Simple Parts Check Method - Mitsubishi Electric PUH-P8MYA Technical & Service Manual

Heat pump, single and twin /triple/four, air-cooled, packaged
Hide thumbs Also See for PUH-P8MYA:
Table of Contents

Advertisement

[4] Simple parts check method

• PUH-P8MYA/P10MYA
Part name
Thermistor (TH1) <Liquid
temperature detection>
Thermistor (TH2)
<Dischargetemperature
detection>
Thermistor (TH3) <Condenser/
evaporater temperature
detection>
Fan motor
Red
Thermal protector
trip temperature
135 ± 5˚C : ON
88 ± 5˚C : OFF
White
Blue
Compressor
Disconnect the connector and measure the resistance value with a multimeter.
(Ambient temperature 10 ˚C to 30 ˚C)
TH1, 3
4.3 kΩ~9.6 kΩ
TH2
160 kΩ~410 kΩ
Measure the resistance value across the terminals with a multimeter. (Winding
temperature 20 ˚C)
Motor lead wire
Between 2 phases
Black
Measure the resistance value across the terminals with a multimeter. (Winding
temperature 20 ˚C)
Normal
PUH-P8MYA
Each phase 1.574 Ω
PUH-P10MYA
Each phase 1.263 Ω
Judgment instructions
Normal
Abnormal
Open or short
(Based on thermistor characteristic table (next page))
Normal
Abnormal
45.5 Ω
Open or short
Abnormal
Open or short
Open or short
–35–

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Puh-p10mya

Table of Contents