Automationdirect.com Productivity2000 P2-08TRS Manual

Relay output

Advertisement

Quick Links

Output Specifications

Outputs per Module
(CE)
Operating Voltage Range
(Tolerance)
(UL)
Output type
AC Frequency
Maximum Output Current
@ Temp
Minimum Load Current
Maximum Inrush Current
OFF to ON Response
ON to OFF Response
Status Indicators
Commons
External Fuses (user supplied)
Document Name
P2-08TRS-DS
Copyright 2016, AutomationDirect.com Incorporated/All Rights Reserved Worldwide
Sales 800-633-0405
8
6.25 - 24 VDC (-15% / + 20%)
6 - 120 VAC (-15% / + 10%)
120VAC / 30VDC, 4A / point
6 Relays, FORM A (SPST)
2 Relays, FORM C (SPDT)
47 - 63 Hz
4A / point @ 60°C for both AC and DC
2A / point if used with ZIPLink Cable
5mA @ 5VDC
4A for 10ms
m 10ms
m 10ms
Logic Side (8 points)
8 Isolated (1 point / common)
6.3A Max
Edition/Revision
Date
2nd Ed.
9/5/2019
P2-08TRS Relay Output
The P2-08TRS high-current isolated relay output
module provides eight 4A surge-protected
outputs for extended relay life. Module offers
both normally open and normally closed relay
contacts for use with the Productivity2000
system.
Output Specifications .....................1
Module Installation .........................2
Qr Code ........................................2
Hot Swap Information .....................2
Wiring Options ................................3
Warning ..........................................4
Typical Relay Life ...........................4
Removable Terminal Block
Specifications .................................4
General Specifications ...................4
Terminal Block sold separately, (see wiring options on page 3).
Warranty: Thirty-day money-back guarantee. Two-year limited replacement.
(See www.productivity2000.com for details).
www.productivity2000.com
®
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Productivity2000 P2-08TRS and is the answer not in the manual?

Questions and answers

Summary of Contents for Automationdirect.com Productivity2000 P2-08TRS

  • Page 1 General Specifications ....4 Document Name Edition/Revision Date Terminal Block sold separately, (see wiring options on page 3). P2-08TRS-DS 2nd Ed. 9/5/2019 Warranty: Thirty-day money-back guarantee. Two-year limited replacement. Copyright 2016, AutomationDirect.com Incorporated/All Rights Reserved Worldwide (See www.productivity2000.com for details). Sales 800-633-0405 www.productivity2000.com...
  • Page 2 Before attempting to use the hot-swap feature, be sure to read the hot-swap topic in the programming software’s help file or our online documentation at AutomationDirect.com for details on how to plan your installation for use of this powerful feature. www.productivity2000.com...
  • Page 3 P2-08TRS Wiring Diagram and Schematic Wiring Options ZIPLink Feed Through Modules and Cables¹ User Supplied External Fuse ZL-RTB20 ZL-RTB20-1 6.3 A ZL-RTB20-1 0.5 m (1.6 ft) cable ZL-RTB20 ZL-P2-CBL18 1.0 m (3.3 ft) cable ZL-P2-CBL18-1 2.0 m (6.6 ft) cable ZL-P2-CBL18-2 Terminal Block with pigtail cable 1.0 m (3.3 ft) cable...
  • Page 4 >10MΩ @ 500VDC This publication is based on information that was available at the time it was print- ed. At AutomationDirect.com® we constantly strive to improve our products and services, Heat Dissipation so we reserve the right to make changes to the products and/or publications at any time...

Table of Contents