INSTALLATION AND MAINTENANCE INSTRUCTIONS
GENERAL
These instructions must be carefully read before any work involving products supplied by VALSTEAM ADCA
ENGINEERING S.A. is undertaken.
The installation procedure is a critical stage in a life of a steam trap and care should be taken to avoid damage
to the trap or equipment.
Warning!
- At start up, the presence of small particles in the water (dirt, scale, weld splatters, etc) may cause an imperfect
closure of the seat. If this occurs, proceed to an accurate cleaning.
- Do not touch the equipment without appropriate protection during working operation because it may conduct heat
if the used fluid is at high temperature.
- Before starting maintenance be sure that the equipment is not pressurized or hot.
- The equipments must be used within the working temperature and pressure limits laid down for them, otherwise
they may fail (refer to nameplate and/or IS- Information Sheet).
- Do not remove the nameplate attached to the equipment. Serial number and other useful information is stamped
on it.
INSTALLATION
- Before to install remove plastic covers placed on flanges or connection ends. The equipment has an arrow or
Inlet/Outlet designations. Be sure that it will be installed on the appropriate direction.
- Install the steam trap in the point of the system, where the condensate tends to collect. It must be installed with the
float lever in horizontal plane, so that it rises and falls vertically. An ADCA strainer should be installed upstream of
the trap.
BODY LIMITING CONDITIONS
FLANGED PN40 /
ANSI 300 lb *
ALLOWABLE
PRESSURE
37,1 bar
33,3 bar
30,4 bar
27,6 bar
PMO – Max. operating pressure
TMO – Max. operating temperature
*Acc. to EN1092-1:2018 ; **Acc. to EN1759-1:2004
Body limiting conditions PN40 or below, depending on the
type of connection adopted. Rating PN40 for thread, SW
and BW.
ADCA
VALSTEAM
FLOAT & THERMOSTATIC STEAM TRAPS
FLANGED
ANSI 150 lb **
RELATED
TEMPERATURE
ALLOWABLE
PRESSURE
15,4 bar
100 ºC
13,8 bar
200 ºC
12,1 bar
250 ºC
10,2 bar
300 ºC
32 bar;
250 ºC;
FLT32
We reserve the right to change the design and material of this product without notice.
MAX. DIFFERENTIAL PRESSURE
FLT32-4,5
4,5 bar
FLT32-10
10 bar
FLT32-14
14 bar
FLT32-21
21 bar
IMI 1.381 E 05.14

Advertisement

loading

Summary of Contents for VALSTEAM ADCA FLT32

  • Page 1 FLT32 GENERAL • These instructions must be carefully read before any work involving products supplied by VALSTEAM ADCA ENGINEERING S.A. is undertaken. • The installation procedure is a critical stage in a life of a steam trap and care should be taken to avoid damage to the trap or equipment.
  • Page 2: Maintenance

    When reassembling make sure that all gasket faces are clean and always use a new gasket. Tighten cover bolts uniformly in a diagonal sequence. • For further information refer to the relevant FLT32 brochure or consult our Sales Office. TROUBLESHOOTING If the malfunctions cannot be solved with the help of the following chart, please consult the manufacturer.
  • Page 3 Slow initial start up The air flow is too high for the trap. Install an additional air eliminator. Downsizing. Check maximum flow rate (during start-up) PARTS LIST FOR FLT32- STEAM TRAPS DN 1/2”- 1”, DN15-DN25 TRAP SIZE CODE DESIGNATION POS.NR. QTY.
  • Page 4 POS.NR. 1” 50±5 1” 50±5 1” 80±5 Remarks: Tighten cover bolts uniformly. PARTS LIST FOR FLT32 STEAM TRAPS DN 11/2”-2”, DN40-50 TRAP SIZE CODE DESIGNATION POS.NR. QTY. DN11/2”-2” A.92.2502.040 Valve, seat, float & gasket D.P.4,5bar 3, 4, 5, 6, 7 1Set DN11/2”-2”...
  • Page 5 Valsteam ADCA engineering. Health and safety data sheets regarding substances identified as hazardous or potentially hazardous must be provided with the information mention above.

This manual is also suitable for:

Flt32hc