% total RMS content at
full load.
Efficiency: 85% or 90% at full load typical. No loss of output for
line loss of 3 msec.
Noise Reduction: Common mode noise rejection exceeds 120dB.
Transverse noise rejection exceeds 60dB.
Voltage Surge Suppression: Meets
ANSI/IEEE C62.41
Category A and B waveforms
(formerly IEEE 587-1980).
Primary Voltage
Interconnect
220-240
H2 to H3
380-415
H2 to H3
Secondary Voltage
Interconnect
110
120
220
240
MCR 50 Hz 10000 - 15000 VA
Table 3
VA
Voltage Input
Voltage Output
120
110, 120, 220, 240, 380, 415
110, 120, 220, 240
250
110, 120, 220, 240, 380, 415
110, 120, 220, 240
500
110, 120, 220, 240, 380, 415
110, 120, 220, 240
1000
110, 120, 220, 240, 380, 415
110, 120, 220, 240
2000
110, 120, 220, 240, 380, 415
110, 120, 220, 240
3000
110, 120, 220, 240, 380, 415
110, 120, 220, 240
5000
110, 120, 220, 240, 380, 415
110, 120, 220, 240
7500
220, 240, 380, 415
110, 120, 220, 240
10000
220, 240, 380, 415
110, 120, 220, 240
15000
220, 240, 380, 415
110, 120, 220, 240

Installation

All regulators generate considerable heat and depend on the
natural draft air circulation for adequate cooling.
It is important that ventilation openings not be obstructed.
Mounting in a confined or poorly ventilated space should be
avoided unless special provisions have been made
for ventilation.

Hard-Wired Voltage Regulators

Hard-wired voltage regulators vary in size according to the
output power and may be mounted in either a horizontal or
vertical position. If mounted in a vertical position (on a wall,
for example), steel mounting hardware must be selected in
accordance with Table 1 for a secure installation. The wiring
compartment should be at the top. Regardless of position,
the regulator should be located where contact with the hot
surface of the transformer is unlikely.
For proper ventilation, allow a minimum of 12 inches of
clearance above the unit and a minimum of 6 inches of
clearance on each side. Dimensions of the regulators and
the morning brackets are presented in Figures 1, 2, 3, and 4.
The specifications for the figures are listed in Table 3.
Table 1: Bolt Sizes
Rated VA of Regulator
125/250
500/1000
1500 to 10000
150000
1
Figure 1:
Outline
Drawing 1
Figure 2:
Outline
Drawing 2
4
Table 2: Wire and Jumper Configurations
Connect Lines To
H1 & H4
Unit (VA)
H1 & H5
250 to 5000
Connect Lines To
X1 & X2 or X3 & X2
X4 & X2 or X5 & X2
X1 & X3
7500
X4 & X5
10000 to 15000
Catalog
OD
Dim.
Dim.
Dim.
Number
A
B
C
(cm)
(cm)
(cm)
63-23-612-8
A
23,11
18,90
11,43
63-23-625-8
A
26,92
18,90
11,43
63-23-650-8
A
33,66
16,21
19,69
63-23-710-8
A
45,57
16,21
19,69
63-23-720-8
B
44,65
23,72
26,82
63-23-730-8
B
67,72
23,81
26,90
63-23-750-8
B
76,20
23,81
26,90
63-23-775-8
C
71,12
23,81
62,23
63-23-810-8
C
76,20
23,81
62,23
63-28-815-8
D
76,20
23,81
91,44
7
Minimum Recommended Size
of Steel Mounting Hardware
M6
M7
M8
M12
Figure 3:
Outline
Drawing 3
Figure 4:
Outline
Drawing 4
Input
Jumper
Input Volts
Terminals
Connection
Connection
(H1-H3)
90-130
H1-H4
(H2-H4)
180-260
H1-H4
(H2-H3)
(All Models)
110-X1-X2 or
310-450
H1-H5
(H2-H3)
120 X4-X2 or
(H1-H3)
180-260
H1-H5
(H2-H5)
310-450
H1-H4
(H2-H3)
180-260
H1-H4
(H2-H3)
H1-H5
(H2-H3)
Dimensions
Approx.
Shipping
Dim.
Dim.
Dim.
Dim.
Weight
Dim. H
D
E
F
G
(kg)
(cm)
(cm)
(cm)
(cm)
(cm)
13,67
12,07
10,48
5,53
0,79 X 1,75
8,08
13,67
12,07
10,48
5,53
0,79 X 1,75
12,24
22.86
20,64
14,30
9,12
0,79 X 2,06
18,14
22,86
20,64
14,30
14,83
0,79 X 2,06
28,12
32,38
29,84
10,69
12,70
1,12 X 1,75
50,81
32,38
29,84
15,39
9,29
1,12 X 1,75
72,59
32,38
29,84
23,79
9,37
1,12 X 1,75
109,79
65,55
63,02
18,71
9,37
1,12 X 1,75
176,94
65,55
63,02
23,80
9,37
1,12 X 1,75
220,50
97,15
76,20
23,81
91,44
97,15
349,35
Hard-wired regulators must be connected to a branch
circuit in accordance with local and national electrical
codes. Electrical connections are diagrammed in Figure 5.
Proper wiring is determined by the Figure indicated from the
regulator specifications in Table 3.
If operation from a 3-phase source is required, three
hard-wired regulators may be wired in delta as shown in
Figure 10.
Table 2 gives the proper jumper configurations for needed
input and output voltages. Table 2 also defines the regulator
connections in relation to the points diagrammed in Figure 6.
Fusing and wire gauge size are detailed in Table 3.
Note: Branch circuit protection must be located in the
primary of each transformer! Not in the three-phase
operation, fuses must be connected in the primary of each
unit, not in the three-phase lines.
On 7.5 and 10 kVA models, the terminal block is located in
the right unit. Use only the front or right side knockouts of
the right unit for conduit connections. On 15 kVA models,
the terminal block is located in the middle unit. Use only the
front knockouts of the middle unit for conduit connections.
Two or more models of the same rating may be connected
with their input and output in parallel. However, on models
smaller than 5 kVA, do not parallel both 208 V (X4-X5) and
240 VCT (X1-X2-X3). This may damage the
output windings.
2
Figure 5: 7500 VA and 10000–15000 VA
Electrical Connections
Primary Voltage
220-240
380-415
Secondary Voltage
110
120
220
240
MCR 50 Hz 7500 VA
5
Output
Figure 6.
3-Phase Connections
X2-X3
* Connect Per Table 2
X2-X5
220-X1-X3
240 X4-X5
Input Voltage
Required Circuit Protection / Minimum Gauge 90
110-120
220-240
380-415
110-120
3
1.5
0.8
1, 0
6
3
1
1, 0
10
6
1
1, 5
15
10
3
2, 5
30
15
10
6, 0
45
25
15
16,0
80
40
20
25,0
-
60
30
16,0
-
80
40
25,0
-
110
60
50,0
8
3
Interconnect
Connect Lines To
H1 to H3
H1 & H5
H2 to H5
H2 to H3
H1 & H4
Interconnect
Connect Lines To
X1 & X2 or X2 & X3
X4 & X2 or X5 & X2
X1 & X3
X4 & X5
6
Output Voltage
o
C WIRE
Minimum Gauge 90
o
C WIRE
220-240
380-415
110-120
220-240
1, 0
1, 0
1,0
1,0
1, 0
1, 0
1,0
1,0
1, 0
1, 0
1,0
1,0
1, 5
1, 0
1,5
1,0
2, 5
1, 5
4,0
1,5
4,0
2,5
6,0
2,5
10,0
4,0
16,0
4,0
6,0
-
25,0
10,0
10,0
-
35,0
16,0
16,0
-
45,0
25,0
9

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Sola Hevi Duty MCR and is the answer not in the manual?

Questions and answers

Summary of Contents for EGS Sola Hevi Duty MCR

  • Page 1 50 Hz Mini/Micro Computer Regulator (MCR) Installation Hard-wired regulators must be connected to a branch Installation and Operation Manual circuit in accordance with local and national electrical All regulators generate considerable heat and depend on the codes. Electrical connections are diagrammed in Figure 5. natural draft air circulation for adequate cooling.
  • Page 2 Operating Notes and Data Response Time An important advantage of the Sola principle of static magnetic regulation is its exceedingly fast response time Safety Notice compared with other types of AC regulators. Transient High voltages are present inside the MCR. Do not reach changes in supply voltage are usually corrected with 1-1/2 inside the unit while it is energized.
  • Page 3 X-ON Electronics Largest Supplier of Electrical and Electronic Components Click to view similar products for category: Gate Drivers Click to view products by manufacturer: Solahd Other Similar products are found below : 00028 00053P0231 8967380000 56956 CR7E-30DB-3.96E(72) 57.404.7355.5 LT4936 57.904.0755.0 5801-0903 5803-0901 5811-0902 5813-0901 58410 00576P0030 00581P0070 5882900001 00103P0020 00600P0005 00-9050-LRPP 00-9090-RDPP 5951900000 01- 1003W-10/32-15 LTILA6E-1S-WH-RC-FN12VXCR1 0131700000 00-2240 LTP70N06 LVP640 0158-624-00 5J0-1000LG-SIL 020017-13 LY1D-2-5S-AC120 LY2-0-US-AC120 LY2-US-AC240 LY3-UA-DC24 00-5150 00576P0020 00600P0010 LZNQ2M-US-DC5 LZNQ2-...