PTAC Control Board Kit RSKP0013
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to know
the product better than the customer. This includes all safety
precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this
Instruction Manual. Pay special attention to all safety warnings.
Often during installation or repair it is possible to place yourself
in a position which is more hazardous than when the unit is in
operation.
Remember, it is your responsibility to install the product safely
and to know it well enough to be able to instruct a customer in its
safe use.
Safety is a matter of common sense...a matter of thinking before
acting. Most dealers have a list of specific good safety practices...
follow them.
The precautions listed in this Installation Manual are intended as
supplemental to existing practices. However, if there is a direct
conflict between existing practices and the content of this manual,
the precautions listed here take precedence.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION
Only personnel that have been trained to install, adjust, service
or repair (hereinafter, "service") the equipment specified in this
manual should service the equipment. The manufacturer will not
be responsible for any injury or property damage arising from
improper service or service procedures. If you service this unit,
you assume responsibility for any injury or property damage
which may result. In addition, in jurisdictions that require one or
more licenses to service the equipment specified in this manual,
only licensed personnel should service the equipment.
Improper installation, adjustment, servicing or repair of the
equipment specified in this manual, or attempting to install,
adjust, service or repair the equipment specified in this manual
without proper training may result in product damage, property
damage, personal injury or death.
PROP 65 WARNING
FOR CALIFORNIA CONSUMERS
Cancer and Reproduc�ve Harm
www.P65Warnings.ca.gov
IO-904B
under license to Goodman Company, L.P., Houston, TX, USA. All rights reserved.
1/2020
Installation Instructions
WARNING
WARNING
-
19001 Kermier Rd., Waller, TX 77484
is a registered trademark of Maytag Corporation or its related companies and is used
© 2015 - 2016, 2020 Goodman Company, L.P.
DESCRIPTION
Control board installation procedures are described in detail in
these instructions. Read and follow these instructions carefully
before replacing the control board. Failure to do so may result
in control board damage. Pages 3 through 5 are procedures for
programming the control board and the diagnostic codes for the
control board.
Important note:
Damage to the control board can occur from failure to disconnect
power supply or failure to set the master switch (located on the
control board) to OFF before removing the low voltage terminal
strip cover from an installed control board. Damage to this board
by not following these instructions is considered misuse and not
covered under either the standard unit warranty or any extended
service contract.
Important note:
All warranty replaced boards must be returned to the parts source
from which they were purchased to insure proper warranty credit.
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS
Before removing the new control board from the static wrap, it
is very important to discharge any static electricity. This can be
accomplished in two methods. Servicer can wear a ground strap
or by touching the metal chassis before replacing the board.
EXISTING CONTROL BOARD REMOVAL
PROCEDURES
1. Disconnect electrical power to the unit.
2. Remove front cover.
3. Remove the two mounting screws, one on each side of
control board cover. Lift the cover up to gain access to
the ribbon connector. Unplug ribbon connector from
control board and remove cover completely. Remove the
screw on right side of the control panel.
0140M00517-A
www.amana-ptac.com

Advertisement

loading

Summary of Contents for Amana Goodman RSKP0013

  • Page 1 Cancer and Reproduc�ve Harm www.P65Warnings.ca.gov 0140M00517-A 19001 Kermier Rd., Waller, TX 77484 www.amana-ptac.com is a registered trademark of Maytag Corporation or its related companies and is used IO-904B under license to Goodman Company, L.P., Houston, TX, USA. All rights reserved.
  • Page 2 4. If a remote thermostat or any low voltage accessory is being 9. If Reconnect the thermistors to the control board. The used, remove the low voltage pin connector from the low BLACK thermistor connects to the IAT BLACK terminal voltage terminal strip.
  • Page 3: Configuration Settings

    Remote Thermostat *Only load wires needed for accessories attached to unit. Figure 1 CONFIGURATION SETTINGS INITIAL BOARD PROGRAMMING Press and continue to hold down the plus (+) and minus The control can be configured to operate a wide range (-) keys at the same time. While holding the keys down, of options.
  • Page 4 CONFIGURATION SETTINGS CHART Configuration Configuration Feature Option Code Option Code Chassis Membrane * Interface Wired Thermostat Wireless Stat & 7-Button Locked Membrane do not use ID Fan Operation do not use Button present Revert to Cyclic Always run fan (even if Off) do not use Revert to Continuous PTC (Standard Cooler)
  • Page 5 CONFIGURATION SETTINGS CHART (CONT.) Configuration Configuration Feature Option Code Option Code Smart Vent Operation On only when ID fan runs On when ID fan runs & room occupied Runs continuously On when room is occupied Economizer Economizer with compressor assist Vent Dehumid Make-up Air Kit Operation May be on anytime...
  • Page 6 DIAGNOSTIC MAINTENANCE & STATUS REPORT The Diagnostic Maintenance & Status Report provides detailed information on PTAC control operation and operational status including present modes, failures, airflow restriction warnings, operating temperatures, and past failures. The lower right hand dot on the center display flashes in this mode.
  • Page 7: Diagnostic Codes

    DIAGNOSTIC CODES ERROR CODE STATUS DISPLAY SUGGESTED ACTION LIGHT Freeze Protection Engaged. The room temperature No Action required. This setting will disengage when the measured by the wireless remote thermostat or indoor room temperature rises above 43°F. ambient thermistor active sensor falls below 40°F. Front Desk switch is closed.
  • Page 8 WIRING DIAGRAMS Single motor TRANS FO RM E R RD33 BR34 BR34 GY21 VT12 BK37 BK37 LINE 1 HEATER 1 HEATER 2 LINE 2 COMPRESSOR E5 E6 CR11 ON / OFF GL W2 Y/W1 B GL W2 Y/W1 B IN1 COM IN2 IN1 COM IN2 MASTER SWITCH BLACK...
  • Page 9 WIRING DIAGRAMS Single Motor Power Vent Door HEATER 2 LINE 1 HEATER 1 LINE 2 CO MPRES S OR E5 E6 CR11 ON / OFF GL W2 Y/W1 B GL W2 Y/W1 B IN1 COM IN2 IN1 COM IN2 MAS TER S WITCH BLACK BLACK AUXILIARY...
  • Page 10 WIRING DIAGRAMS Single Motor Condensate Pump HEATER 2 LINE 1 HEATER 1 LINE 2 C OMPRES SO R E5 E6 CR11 ON / OFF IN1 COM IN2 IN1 COM IN2 GL W2 Y/W1 B GL W2 Y/W1 B MASTER S WITCH BLACK BLACK AUXILIARY...
  • Page 11 WIRING DIAGRAMS Dual Motor Wiring is subject to change. To MC TR 1 MOTOR MOTOR TR 1 TR 1 MOTOR MOTOR DANGER HIGH HEATER 1 HEATER 2 DANGER DANGER HIGH HIGH VOLTAGE VOLTAGE ALTERNATE REV. REV. LINE 1 LINE 1 HEATER 1 HEATER 1 HEATER 2...
  • Page 12 WIRING DIAGRAMS Dual Motor (continued) > > > > ON/OFF SWITCH OPTIONAL DEHUMIDIFICATION OPTIONAL ELECTRIC HEATER > > OPTIONAL OPTIONAL TRANSFER LIGHTING CONTROL To MC To MC Outdoor Motor Speed Selection Indoor Motor Speed Selection High Speed Low Speed High Speed Low Speed Model Starts With VSTM Tap...
  • Page 13 WIRING DIAGRAMS Dual Motor, 2 Speed Relay DUAL MOTOR, 2 SPEED RELAY * FOR A HEAT PUMP, THERMOSTAT USED REMOTE THERMOSTAT ON A STRAIGHT OPERATION COOL UNIT ** GL - LOW SPEED COOLING UNIT GH - HIGH SPEED RCCF W / ELECTRIC HEAT FUNCTION CONNECT R TO:...
  • Page 14 WIRING DIAGRAMS Dual Motor No Speed Relay Single Speed Condenser Fan DUAL MOTOR, NO SPEED RELAY SINGLE SPEED CONDENSER FAN * FOR A HEAT PUMP, THERMOSTAT USED REMOTE THERMOSTAT ON A STRAIGHT OPERATION COOL UNIT ** GL - LOW SPEED COOLING UNIT GH - HIGH SPEED RCCF...
  • Page 15 WIRING DIAGRAMS Dual Motor No Speed Relay Single Speed Condenser Fan 24VAC TRANSFORMER 12VA CLASS 2 ONLY LOAD...
  • Page 16 WIRING DIAGRAMS Dual Motor No Speed Relay Single Speed Condenser Fan 24VAC TRANSFORMER 12VA CLASS 2 ONLY LOAD...
  • Page 17 THIS PAGE INTENTIONALLY LEFT BLANK...
  • Page 18 THIS PAGE INTENTIONALLY LEFT BLANK...
  • Page 19 THIS PAGE INTENTIONALLY LEFT BLANK...
  • Page 20: Customer Feedback

    Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX, USA. All rights reserved. 19001 Kermier Rd. • Waller, TX 77484 • www.amana-ptac.com © 2015 - 2016, 2020 Goodman Company, L.P.