Preset Single Register - Function Code 06 - ABB COMMANDER 100 Operating Manual

Modbus (rtu) communications option
Table of Contents

Advertisement

...5 MODBUS FUNCTIONS
5.4
Preset Single Register – Function Code 06
5.4.1
Preset Single Register Query
The Preset Single Register Query modifies the contents of a holding register.
Note. Function codes 05, 06 and 16 are the only messages that are
recognized as valid for broadcast.
Example. Write the value 500 to holding register address 25 (proportional band 1
– heat) in slave 01.
Note. To write to a register, its offset address (one less than the register
number) must be used, e.g. to write to register 25, the offset address 24 (18H)
is transmitted.
Address
Function
01
06
5.4.2 Preset Single Register Response
The response to a Preset Single Register Response requests is to retransmit the
query message after the register has been altered.
Example
Address
Function
01
06
12
Register Register
Offset
Offset
High
Low
00
18
Register Register
Offset
Offset
High
Low
00
18
Data
Data
Value
Value
High
Low
01
F4
Data
Data
Value
Value
High
Low
01
F4
Error
Check
(CRC-16)
Field
09
DA
Error
Check
(CRC-16)
Field
09
DA